background image

PROBLEM

POSSIBLE CAUSE

ACTION

High Discharge Pressure

Warm inlet water or insufficient
water flow through the condenser

Gas outlet valve on the condenser
not completely open

Overcharged refrigerant

Condenser plates coated with scale,
slime, corrosion

Suction pressure is higher than
standard

Open the valve

Check the valves, capillary tubes and strainer. Replace,
if necessary.

Purge the refrigerant.

Clean the condenser water plates with chemical cleaner

See "High Suction Pressure".

Low Discharge Pressure

Too much water flowing through the
condenser or water is too cold

Insufficient refrigerant charge

Leakage from the condenser gas
outlet valve

Liquid refrigerant flooding back from
the water cooler, causing oil to
foam.

Suction pressure is lower than
standard

Adjust the water cock or the regulating valve.
Check the operation of cooling tower.

Add refrigerant.

Check to determine how long it takes to balance high
and low.

Check the operation and adjustment of the expansion
valve. Check the feeler bulb is securely connected to the
suction pipe and that it is completely insulated.
Inlet water temperature is lower than the limited
temperature.

See "Low Suction Pressure"

High Suction Pressure

High discharge pressure

Refrigerant overcharged

Liquid refrigerant flooding back from
the water cooler

Leakage from the condenser gas
outlet valve

Insufficient insulation for the chilled
water piping

See "High Discharge Pressure"

Purge the refrigerant

Check the operation and adjustment of the expansion
valve. Check the feeler bulb is securely connected to the
suction pipe and completely insulated.
Inlet chilled water temperature to the unit is considerably
higher than the standard temperature.

Check the condenser gas outlet valve

Check the insulation of the piping

Low Suction Pressure

Condenser liquid outlet valve not
completely open

Expansion valve not properly
adjusted or faulty.

Inlet chilled water temperature is
considerably lower than standard
temperature.

Insufficient refrigerant charge

Excessive oil circulating in the
system

Insufficient chilled water flow
through the water cooler.

Low discharge pressure

Scales on water cooler plates

Open the valve.

Adjust for correct superheat. Check for loss of refrigerant
in the feeler bulb.

Check the insulation specifications

Add refrigerant

Check the oil charge

Check the chilled water piping lines for pressure loss.

Adjust the water shutoff valve

Clean the plates

8

-

2

035-21786-100 Rev. 1 (0909)

Содержание York YCRE 040

Страница 1: ...YCRE040 YCRE100 INSTALLATION COMMISSIONING OPERATION MAINTENANCE Form 035 21786 100 0909 Revision 1 R407C Aspak WATER AND REMOTE AIR COOLED LIQUID CHILLERS WITH SCREW COMPRESSORS STYLE B YCSE 134 320K...

Страница 2: ......

Страница 3: ...s 3 2 3 5 Weight Distribution Centre of Gravity 3 2 4 INSTALLATION 4 1 Location Requirements 4 1 4 2 Installation of Vibration Isolators 4 1 4 3 Pipework Connection 4 1 4 4 Water Treatment 4 2 4 5 Pip...

Страница 4: ...9 3 Operating Limitations 9 4 9 4 Physical Data 9 5 9 5 Electrical Data 9 6 9 6 Sound Data 9 7 9 7 Clearances and Foundations 9 8 9 8 Dimensions 9 9 10 SPARE PARTS 10 1 Renewal Parts List 10 1 10 2 R...

Страница 5: ...ecified All warranty claims must specify the unit model serial number and order number These details are printed on the unit identification plate fitted on the outer edge of the options panel The unit...

Страница 6: ...1 6 Misuse of Equipment Suitability for Application The unit is intended for cooling water or glycol solutions and is not suitable for purposes other than those specified in these instructions Any us...

Страница 7: ...ata tables provided High Temperature and Pressure Cleaning High temperature and pressure cleaning methods e g steam cleaning should not be used on any part of the pressure system as this may cause ope...

Страница 8: ...limits Recommended limit 1000 ppm v v 8 hr TWA Stability Not specified Conditions to avoid Use in presence of naked flames red hot surfaces and high moisture levels Hazardous reactions May react viole...

Страница 9: ...le ester and Lubricating oil additive COMPONENT Polyole ester 99mass Lubricating oil additive 1mass OSHA PEL ACGIH TLV Physical Characteristics Boiling Point Not applicable Vapor Pressure mmHg Not app...

Страница 10: ...d to enter open waters or ground water Waste Disposal Method Waste material may be incinerated under conditions which meet all Federal state and local environmental control regulations Precautions to...

Страница 11: ...tion and provide a capacity control range from 15 to 100 per compressor using a continuous function slide valve 2 3 Refrigerant Circuits Depending on model size one or two independent refrigerant circ...

Страница 12: ...cations protocol Refer to HARC Lonworks data sheet 035 22383 000 Multi Unit Sequencer CSC 5S Provides individual control and monitoring for up to 8 units within the air conditioning system This allows...

Страница 13: ...IGERANT DESIGN SERIES Y York kW S Standard Unit 5 0 380 415 3 50 N C Chiller Standard Units B R407C Refrigerant B Design Level S S Screw 040 050 060 R Remote Air 080 100 Cooled Screw E European YCSE10...

Страница 14: ...6 Stop Valve Refrigerant Charge Point 21 Thermistor Evaporator Water Inlet 7 Stop Valve 22 Thermistor Evaporator Water Oulet 8 Drier 23 Thermistor Evaporator Water Oulet 9 Sight Glass 24 Thermistor C...

Страница 15: ...orator 9 Sight Glass 26 Thermistor Evaporator Water Inlet 10 Electronic Expansion Valve 27 Thermistor Evaporator Water Oulet 11 Evaporator 28 Thermistor Evaporator Water Oulet 12 Stop Valve Option 29...

Страница 16: ...ermistor Suction 5 Remote Condenser Field Supplied 19 Thermistor Discharge 6 Stop Valve 20 Thermistor Evaporator 7 Drier 21 Thermistor Evaporator Water Inlet 8 Solenoid Valve 22 Thermistor Evaporator...

Страница 17: ...t the unit is periodically inspected during storage 3 2 Inspection Remove any transit packing and inspect the unit to ensure that all components have been delivered and that no damage has occurred dur...

Страница 18: ...pport both outer frames Ensure the unit is balanced evenly on all the rollers 3 4 Lifting Weights For details of weights and weight distribution refer to Section 9 3 5 Weight Distribution Centre of Gr...

Страница 19: ...transmitted vibration levels are required optional anti vibration isolators can be supplied loose for site installation 4 2 Installation of Vibration Isolators An optional set of spring and cage or ru...

Страница 20: ...ed supplied independently and controlled by an ambient temperature thermostat set to switch on at 3 C above the freezing temperature of the liquid Any debris left in the water pipework between the str...

Страница 21: ...m and has discharge capacity required by the relevant standard It is recommended that each valve should be piped to the exterior of the building so that when the valve is activated the release of high...

Страница 22: ...dampers on the tower or to control condenser flow using a three way bypass valve The aim is to maintain a stable discharge pressure as low as possible but at least 5 0 bar above suction pressure This...

Страница 23: ...shing will occur in the liquid line to the unit or in the filter drier and liquid valves on the unit itself Liquid subcooling should be 4 C to 10 C on arrival at the unit It is important to ensure tha...

Страница 24: ...Install the connection piping and accessories with soldered brazed or flare connections Install oil traps and liquid loops in accordance with the piping arrangement digrams Piping length and lift mus...

Страница 25: ...CRE Unit YCRE Unit Receiver Receiver Receiver Receiver Oil Trap Oil Trap Oil Trap Remote Condenser Liquid Loop Liquid Loop Liquid Loop Remote Condenser Remote Condenser Remote Condenser At each 10 met...

Страница 26: ...replaced by a non metallic gland plate with due regard given to sealing the panel to IP2X All sources of supply to the unit must be taken via a common point of isolation not supplied by York Voltages...

Страница 27: ...Output signal Only cycle N 1 19 In case of individual indication without Remote Control Switch 20 Customer wiring 21 Force compressor load 22 Setting of low voltage control NOTE 1 All the setting shal...

Страница 28: ...gnal Only cycle N 1 17 In case of individual indication without Remote Control Switch 18 Customer wiring 19 Force compressor load 20 Setting of low voltage control NOTE 1 All the setting must be perfo...

Страница 29: ...e valves on all systems Compressor oil Check the compressor oil for correct level at the oil level sight glass Full at commission startup and no less than half full during normal operation Isolation p...

Страница 30: ...ll be a delay before the compressor starts See the operating sequence chart in Section 6 Be ready when the compressor starts to switch off the unit immediately if any unusual noises or other adverse c...

Страница 31: ...o Alarm Codes tables for further details 6 4 Shutdown The unit can be stopped manually at any time by pressing the system OFF switch SW2 To prevent damage to the unit the control supply to the compres...

Страница 32: ...tion of the display when Parameter Settings mode is selected To return to Normal mode press and hold SW3 again for 3 seconds Press SW3 p or SW4 q to scroll through the paramaeter settings The display...

Страница 33: ...n only q p Chilled 2nd Setting Water Outlet Temperature Cooling C 7 C q p Hot Water 2nd Setting Outlet Temperature Heating C 7 C YCSE Heat Pump option only q p C 1 L D D U P C 2 L D D n U C 2 L D D d...

Страница 34: ...cally toggles E between the parameter and the parameter value Press SW3 p or SW4 q to switch btween Hot Water Temperature Setting YCSE heat pump option only and Chilled Water Temperature Setting Press...

Страница 35: ...ort Communication Error between Chiller and Remote Control if CSC 5S connected C1 27 C2 27 Failure of Discharge Gas Pressure Sensor Open Short Excessive High Water Temperature C1 26 C2 26 Failure of S...

Страница 36: ...quid Temp C Cooling Liquid Brine Glycol DSW4 4 ON Alarm Cn Ln immediately when Ps 0 5bar If Td 140 C for 3 secs alarm Cn 6n Starts loading down at 26bar Pressure Control Suction Gas Ps N A Freeze Prot...

Страница 37: ...LS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS OPN OPN CLS CLS CLS CLS N 2 CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS CLS OPN CLS CLS CLS CLS Power Supply Lamp OFF ON ON ON ON...

Страница 38: ...Outlet Temperature Setting Switch heat pump option only 5 RSW 4 Hot Water Outlet Temperature Setting Switch heat pump option only 4 RSW 5 Not Used N A RSW 6 Not Used N A RSW 7 Not Used N A RSW 8 Neutr...

Страница 39: ...Cooling Only OFF or Heat Pump Enabled ON OFF DSW4 4 Water OFF or Brine Glycol ON OFF DSW4 2 DSW4 6 DSW4 7 Not Used ON DSW4 3 DSW4 5 DSW4 8 Not Used OFF DSW5 1 DSW5 2 Temperature Band for Stop Setting...

Страница 40: ...DSW5 2 OFF The settings for DSW5 1 DSW5 2 are as follows Temperature Band for Restart Setting Switch DSW5 3 DSW5 4 2 C is factory default DSW5 3 ON DSW5 4 OFF The settings for DSW5 3 DSW5 4 are as fo...

Страница 41: ...ates in cooling mode only or if the optional heat pump mode is enabled The setting for DSW4 1 is as follows Manual Set Switch B DSW4 4 This switch defines the unit chilled liquid as either water or br...

Страница 42: ...fitted set SW8 to the down position for HEATING operation Note DSW4 1 must be in the ON position for heat pump operation to be enabled Selection Switch for Local Remote Operation SW6 Factory default...

Страница 43: ...on a daily basis by the operator customer Please note that the units are not generally user serviceable and no attempt should be made to rectify faults or problems found during daily checks unless com...

Страница 44: ...Condenser YCSE Only Check water flow Check water pH glycol strength Check water pressure drop Power Control system general Check panel condition Check all wiring connections for tightness Main power s...

Страница 45: ...Shortage of chilled water flow Air in water circuit Check for excessively low setting of the chilled water tempearture switch Check for malfunction of the thermistor Replace if necessary Check chille...

Страница 46: ...e limited temperature See Low Suction Pressure High Suction Pressure High discharge pressure Refrigerant overcharged Liquid refrigerant flooding back from the water cooler Leakage from the condenser g...

Страница 47: ...9 TECHNICAL DATA 9 1 Flow Rate and Pressure Drop Graphs 9 1 035 21786 100 Rev 1 0909 YCSE YCRE Evaporator Water Pressure Drop YCSE Condenser Water Pressure Drop...

Страница 48: ...9 2 Performance Graphs 9 2 035 21786 100 Rev 1 0909 Discharge Pressure Water Cooled Condenser Discharge Pressure Air Cooled Condenser...

Страница 49: ...9 3 035 21786 100 Rev 1 0909 Suction Pressure Evaporator Sub cooling Temperatures...

Страница 50: ...Temperature Maximum Refrigerant Side Pressure 510 610 420 Minimum Ambient Air Temperature 46 Power Supply Voltage 400V 3 50 Hz nominal Recommended Minimum System Water Volume 2 30 730 360 to 440 5 5 t...

Страница 51: ...ant circuits Refrigerant Charge Circuit 1 Circuit 2 1 kg 12 14 16 18 14 14 Oil Charge Circuit 1 Circuit 2 2 litre 6 6 6 6 6 6 Number of Compressors Type Capacity Control Number of Evaporator Type Wate...

Страница 52: ...voltage 90 of rated voltage Unit capacity 100 at maximum operating condtions Nominal Running Conditions YCSE Start up Amps 3 Maximum Running Conditions kW Amps 1 at 400 V Amps 2 at 400V 040 34 59 77...

Страница 53: ...r EN 292 1991 1 metre from Control Panel and 1 5 metres from Ground Level in dB A 100 72 080 71 050 69 060 71 YCSE 040 68 Mean Sound Power Band Levels Frequency Hz SPL SWL 63 125 250 500 1000 2000 400...

Страница 54: ...9 7 Clearances and Foundations 9 8 035 21786 100 Rev 1 0909...

Страница 55: ...9 8 Dimensions 9 9 035 21786 100 Rev 1 0909 Model YCSE 040...

Страница 56: ...9 10 035 21786 100 Rev 1 0909 Model YCSE 050...

Страница 57: ...9 11 035 21786 100 Rev 1 0909 Model YCSE 060...

Страница 58: ...9 12 035 21786 100 Rev 1 0909 Model YCSE 080...

Страница 59: ...9 13 035 21786 100 Rev 1 0909 Model YCSE 100...

Страница 60: ...9 14 035 21786 100 Rev 1 0909 Model YCRE 040...

Страница 61: ...9 15 035 21786 100 Rev 1 0909 Model YCRE 050...

Страница 62: ...9 16 035 21786 100 Rev 1 0909 Model YCRE 060...

Страница 63: ...9 17 035 21786 100 Rev 1 0909 Model YCRE 080...

Страница 64: ...9 18 035 21786 100 Rev 1 0909 Model YCRE 100...

Страница 65: ...000 YCSE YCRE Wiring Amendments Flow Switch Identification T33 34 035 21904 000 YCSE YCRE Wiring Amendments Force Compressor Loading Incorrect 035 21906 000 Sheet 5 10 1 035 21786 100 Rev 1 0909 YCSE...

Страница 66: ...This Page Intentionally Blank 10 2 035 21786 100 Rev 1 0909...

Страница 67: ...nger section of the systems If no isolation valves are installed it may be necessary to drain the complete system If glycol or similar solutions have been used in the water system or chemical additive...

Страница 68: ...Subject to change without notice ALL RIGHTS RESERVED Form 035 21786 100 Rev 1 0909 www johnsoncontrols com...

Отзывы: