 1.  Record the liquid line pressure and its correspond-

ing  temperature,  liquid  line  temperature  and 

subcooling below:

 

  

 

 

  SYS 1    SYS 2

 

Liq Line Press =  _______  _______ PSIG

 

Saturated Temp =  _______  _______ °F

 

Liq Line Temp =  _______  _______ °F

 

Subcooling =  _______  _______ °F

After the subcooling is verified, the suction superheat 

should be checked. The superheat should be checked only 

after steady state operation of the chiller has been estab-

lished, the leaving water temperature has been pulled down 

to the required leaving water temperature, and the unit is 

running in a fully loaded condition. Correct superheat set-

ting for a system is 10°F - 15°F (5.56°C - 8.33°C) 18” (46 

cm) from the cooler.

Superheat should typically be set for no less than 10°F 

with only a single compressor running on a circuit.

 

The superheat is calculated as the difference between 

the actual temperature of the returned refrigerant gas in 

the suction line entering the compressor and the tem-

perature corresponding to the suction pressure as shown 

in a standard pressure/temperature chart.

Example:

 

Suction Temp = 

46°F

 

minus Suction Press

  60 PSIG converted to Temp   - 34°F

 

Superheat =   12°F 

When adjusting the expansion valve (TXV only), the 

adjusting screw should be turned not more than one 

turn at a time, allowing sufficient time (approximately 

15 minutes) between adjustments for the system and the 

thermal expansion valve to respond and stabilize.

The EEV is non-adjustable. Superheat 

setpoint  is  programmable  from  the 

keypad.

Assure that superheat is set at a minimum of 10°F (5.56°C) 

with a single compressor running on each circuit.     

 2.  Record the suction temperature, suction pressure, 

suction saturation temperature, and superheat of 

each system below:

 

 

 SYS 1   SYS 2

 

Suction Temp =  _______  _______ °F

 

Suction Pressure =  _______  _______ PSIG

 

  Saturation Temp =  _______  _______ °F

 

Superheat =  _______  _______ °F

LEAk ChECkIng

 1.  Leak check compressors, fittings, and piping to 

ensure no leaks.

If the unit is functioning satisfactorily during the initial 

operating period, no safeties trip and the compressors 

cycle to control water temperature to setpoint, the chiller 

is ready to be placed into operation.