24
Flow %
70
80
90
100
110
120
130
Correction in °C on real
temperature of air going
to the outdoor coil
5
3
1.5
0
-1
-2
-2.5
Flow %
80
90
100
110
120
130
Total capacity
0.960 0.980
1
1.016 1.032
1.046
Sensible capacity
0.945 0.973
1
1.038 1.075
1.118
Comp. absorbed
power
0.980 0.990
1
1.009 1.017
1.025
Flow %
70
80
90
100
110
120
130
Correction in °C on
real temperature
of air intake to the
outdoor unit
-2
-1.5
-0.5
0
0.5
1
1.2
Correction of the real temperature of intake air to the outdoor
unit for flows that differ from the nominal values.
Nominal performances
Correcting factors
Correcting factors for cooling capacities
Cooling capacity correcting factors for flows that differ from
the nominal flows of the indoor coil.
Correction of the real temperature of air intake to the outdoor
coil for flows that differ from the nominal values.
Correcting factors for the heating capacities
Outdoor unit
Indoor unit
Summer
Winter
Model
Air flow m³/h
Model
Air flow m³/h
Cooling
capacity W
Consump-
tion (W)
E.E.R.
Heating
capacity W
Consump-
tion (W)
C.O.P.
VCH 20A
6 235
VIR 25A
4 590
16 800
5 900
2.85
21 500
5 680
3.79
VCH 25A
6 235
VIR 25A
4 590
20 600
7 480
2.75
23 200
6 840
3.39
VCH 30A
11 975
VIR 40A
7 500
28 700
10 250
2.80
32 300
9 950
3.25
VCH 40A
11 975
VIR 40A
7 500
32 400
12 810
2.53
39 300
12 870
3.05
VCH 45A
17 250
VIR 45A
9 000
43 500
14 810
2.94
47 400
13 750
3.45
VCH 60A
20 340
VIR 60A
10 500
54 100
20 860
2.60
53 000
20 000
2.80
VCH 75A
25 200
VIR 75A
13 700
76 100
29 210
2.61
77 700
27 560
2.82
VCH 90A
25 200
VIR 90A
16 000
87 300
34 920
2.50
89 900
33 190
2.71
Indoor unit air
intake tempe-
rature °C DB
Outdoor unit air temperature °C WB
14
10
6
0
-8
23
1.20
1.04
0.96
0.77
0.58
20
1.25
1.10
1.00
0.80
0.69
17
1.30
1.13
1.04
0.83
0.63
Voltage
Interconnecting
pipes length
Summer
Winter
Outdoor temp. °C
Indoor temp. °C
Outdoor temp. °C
Indoor temp. °C
DB
WB
DB
WB
DB
WB
DB
WB
400
7.5 metre
35
24
27
19
7
6
20
12
Test conditions
Содержание York VCH 20A
Страница 17: ...17 Technical characteristics General dimensions mm VCH 20A and 25A ...
Страница 18: ...18 General dimensions mm VCH 30A and 40A ...
Страница 19: ...19 General dimensions mm VCH 45A and 60A ...
Страница 20: ...20 General dimensions mm VCH 75A and 90A ...
Страница 21: ...21 General dimensions mm VIR 25A VIR 40A ...
Страница 22: ...22 General dimensions mm VIR 45A and 60A VIR 75A and 90A ...
Страница 23: ...23 Cooling diagram Variant chart ...
Страница 31: ...31 Electric diagram VCH 20 25 30 40A 400 3 50 ...
Страница 32: ...32 Electric diagram VCH 45 60 75 90A 400 3 50 ...
Страница 33: ...33 Electric diagram VCH 45 60 75 90A 400 3 50 ...
Страница 34: ...34 Configuration of switches ...
Страница 43: ...43 Wiring diagram VIR 45 90 ...
Страница 48: ...48 Wiring diagram Heater 10 15kW 400 3 50 VIR 25A 40A 45A and 60A ...
Страница 49: ...49 Wiring diagram Heater 20 30 40kW 400 3 50 VIR 40A 45A 60A 75A and 90A ...
Страница 59: ...59 VCH 20A to 40A VCH 45 to 90A ...
Страница 61: ...61 Wiring diagrams ...
Страница 62: ...62 Wiring diagrams ...
Страница 69: ...69 Wiring diagram ...
Страница 71: ......
Страница 72: ...www johnsoncontrols com ...