background image

JOHNSON CONTROLS

14

FORM 160.43-NM4 

ISSUE DATE: 11/12/2012

SECTION 3 - TESTING AND ADJUSTMENTS

CUTOUT SETPOINT TESTING AND 

CALIBRATION

The LPCO CUTOUT setpoint is calibrated first, then 

the switch DEADBAND is set.
CUTOUT on pressure fall: refer to Table 1 for setpoint.

1. 

Remove enclosure cover first by removing the one 

captive screw located on the front of the cover Re-

fer to Figures 2 and 3.

2.  Disconnect the three wires (47, 48 and 49) from 

the LPCO switch terminals and secure out of the 

way.

3.  Connect an Ohm meter, to measure continuity, 

between the LPCO switch Common and Normal-

ly Open terminals. At atmospheric pressure the 

switch contacts are made between the Common 

and Normally Open terminals and open between 

the Common and Normally Closed terminals.

4.  Using the controlled vacuum source, slowly lower 

the pressure to the LPCO toward vacuum. Note 

at what exact vacuum pressure the switch trans-

fers opening between the Common and Normally 

Open terminals. As the pressure falls below the 

control CUTOUT setpoint the switch transfers 

to be made between the Common and Normally 

Closed terminals and open between the Common 

and Normally Open terminals.

5.  Carefully and slowly, loosen the hose connection 

at the vacuum source and allow the pressure in the 

line to the LPCO slowly rise to atmospheric pres-

sure. Retighten the hose connection at the vacuum 

source.

6.  If the CUTOUT setpoint noted in step 4 is below 

or above the allowable CUTOUT setpoint range 

called out in Table 1, then make an adjustment to 

the setpoint screw. The set point adjusting screw, 

labeled “A” in Figure 4, is located beneath the 

switch and is turned to adjust the set point. Use 

a 1/4 inch open-end wrench to keep plunger, la-

beled “B” in Figure 4, from turning. Using a 3/16 

inch open-end wrench, turn the adjustment screw 

towards the right (counter-clockwise) to increase 

set point (towards full vacuum) or towards the left 

(clockwise) to decrease set point (towards 0 psig).

7.  Repeat steps 4, 5, and 6 until the noted CUT OUT 

setpoint is within the allowable range.

8. 

Once the CUTOUT set point is verified or cali

-

brated, then proceed to the switch DEADBAND 

calibration procedure.

SWITCH DEADBAND TESTING AND 

CALIBRATION

CUTIN on pressure rise: CUTIN equals CUTOUT plus 

DEADBAND settings. Refer to Table 1 for settings.

1.  Connect an Ohm meter, to measure continuity, 

between the LPCO switch Common and Normal-

ly Open terminals. At atmospheric pressure the 

switch contacts are made between the Common 

and Normally Open terminals and open between 

the Common and Normally Closed terminals.

2.  Using the controlled vacuum source, slowly low-

er the pressure to the LPCO toward vacuum. As 

the pressure falls below the control CUTOUT 

setpoint the switch transfers to be made between 

the Common and Normally Closed terminals and 

open between the Common and Normally Open 

terminals.

3.  Carefully and slowly, loosen the hose connection 

at the vacuum source and allow the pressure in the 

line to the LPCO to rise very slowly toward atmo-

spheric pressure. Note at what exact vacuum pres-

sure the switch transfers, again, closing between 

the Common and Normally Open terminals. As 

the pressure rises above the control CUTIN (CU-

TIN equals cutout plus deadband settings) the 

switch transfers to be made between the Common 

and Normally Open terminals and open between 

the Common and Normally Closed terminals. Al-

low the pressure to rise to atmospheric. Retighten 

the hose connection at the vacuum source.

4.  If the CUTIN setting noted in step 3 is below or 

above the allowable DEADBAND range called 

out in Table 1, then make an adjustment to the 

switch DEADBAND setting. To adjust the dead-

band, turn the adjustment wheel on the underside 

of the switch, labeled “C” in Figure 4, using the 

switch Ground (green) mounting screw as an in-

dex. As the letters advance, the deadband widens. 

Turn the adjustment wheels towards the right 

(counterclock wise) to decrease deadband (to-

wards letter “A”) or towards the left (clockwise) 

to increase deadband (towards letter “F”).

5.  Repeat steps 3, 4, and 5 until the noted CUTIN is 

within the allowable DEADBAND setting range.

Содержание York 366-70487

Страница 1: ...RS STYLE B AND C CONTROL CENTERS 366 70488 366 70487 AND 366 73582 LOW PRESSURE CUTOUT CONTROL P N 025 45742 000 INSTALLATION AND MAINTENANCE Supersedes 160 43 NM4 1206 Form 160 43 NM4 1112 035 21593...

Страница 2: ...als This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question SAFETY SYMBOLS The following symbols are used i...

Страница 3: ...icy for con tinuous product improvement the information con tained in this document is subject to change without notice Johnson Controls makes no commitment to update or provide current information au...

Страница 4: ...JOHNSON CONTROLS 4 FORM 160 43 NM4 ISSUE DATE 11 12 2012 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 5: ...ting 025 45742 LPCO Control 9 Pressure Connection Piping 10 Wiring 11 SECTION 3 TESTING AND ADJUSTMENTS 13 Tools Needed 13 Secure Chiller From Operation 13 Connect LPCO Pressure Connection To A Calibr...

Страница 6: ...JOHNSON CONTROLS 6 FORM 160 43 NM4 ISSUE DATE 11 12 2012 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 7: ...tments LPCO controls 025 45742 are vacuum switches which are negative gauge pressure controls that operate at a predetermined constant pressure below atmospheric This means that the absolute pressure...

Страница 8: ...At atmospheric pressure the switch contacts are made between the Common and Normally Open terminals and open between the Common and Normally Closed terminals As the pressure falls below the control C...

Страница 9: ...rated in a vertical position with the switch up and pressure con nection down The controls are surface mounted using two mounting ears with holes for 10 screws on either side of the control bracket pl...

Страница 10: ...o pressure connection tight enough to ensure a leak free seal 2 Installing kit supplied Capillary Tube 48 in YORK p n 026 45010 000 a Ensure 1 4 in flare mating surfaces are clean and free of debris o...

Страница 11: ...itch bracket Refer to Figure 3 The three switch terminals are clearly labeled COM MON NORMALLY OPEN and NORMALLY CLOSED Refer to Figures 3 and 4 1 Remove enclosure cover first by removing the one capt...

Страница 12: ...res 1 3 and 4 and ECC Wiring Diagram 8 Use kit supplied wire tie wraps YORK p n 025 09607 000 to bundle and or secure LPCO control wires numbered 47 48 and 49 as needed 9 Reinstall enclosure cover sec...

Страница 13: ...flare half union fitting at the LPCO control pressure con nection 2 Using clean 1 4 in refrigerant hoses connect a controllable vacuum source in series to a digital vacuum gauge and to the 1 4 in ext...

Страница 14: ...7 Repeat steps 4 5 and 6 until the noted CUT OUT setpoint is within the allowable range 8 Once the CUTOUT set point is verified or cali brated then proceed to the switch DEADBAND calibration procedur...

Страница 15: ...k free seal 4 Disconnect the Ohm meter from the switch Com mon and Normally Open terminals 5 Connect the wire numbered 47 to the 025 45742 LPCO control switch terminal labeled as COM MON Refer to Figu...

Страница 16: ...JOHNSON CONTROLS 16 FORM 160 43 NM4 ISSUE DATE 11 12 2012 Section 3 Testing and Adjustments THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 17: ...plated brass Wetted Materials Brass bellows and zinc plated steel spring Weight Approx 1 lb Approvals UNITED STATES AND CANADA UL Listed cUL Certified Pressure UL 508 CSA C22 2 No 14 Files E42272 EUR...

Страница 18: ...USA 17405 1592 800 861 1001 Subject to change without notice Printed in USA Copyright by Johnson Controls 2012 www johnsoncontrols com ALL RIGHTS RESERVED Form 160 43 NM4 1112 Issue Date November 12 2...

Отзывы: