SECTION 2 - INSTALLATION

TOOLS NEEDED

• 

Power Drill and a #25 or 9/64 in. drill bit 

• 

Adjustable wrenches; 6 in. and 8 in.

• 

Open-end wrenches; 3/4 in., 5/8 in. and 9/16 in.

• 

Screwdrivers; Flat Blade and Phillips

SECURE CHILLER FROM OPERATION

1.  Shut off power source feed to the chiller Electron-

ic Control Center (ECC).

2.  Lock-Out, Tag-Out the chiller.
3.  Pull ECC fuses 1FU, 2FU and 3FU to ensure the 

LPCO control wiring is deenergized.

4.  Close the evaporator service valve having gauge 

piping going to the “Cooler” (evaporator) panel 

gauge and LPCO control.

REMOVE PRE-EXISTING LPCO CONTROL

1. 

Disconnect  LPCO  control  pressure  (¼  in.  flare 

nut) connection from the pressure tap behind the 

“Cooler” (evaporator) panel gauge.

2.  Using a voltage meter, reverify the ECC supply 

power and to the LPCO control wiring is deener-

gized. 

3.  Disconnect the three wires (47, 48 and 49) from 

the LPCO control and secure out of the way.

4.  Remove the two mounting screws and the LPCO 

control from the ECC.

MOUNTING 025 45742 LPCO CONTROL

Install unit where shock, vibration and 

ambient temperature fluctuations will not 

damage unit or affect operation. Orient 

unit so that moisture does not enter the 

enclosure via the electrical connection. 

When appropriate, this entry point should 

be sealed to prevent moisture entry.
Do not mount unit in ambient temperature 

exceeding Specified limits.

LPCO controls 025 45742 are mounted and operated in 

a vertical position with the switch up and pressure con-

nection down. The controls are surface mounted using 

two mounting ears, with holes for #10 screws, on either 

side of the control bracket plate. 

1. 

Remove  enclosure  cover  first  by  removing  one 

captive screw located on the front of the cover.

2.  When replacing a former 225 15443 002 LPCO 

control:

a.  Select a vertical surface mounting location 

on the back wall of the ECC for the replace-

ment LPCO control 025 45742 in the same 

general area of the former control. Ensure 

that the mounting location allows connection 

to the preexisting wiring to the control switch 

terminals and for the new capillary tubing to 

the “Cooler” (evaporator) panel gauge pres-

sure tap.

b.  To reach the LPCO control 025 45742 switch 

terminals, the preexisting wires (47, 48 and 

49) may need to be relocated through the 

cabinet middle conduit fitting containing the 

high pressure control wires. 

c.  Using the LPCO control 025 45742 bracket 

plate as a guide, locate and mark the two 

mounting holes locations on the ECC back 

wall. Ensure that the mounting holes loca-

tions will not interfere with anything within 

or outside of the ECC panel.

d.  Using a power drill and a #25 or 9/64 in. drill 

bit, drill out the two mounting holes. 

e.  Mount the replacement LPCO control 025 

45742 to the back wall of the ECC using 

two #10 self tapping screws (YORK p/n 021 

14727 000) provided in kit.

3.  When replacing a former 025 45742 LPCO con-

trol

a.  Mount the replacement LPCO control 025 

45742 to the back wall of the ECC where 

the former control was located and using 

two #10 self tapping screws (YORK p/n 021 

14727 000) provided in kit.

Содержание York 366-70487

Страница 1: ...RS STYLE B AND C CONTROL CENTERS 366 70488 366 70487 AND 366 73582 LOW PRESSURE CUTOUT CONTROL P N 025 45742 000 INSTALLATION AND MAINTENANCE Supersedes 160 43 NM4 1206 Form 160 43 NM4 1112 035 21593...

Страница 2: ...als This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question SAFETY SYMBOLS The following symbols are used i...

Страница 3: ...icy for con tinuous product improvement the information con tained in this document is subject to change without notice Johnson Controls makes no commitment to update or provide current information au...

Страница 4: ...JOHNSON CONTROLS 4 FORM 160 43 NM4 ISSUE DATE 11 12 2012 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 5: ...ting 025 45742 LPCO Control 9 Pressure Connection Piping 10 Wiring 11 SECTION 3 TESTING AND ADJUSTMENTS 13 Tools Needed 13 Secure Chiller From Operation 13 Connect LPCO Pressure Connection To A Calibr...

Страница 6: ...JOHNSON CONTROLS 6 FORM 160 43 NM4 ISSUE DATE 11 12 2012 THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 7: ...tments LPCO controls 025 45742 are vacuum switches which are negative gauge pressure controls that operate at a predetermined constant pressure below atmospheric This means that the absolute pressure...

Страница 8: ...At atmospheric pressure the switch contacts are made between the Common and Normally Open terminals and open between the Common and Normally Closed terminals As the pressure falls below the control C...

Страница 9: ...rated in a vertical position with the switch up and pressure con nection down The controls are surface mounted using two mounting ears with holes for 10 screws on either side of the control bracket pl...

Страница 10: ...o pressure connection tight enough to ensure a leak free seal 2 Installing kit supplied Capillary Tube 48 in YORK p n 026 45010 000 a Ensure 1 4 in flare mating surfaces are clean and free of debris o...

Страница 11: ...itch bracket Refer to Figure 3 The three switch terminals are clearly labeled COM MON NORMALLY OPEN and NORMALLY CLOSED Refer to Figures 3 and 4 1 Remove enclosure cover first by removing the one capt...

Страница 12: ...res 1 3 and 4 and ECC Wiring Diagram 8 Use kit supplied wire tie wraps YORK p n 025 09607 000 to bundle and or secure LPCO control wires numbered 47 48 and 49 as needed 9 Reinstall enclosure cover sec...

Страница 13: ...flare half union fitting at the LPCO control pressure con nection 2 Using clean 1 4 in refrigerant hoses connect a controllable vacuum source in series to a digital vacuum gauge and to the 1 4 in ext...

Страница 14: ...7 Repeat steps 4 5 and 6 until the noted CUT OUT setpoint is within the allowable range 8 Once the CUTOUT set point is verified or cali brated then proceed to the switch DEADBAND calibration procedur...

Страница 15: ...k free seal 4 Disconnect the Ohm meter from the switch Com mon and Normally Open terminals 5 Connect the wire numbered 47 to the 025 45742 LPCO control switch terminal labeled as COM MON Refer to Figu...

Страница 16: ...JOHNSON CONTROLS 16 FORM 160 43 NM4 ISSUE DATE 11 12 2012 Section 3 Testing and Adjustments THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 17: ...plated brass Wetted Materials Brass bellows and zinc plated steel spring Weight Approx 1 lb Approvals UNITED STATES AND CANADA UL Listed cUL Certified Pressure UL 508 CSA C22 2 No 14 Files E42272 EUR...

Страница 18: ...USA 17405 1592 800 861 1001 Subject to change without notice Printed in USA Copyright by Johnson Controls 2012 www johnsoncontrols com ALL RIGHTS RESERVED Form 160 43 NM4 1112 Issue Date November 12 2...

Отзывы: