![Johnson Controls YCIV0157 Скачать руководство пользователя страница 302](http://html1.mh-extra.com/html/johnson-controls/yciv0157/yciv0157_installation-operation-and-maintenance_2023452302.webp)
JOHNSON CONTROLS
302
FORM 201.23-NM2
ISSUE DATE: 3/9/2015
SECTION 8 - MICROPANEL
TABLE 27 -
REAL TIME ERROR NUMBERS
ERROR NUMBER
(##)
DESCRIPTION
0
ALL OK
1
DATUM TYPE OK TEST FAILED
2
ENGLISH TEXT TOO LONG
3
FLOATING POINT EXCEPTION
4
GET PACKET FAILED
5
GET TYPE FAILED
6
INVALID UNIT CONVERSION
7
INVALID HARDWARE SELECTION
8
REAL TIME FAULT
9
SPANISH TEXT TOO LONG
10
THREAD EXITED
11
THREAD FAILED
12
THREAD STALLED
13
IO BOARD RESET
14
BRAM INVALID
15
BACNET SETUP FAILED
TABLE 26 -
VALUES REQUIRED FOR BAS COMMUNICATION
SETTING DESCRIPTION
Protocol
BACnet MS/TP
Modbus RTU
5
YorkTalk 2
DE MODIFIER ADDRESS
0 to 41943
(3)
1
-1
DE MODIFIER OFFSET
0 to 99
(4)
0
N/A
P1 PROTOCOL
BACNET
N/A
N/A
P1 MANUAL MAC ADDRESS
0-127
(1)
N/A
N/A
P1 BAUD RATE
9600 To 76800 or Auto Selectable
(1)
N/A
N/A
P1 PARITY
NONE
N/A
N/A
P1 STOP BITS
1
N/A
N/A
P2 PROTOCOL
N/A
MODBUS SVR
N/A
P2 MANUAL MAC ADDRESS
N/A
0-127
(1)
N/A
P2 BAUD RATE
N/A
19,200
(2)
N/A
P2 PARITY
N/A
NONE
(2)
N/A
P2 STOP BITS
N/A
1
N/A
P2 HW SELECT BIT
N/A
RS-485 or RS-232
(1)
N/A
RESET REAL TIME ERROR
N/A
N/A
N/A
P1 HW SELECT BIT
N/A
N/A
N/A
CHILLER ID
N/A
N/A
0
1
as Required By Network
2
or Other As Required By Network
3
number Is Multiplied By 100, Set As Required By Network
4
number Is Added To De Modifier Address, Set As Required By Network
5
unit Operating Software Version C.Mmc.13.03 Or Later Required For Modbus Protocol
The table below shows set-up requirements for each communication protocol.
Reboot required (cycle power) after
settings are changed.
shows the real time error num-
bers that may be encountered during communication
setup and a description of each.
Содержание YCIV0157
Страница 18: ...JOHNSON CONTROLS 18 FORM 201 23 NM2 ISSUE DATE 3 9 2015 SAFETY SYMBOLS THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 38: ...JOHNSON CONTROLS 38 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 42: ...JOHNSON CONTROLS 42 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 50: ...JOHNSON CONTROLS 50 FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 104: ...JOHNSON CONTROLS 104 FORM 201 23 NM2 ISSUE DATE 3 9 2015 SECTION 6 TECHNICAL DATA Panel Layout 2 Compressor Models ...
Страница 105: ...JOHNSON CONTROLS 105 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 115: ...JOHNSON CONTROLS 115 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 119: ...JOHNSON CONTROLS 119 SECTION 6 TECHNICAL DATA FORM 201 23 NM2 ISSUE DATE 3 9 2015 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 333: ...JOHNSON CONTROLS 333 FORM 201 23 NM2 ISSUE DATE 3 9 2015 NOTES ...