Johnson Controls WRZ-7860-0 Скачать руководство пользователя страница 2

Use the following procedure to mount, wire, and prepare

the receiver for operation:

1.  Mount the mounting base. See 

Mounting

.

2.  Set the DIP switches. See 

Setup and Adjustments

.

3.  Align the tabs on the edge of the mounting base

with the slots on the edge of the receiver housing,

and rotate the assembly onto its mounting base as

illustrated in Figure 3.

4.  Use a 1/16 in. (1.5 mm) Allen wrench or Johnson

Controls T-4000-119 Allen-Head Adjustment Tool to

tighten the tamper-resistant set screw and fasten the

receiver enclosure to the mounting base.

Note: 

To avoid damage to the unit, do not

overtighten the set screw.

5.  Connect the SA bus cable from the controller to the

WRZ-7860-0 Receiver. See 

Wiring

.

Parts included

• One WRZ-7860-0 Receiver with factory-installed double-

sided adhesive foam tape on the back of the unit

• One installation guide sheet

Dimensions

See the following figure for dimensions and physical

features of the WRZ-7860-0 Receiver.

Figure 1: WRZ-7860-0 Receiver physical features and

dimensions, in. (mm)

Mounting

Location considerations

To locate a WRZ-7860-0 Receiver, follow these guidelines:
• Locate the receiver so that it is easily accessible in

the proximity of the field controller, on a Variable Air

Volume (VAV) duct, or just above or just below the

ceiling tiles.

Note: 

Communication cables of various lengths

are available to connect the receiver SA bus. See

Table 4 for more details.

• Locate the receiver up to 100 ft (30 m) from the WRZ

Series Wireless Room Sensor in a building environment.

• Locate the receiver near the center of the associated

room sensor layout in multi-sensor applications.

• Locate the receiver on the same floor or building level

as the associated room sensor.

• Locate the receiver in the direct line-of-sight with the

room sensor whenever possible. Signal transmission is

best if the path between the room sensor and receiver

is as direct as possible. Line-of-sight is preferred but

not required, as long as the path is not blocked by large

metal objects.

• Mount the receiver so that the antenna symbol on the

cover near the LEDs is in a vertical orientation, up or

down. The antenna symbol indicates the approximate

location of the receiver’s internal onboard antenna.

Figure 2: Correct mounting orientation

• If you mount the receiver on duct work, such as a

VAV box, ideally the antenna portion of the receiver,

approximately 1/3 of the enclosure, hangs below the

duct work. Avoid pipes, duct work, or other metal

obstructions in the direct line-of-sight to the room

sensor.

• Avoid large metal obstructions, including equipment

rooms and elevator shafts, and concrete or brick walls

between the receiver and the room sensor.

• Do not mount the receiver in recessed areas or shelving

units.

Wireless signal transmission considerations

Line-of-sight transmission ranges between a WRZ Series

Wireless Room Sensor and a WRZ-7860-0 Receiver can

be less than the maximum distances shown in Table 1.

The effective transmission range for indoor applications

varies because of RF signal absorption and reflection due

to metal obstructions, walls or floors, and furniture found

in building interiors.

Table 1: Indoor line-of-sight transmission ranges

Range type

Transmission distance

Practical

average

100 ft (30 m)

Maximum

150 ft (45 m)

Use the manual occupancy override button on the WRZ

Series Wireless Room Sensor to test the RF signal strength

between an installed room sensor and receiver. Refer

to the 

WRZ-7860-0 Receiver for One-to-One Wireless Room

Sensing Systems Technical Bulletin (LIT-12011641) 

for

more information about how to determine the signal

strength between a WRZ Series Wireless Room Sensor

and a WRZ-7860-0 Receiver. If the RF signal path provides

unsatisfactory results, use a Johnson Controls ZFR18xx

Series Wireless Field Bus Router as a repeater and locate it

between the room sensor and the receiver.

WRZ-7860-0 Receiver for One-to-One Wireless Room Sensing Systems Installation Guide

2

Содержание WRZ-7860-0

Страница 1: ... malfunction of the receiver could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfunction of the WRZ 7860 Receiver Important Le WRZ 7860...

Страница 2: ...s as direct as possible Line of sight is preferred but not required as long as the path is not blocked by large metal objects Mount the receiver so that the antenna symbol on the cover near the LEDs is in a vertical orientation up or down The antenna symbol indicates the approximate location of the receiver s internal onboard antenna Figure 2 Correct mounting orientation If you mount the receiver ...

Страница 3: ...se with screws Wiring The WRZ 7860 0 Receiver has a modular jack on the edge of the enclosure opposite the side with the tamper resistant set screw This modular jack for the SA bus requires a straight through one to one connection cable not a crossover to the SENSOR jack on a Controller Important Configure the field controller as if connected to a wired network sensor Configuring the field control...

Страница 4: ... Troubleshooting Use the status LEDs illustrated in Figure 1 with the information in the following table to troubleshoot the WRZ 7860 0 Receiver Table 2 Status LEDs Name Color Normal Description Flickering SA bus activity SA bus Green Flickering Off steady no SA bus activity Green good room sensor battery 1 blink marginal RF signal strength 2 blinks good RF signal strength 3 blinks excellent RF si...

Страница 5: ...less Room Sensor temperature LCD display F C manual occupancy override button button setpoint adjustment ZFR183x compatible WRZ THB0000 0 Temperature Humidity Sensor with display Warmer Cooler setpoint dial adjustment or scaled setpoint dial adjustment 55 F to 85 F 13 C to 29 C F C button RH button and manual occupancy override button WRZ THN0000 0 Wireless Room Temperature and Humidity Sensor wit...

Страница 6: ...ne RJ 12 Port for SA Communication Bus output sensed zone temperature and humidity temperature setpoint and occupancy override data Temperature sensor accuracy 1 0 F 0 6 C over the range of 55 F to 85 F 13 C to 29 C 1 5 F 0 9 C over the range of 32 F to 55 F 0 C to 13 C and 85 F to 110 F 29 C to 43 C Temperature sensor type Internal 10k ohm Negative Temperature Coefficient NTC thermistor Humidity ...

Страница 7: ...s product constitutes an agreement to such terms Patents Patents https jcipat com Single point of contact APAC Europe NA SA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA Contact information Contact your local branch offi...

Страница 8: ... 2020 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com ...

Отзывы: