FORM 145.20-IOM1 (908)

9

JOHNSON CONTROLS

4.  UNPACKING

a) Check the unit for indications of damage in ship-

ment.  Notify the Transportation company of any 

damage  and  note  the  damage  on  the  shipping 

receipt.  

Rough handling may dislocate internal 

components.

b) allow the shipping base to remain with the unit 

until it is ready to be set in its final location.

c) Rotate blowers to assure free movement.
d) The compressor is mounted on neoprene isolators 

with metal spacing sleeves inside and secured with 

nuts, which must be snug against the metal spacer 

sleeves.

e) Check all refrigeration tubing to assure that it does 

not rub against any other parts.

5.  NORMAL INSTALLATION

This unit is designed for indoor installation adjacent 

to an outside wall having an opening for outdoor air 

flow.  The air flow products must:

a) Discharge directly to the outside.
b) Discharge away from any obstructions which could 

cause discharged air recirculation.

6.  CLEARANCES

The unit is design certified for closet installation with 

the minimum clearances to combustible materials as 

stated on the data label.  No clearance is required 

from the top, sides, or back of the unit.  a minimum 

of 1 inch clearance is required from the front to any 

combustible materials.  a combustible door may be 

placed 6 inches from the front of the unit.  When the 

door is open there must be 30 inches clearance to 

any obstruction, to allow sufficient access for service 

and the replacement of parts. 

Outside Wall Thickness 5”-8”

D = (29” – B)

Outside Wall Thickness 8”-12”

D = (33” – B)

Outside Wall Thickness 12”-15”

D = (36” – B)

7.  WALL OPENING 

A  finished  opening  in  an  outside  wall  is  required 

for intake and exhaust of outdoor airflow.  The wall 

opening required is 21-3/4” wide by 44” high.  The 

bottom edge of wall opening must be located at least 

6” higher from finished floor

Consult local ordinances for building opening fram-

ing requirements.

8.  WALL SLEEVE

A  factory-made  wall  sleeve  is  required  to  finish 

the wall opening. The sleeve should be positioned 

with a minimum of ¼” protruding from the finished 

outside wall face. This projection allows installation 

of  the  exterior  grille  without  interference  from  the 

exterior  finishing  materials,  and  provides  a  right 

angle surface to apply a caulking bead around the 

wall penetration. 

use a spirit level or plumb line to make sure that the 

wall sleeve vertical flanges, which must mate with the 

back of the unit, are perfectly vertical.  The sleeve 

must be secured to the building framing with suitable 

field-supplied  fasteners  (i.e.  lag  screws).  (NOTE: 

use shims as necessary, between the sleeve and 

the rough wall opening, to compensate for any ir-

regularities at the sleeve fastening locations.) DO 

NOT allow the fasteners to distort the wall sleeve 

side panels.

a roll of ¾” wide x ½” thick self adhesive foam gasket 

is packed in the blower compartment of the unit, to 

be used for sealing between the wall sleeve and the 

unit.  Before moving the unit into final position, apply 

self-adhesive foam gasket to all the mating flanges 

on the wall sleeve, be sure to apply gasket material 

to the divider panel flange between the top and bot

-

tom sections of the wall sleeve.  also apply gasket 

material to the vertical flange of fresh air divider.

 22" min.

clear opening

Line up unit

with door openning

3" min.

recommended

"D

C

lo

se

t D

ep

th

"B"

LD13500

Содержание VPC

Страница 1: ...CTIONS Unit Model VPC R 22 Single Packaged Vertical A C Units w Optional Electric Heat Unit Model VPP R 22 Single Packaged Vertical Heat Pumps w Optional Electric Heat Unit Model VPH R 22 Single Packaged Vertical A C Units w Optional Hot Water Heat Cooling Capacities 9 000 12 000 18 000 24 000 Btu Hr Electric Heat Capacities 2kw 3kw 4kw 5kw 8kw 10kw ...

Страница 2: ... It is essential that prior to performing any task on this equipment this individual shall have read and understood this document and any referenced materials This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question safety symbols The following symbols are used in this document to alert the reader to areas ...

Страница 3: ...ould expose the worker the equipment and the building and its inhabitants to the risk of injury or property damage The instructions are written assuming the individual who will perform this work is a fully trained HVAC R journeyman or equivalent certified in refrigerant handling and recovery techniques and knowledgeable with regard to electrical lock out tag out procedures The individual performin...

Страница 4: ...ooling functions for a single zone or multiple rooms Specifically designed for convenient through the wall installation in residential high rise and hospitality industry applications The all indoor design eliminates the need for unsightly exterior equipment thereby maintaining architectural esthetics All units are shipped completely wired and factory tested The refrigeration section features enhan...

Страница 5: ...uh 30 30 000 Btuh 24 24 000 Btuh 18 18 000 Btuh 12 12 000 Btuh 09 9 000 Btuh Voltage 12 208 230 1 60 System Type A R 22 Refrigerant Service Digit Factory Assigned VPH UNIT NOMENCLATURE VP H 02 24 12 A A Product Category VP Single Packaged Vertical Unit Unit Type H Air Conditioner w Hydronic Heat Hydronic Heat Capacity Hot Water Coil Type 02 2 Row Coil 03 3 Row Coil Nominal Cooling Capacity 36 36 0...

Страница 6: ...IMPORTANT SAFETY RULES Read and exactly follow these rules Failure to do so could cause improper unit operation resulting in damage injury or death a Signal words To alert you to potential hazards we use the signal words WARNING and CAUTION throughout this manual WARNING alerts you to situations that could cause serious injury or death CAUTION alerts you to situations that could cause minor or mod...

Страница 7: ...rn air Outdoor air Discharge Outdoor air Intake 68 20 20 41 1 4 17 1 2 11 10 Electric Heater access Panel Compressor Electrical Box access Evap Blower Motor access Disconnect Switch Electrical Connections Low voltage Connection FIG 1 VPC VPP Dimensions Connection Locations LD13498 ...

Страница 8: ...r Outdoor air Discharge Outdoor air Intake 20 12 3 8 70 1 2 17 1 2 41 1 4 Evap Blower Motor access Water In Out Water Out In Compressor Electrical Box access 20 14 7 8 unit Disconnect Switch High voltage Connection Low voltage Connection LD13499 FIG 2 VPH Dimensions Connection Locations ...

Страница 9: ...D 36 B 7 WALL OPENING A finished opening in an outside wall is required for intake and exhaust of outdoor airflow The wall opening required is 21 3 4 wide by 44 high The bottom edge of wall opening must be located at least 6 higher from finished floor Consult local ordinances for building opening fram ing requirements 8 WALL SLEEVE A factory made wall sleeve is required to finish the wall opening ...

Страница 10: ...JOHNSON CONTROLS 10 FORM 145 20 IOM1 908 LD13501 FIG 3 Wall Sleeve Assembly ...

Страница 11: ... with a NPT female pipe fitting which protrudes through the unit wall sleeve bottom casing The drain piping should have drain trap installed to prevent condi tioned air from being blown out of the drain line The trap should be at least 2 inches deep with the outlet a minimum of 1 inch below the inlet The drain piping on the outlet side of the trap should be pitched inch per foot down towards an op...

Страница 12: ... 260 245 230 HIgH 775 760 745 725 705 685 660 635 MED 640 630 620 610 600 585 570 555 LOW 450 445 440 435 430 420 405 390 HIgH 1070 1045 1020 995 970 945 915 885 MED 930 920 910 900 890 875 860 840 LOW 820 815 810 805 800 790 780 765 ExTERNaL STaTIC PRESSuRE vPC vPP 12 vPC vPP 24 vPC vPP 18 vPC vPP 09 Motor Speed Model INDOOR BLOWER CFM VPH MODELS 0 05 0 10 0 15 0 20 0 25 0 30 0 35 0 40 HIgH 435 4...

Страница 13: ... and phase listed on the unit rating plate before installation to be sure the power supply is correct If the compressor fails as the result of installa tion or improper voltage the compressor is not replace able under warranty and the manufacturer will not be responsible for the cost of replacement The minimum and maximum operating voltages and fuse sizes are listed on the unit rating plate The po...

Страница 14: ...0 17 1 10 3 76 4 59 5 00 23 51 25 89 26 98 25 30 30 vPC vPP0618 1 10 0 41 0 0 13 0 75 0 17 1 10 4 51 5 51 6 00 28 02 30 89 32 19 30 35 35 vPC vPP0818 1 10 0 41 0 0 13 0 75 0 17 1 10 6 01 7 35 8 00 37 05 40 87 42 60 40 45 45 vPC vPP1018 1 10 0 41 0 0 13 0 75 0 17 1 10 7 51 9 18 10 00 46 08 50 85 53 02 50 60 60 vPC vPP0324 1 12 1 54 0 0 25 1 50 0 25 1 50 2 25 2 76 3 00 18 13 18 13 18 13 30 30 30 vPC...

Страница 15: ...lectrical heater is energized between 1 24 seconds after time delay is energized Heating fan is energized si multaneously with heating element operation 4 On a unit with two heating elements 6kW 8kW or 10 kW the 2nd element will be energized by clo sure of the 2S sequencer contacts approximately 90 seconds after the first stage is energized 5 When the room thermostat is satisfied terminals R and W...

Страница 16: ...pressures have equalized before a compressor restart B OUTDOOR AMBIENT BELOW 40ºF 1 Room thermostat calls for heat connecting R and Y terminals O terminal de energized 2 The normally closed contacts of the Low Ambient relay R2 route the thermostat signal through R3 to energize the electric element switching sequenc ers The heat cool interlock relay R3 pre vents the electric heat from being en ergi...

Страница 17: ...sea son Inspect clean and repair as needed the following items 1 All electrical wiring and connections including electrical ground 2 All supply air and return air ducts for obstructions air leaks and loose insulation 3 Blower housings motors and wheels and air filters Blower motors do not require oiling 4 Inspect indoor and outdoor coils for accumulations of dirt and debris and clean as required I...

Страница 18: ...JOHNSON CONTROLS 18 FORM 145 20 IOM1 908 LD13504 ...

Страница 19: ...FORM 145 20 IOM1 908 19 Johnson Controls LD13505 ...

Страница 20: ...JOHNSON CONTROLS 20 FORM 145 20 IOM1 908 LD13506 ...

Страница 21: ...FORM 145 20 IOM1 908 21 Johnson Controls NOTES ...

Страница 22: ...JOHNSON CONTROLS 22 FORM 145 20 IOM1 908 NOTES ...

Страница 23: ...eplacing the compressor is not covered by this Warranty LABOR AND COST NOT COVERED This Warranty provides only replacement parts or credits and does not provide for or cover any labor shipping handling or other costs for service travel servicing removing or installing any parts EXCLUSIONS This Warranty shall be void if 1 The unit is not installed by a licensed or otherwise qualified or contractor ...

Страница 24: ...e without notice Printed in U S A Copyright 2008 by Unitary Products Group All rights reserved Form 145 20 IOM1 908 Supersedes 145 20 IOM1 708 York PA 17405 P O Box 1592 York PA 17405 Engineered Systems Products Group ...

Отзывы: