Input and Output wiring guidelines tables
Table 4: I/O terminal blocks, functions, ratings, requirements, and cables
Terminal block label
Terminal labels
Function, ratings, and requirements
To determine wire size and
maximum cable length
+15 V
15 VDC Power Source
for active (3-wire) input
devices connected to the Universal IN
n
terminals.
Provides 35 mA total current.
Same as (Universal)
IN
n
.
Note:
Use 3-wire cable for
devices that source power
from the +15 V terminal.
Analog Input - Voltage Mode (0–10 VDC)
10 VDC maximum input voltage
Internal 75k ohm Pulldown
Analog Input - Resistive Mode (0–600k ohm)
Internal 12 V, 15k ohm pull up
Qualified Sensors: 0–2k potentiometer,
RTD (1k Nickel [ Johnson Controls sensor],
1k Platinum, and A99B Silicon Temperature Sensor)
Negative Temperature Coefficient (NTC) Sensor
10K Type L (10K JCI Type II is equivalent to Type L) or
2.252K Type II
IN
n
Binary Input - Dry Contact Maintained Mode
1 second minimum pulse width
Internal 12 V, 15k ohm pull up
UNIVERSAL
(Inputs)
ICOM
n
Universal Input Common
for all Universal IN
n
terminals
Note:
All Universal ICOM
n
terminals are
isolated from all other commons on the -0
models. The -1 model ICOMn terminals are
isolated from FC BUS COM terminals only.
Same as (Universal)
IN
n
.
OUT
n
Binary Output - 24 VAC Triac (Internal Power)
Sources internal 24 VAC power (24~ HOT)
BINARY
(Outputs)
OCOM
n
Binary Output - 24 VAC Triac (Internal Power)
Connects OCOM
n
to 24~ COM when activated.
Internal Power Source:
30 VAC maximum voltage to load
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current
VMA1826/1832 VAV Controller Installation Guide
17