background image

Mounting and Wiring VMA1200 Series Controllers Technical Bulletin

5

 

Do not run L

ON

W

ORKS

 Network Bus, Zone Bus,

Analog Input (AI), Binary Input (BI), Analog Output (AO), or
Binary Output (BO) wiring in the same conduit as line voltage
wiring (above 30 VAC), or with wiring that switches power to
highly inductive loads such as contactors, coils, motors, or
generators.

 

Run Zone Bus, AI, AO, and BI wiring in the same bundle or
conduit where convenient. If the BO wiring is 

not

 wired through

other switches or contacts, such as actuator end-of-travel switches,
you may also bundle it with the other I/O (Input/Output) wiring
where convenient.

 

The following are additional general wiring considerations:

 

The VMA includes an isolated L

ON

W

ORKS

 Network Bus, isolated

binary outputs, and isolated 24 VAC. See 

VMA Internal Schematic

Diagram 

in this section.

 

The 24 VAC power input is internally transformer isolated by the
VMA. To meet NEC requirements for line voltage greater than
150 VAC, Terminal 1 (24 VAC) can be earth grounded.

 

Up to 14 cooling-only VMAs (Model VMA1210) are powered
from one 100 VA low voltage power limited, Class 2 transformer.
The number of VMA1220s per transformer varies, depending on
power requirements of the valve actuators and relays. Conduit is
not needed for 24 VAC at 100 VA or less.

 

Large insulated spade lugs with a polarizing tab (for high voltage)
do not fit on the VMA.

Содержание VMA1200 Series

Страница 1: ...Wiring VMA1200 Series Controllers 2 Introduction 2 Key Concepts 3 VMA Position and Orientation 3 Determine and Set Damper Polarity 3 Wiring and Cabling Precautions 4 VMA Internal Schematic Diagram 6...

Страница 2: ...mbly VMA which is a controller actuator pressure sensor mounts on the Variable Air Volume VAV terminal box and fastens to the damper shaft Instructions for wiring the VMA and its accessory devices are...

Страница 3: ...VMA so that it has adequate clearance for future servicing and is protected from moisture and corrosive fumes Determine and Set Damper Polarity Damper polarity is established upon installation Incorr...

Страница 4: ...d destroys the VMA triac Read these precautions before touching the terminals or wiring the VMA and its accessories Make all wiring connections in accordance with the National Electrical Code NEC and...

Страница 5: ...put Output wiring where convenient The following are additional general wiring considerations The VMA includes an isolated LONWORKS Network Bus isolated binary outputs and isolated 24 VAC See VMA Inte...

Страница 6: ...ed Power Supply 2 Earth Ground Connection 3 Airflow and High Temperature Safety Switches 4 Isolated Triacs and Power Wiring for the Airflow and High Temperature Safety Switches 5 Isolated LONWORKS Net...

Страница 7: ...han 150 VAC 1 2 XFR Synchronous Motor Actuator COM Water Valve 1 2 4 3 In LONWORKS Network Bus VMA 15V 5V Triacs COM COM AO 15 23 14 OPTO 24 VAC BCOM CablePRO or CVTPRO Laptop R R Reheat BO 3 Reheat B...

Страница 8: ...own cable refer to Fabricating Your Own Interconnection Cable in Appendix A Reference Information located in the Variable Air Volume Modular Assembly VMA 1200 Series Overview and Engineering Guidelin...

Страница 9: ...VDC 6 Power Common and Zone Bus Common and Manual Override Common and LED Common 7 Zone Bus 8 LED and Manual Override Manual Override for Temporary Occupied Mode is selected using DIP switches for ei...

Страница 10: ...ional Note The VMA requires a damper shaft protrusion of at least 44 mm 1 3 4 in from the VMA mounting surface 3 Ensure the VMA installation site meets the following environmental requirements The VMA...

Страница 11: ...crew provided into the VMA mounting slot using a power screwdriver and socket with 4 in extension Alternate mounting 1 Perform Step 1 as shown previously 2 Use a punch to mark the position of the shou...

Страница 12: ...elease lever down and position the actuator collar against its internal stop corresponding to the fully closed position This provides a hard stop for this position The hard stop for the open position...

Страница 13: ...A coupler by hand to ensure that the damper can rotate from full closed to full open positions without binding 6 Plug or seal the end of a hollow damper shaft to stop cold duct air from affecting the...

Страница 14: ...2 or 3 position screw terminals or phone cable is to be used See the Variable Air Volume Modular Assembly VMA 1200 Series Overview and Engineering Guidelines Technical Bulletin LIT 1162350 for screw...

Страница 15: ...they are internal and no wiring is required Connecting the LONWORKS Network Bus A connection between the VMA and the Network Control Module NCM is required if the VMA is to communicate with the Metas...

Страница 16: ...Shield LON A LON B LON A LON B NCMConnect To Next L W Compatible Device or NCM ON ORKS Figure 9 Connecting the VMA to an NCM 2 Apply power Locate and observe the VMA LEDs See Tables 7 and 8 for detail...

Страница 17: ...ED SHLD Description LED Color Included on VMA1220 Only Safety Isolation Transformer in Europe Earth Ground COM CW End Stop 3 Controller operating properly The network table is not configured Use Comm...

Страница 18: ...en received Table 8 Running LED Color Name State Description Blinking Application is running normally LED blinks at one second interval On Steady Application is not running Try the following 1 Check t...

Отзывы: