VA9208-Bxx-x Series On/Off Electric Spring Return Valve Actuators Installation Instructions

10

Setup and Adjustments

Auxiliary Switch (VA9208-xxC-3 Models)

The VA9208-xxC-3 models include two integral 
auxiliary switches with a switch adjuster accessible on 
either face of the actuator (Figure 20). The factory 
setting for Auxiliary Switch No. 1 is 83% closing, and 
the nominal setting for Auxiliary Switch No. 2 is 10% 
opening (relative to the 0 to 100% rotation range as 
printed on the product label). See the Technical 
Specifications table for the auxiliary switch ratings.   

The switch point of Auxiliary Switch No. 1 is fixed. The 
switch point of Auxiliary Switch No. 2 is independently 
and continuously adjustable from 74 to 5% position. 
For the most accurate switch positioning, see Figure 22 
and use the method in the following example. To 
change the switch point of Auxiliary Switch No. 2, 
proceed as follows: 

1.

Position the actuator in the full spring return 
position.

Note:

The switch is factory set to trip when the 

actuator reaches the 10% position.

2.

Rotate the switch adjuster until it points to the 
desired switch point.

3.

Connect Auxiliary Switch No. 2 to a power source 
or an ohmmeter and apply power to the actuator. 
The actuator moves to the fully open position and 
holds while power is applied.

4.

Observe the switch point. If required, repeat Step 1 
through Step 3.

Repair Information

A number of replacement parts are available; see 
Table 3 for more details. If an VA9208 Series
Electric Spring Return Actuator fails to operate within 
its specifications, replace the unit. For a replacement 
electric actuator, contact the nearest Johnson Controls 
representative.

Technical Specifications   

!

WARNING: Risk of Electric Shock and 
Property Damage.

Insulate and secure each unused wire 
lead before applying power to the 
actuator. Failure to insulate and secure 
each unused wire lead may result in 
property damage, electric shock, and 
severe personal injury or death.

AVERTISSEMENT : Risque de 
décharge électrique et dégâts 
matériels.

Isoler et protéger chaque fil non utilisé 
avant de mettre l'actuator sous tension. 
Le non-respect de cette obligation 
d'isolation et de protection de chaque fil 
non utilisé risque d'entraîner des dégâts 
matériels, des décharges électriques et 
des blessures graves, voire mortelles.

Figure 22:  Switch Trip Point Settings

F

IG

:S

W

_

T

R

P

VA9208-Bxx-x Series On/Off Electric Spring Return Actuator (Part 1 of 3 )  

Power 
Requirements

-BGx Models

AC 24 V (AC 18 V to 30 V) at 50/60 Hz: Class 2 (North America) or Safety 
Extra-Low Voltage (SELV) (Europe), 6.1 VA Running, 1.2 VA Holding Position 
DC 24 V (DC 21.6 V to 28.8 V): Class 2 (North America) or SELV (Europe) 
3.5 W Running, 0.5 W Holding Position 
Minimum Transformer Size: 7 VA per Actuator

-BAx Models

AC 120 V (AC 102 V to 132 V) at 60 Hz: 0.05 A Running, 0.03 A Holding 
Position 

-BDx Models

AC 230 V (AC 198 V to 264 V) at 50/60 Hz: 0.04 A Running, 0.03 A Holding 
Position

Содержание VA9208-BAA-3

Страница 1: ...Actuator uniquement pour commander des quipements dans des conditions normales de fonctionnement Lorsqu une d faillance ou un dysfonctionnement du electric actuator risque de provoquer des blessures o...

Страница 2: ...1 A B C D E F G 1 1 4 DN32 All 5 5 32 131 1 1 32 26 1 23 32 44 7 5 32 182 3 15 16 100 11 32 9 1 31 32 50 1 1 2 DN40 All 5 5 16 135 1 9 64 29 1 57 64 48 7 3 8 187 4 21 64 110 11 32 9 2 11 64 55 2 DN50...

Страница 3: ...cted to the coil See Figure 2 Figure 3 Spring Return VA9208 Actuated VG1241 VG1245 VG1841 and VG1845 Series Ball Valve with Optional M9000 561 Thermal Barrier Installed Dimensions in mm 3 29 32 99 A B...

Страница 4: ...ds 212 F 100 C See the Mounting the Thermal Barrier section for more information Note Proceed to Step 7 if the ball valve linkage is on actuator Side B 3 Remove the linkage from Side A Figure 5 4 Inse...

Страница 5: ...tor to Spring Return Port A Coil Closed To mount the actuator to spring return port A coil closed 1 Turn the valve stem to the position outlined in Figure 10 2 Mount optional M9000 561 Thermal Barrier...

Страница 6: ...2 3 to 2 7 N m 6 Insert fixed pointer and M4x0 7x83 mm long screw into the Side B actuator hub Direct the arrow on the pointer to 0 Figure 14 7 Install the actuator on the ball valve Figure 15 Tighte...

Страница 7: ...o the valve when mounting the actuator to the thermal barrier Note Depending on your application you may position the assembly in any of the four 90 increments on the valve Manual Override Use only th...

Страница 8: ...ment lectrique Plusieurs isolations et d branchements sont peut tre n cessaires pour couper enti rement l alimentation de l quipement Tout contact avec des composants porteurs de tensions dangereuses...

Страница 9: ...the screws through the product label in the marked positions Drive the screwhead flush with the plate to secure the conduit Figure 19 Control Wiring Diagrams AC 120 V 60 Hz L1 N WHT BLK 2 1 AC 230 V...

Страница 10: ...ugh Step 3 Repair Information A number of replacement parts are available see Table 3 for more details If an VA9208 Series Electric Spring Return Actuator fails to operate within its specifications re...

Страница 11: ...3 lb in 6 N m Load at 40 F 40 C Life Cycles 60 000 Full Stroke Cycles with 70 lb in 8 N m Load Audible Noise Rating Power On Running 47 dBA at 70 lb in 8 N m Load at a Distance of 39 13 32 in 1 m Powe...

Страница 12: ...Electrical Controls for Household and Similar Use and CSA C22 2 No 24 93 Temperature Indicating and Regulating Equipment Europe CE Mark Johnson Controls declares that this product is in compliance wi...

Отзывы: