background image

VA-8052 Technical Bulletin

     3

plate must not contact the
upper stop and the drive
coupler must not contact
the bottom surface of the
actuator yoke (see Fig. 1).

Installation of VA-8052-1 on
3/4 in. Stroke 2-Way, Push
Down to Close (PDC) Valves

1.

Unpack the VA-8052
Actuator and insure that the
feedback potentiometer
plunger is on top of the
coupler arm.

2.

Install the valve packing
that is provided according
to the instructions included
with it.

3.

Thread the 1/4 in. Palnut,
open side down, onto the
valve stem and all the way
to the end of the threads.

4.

Loosely install the actuator
by sliding the actuator yoke
between the spring plate
and valve centerpiece
surface.  Finger tighten the
spring plate to hold the
actuator in place (see Fig. 1).

Содержание VA-8052

Страница 1: ...DC to the IN and COM terminals see Fig 4 Check to see that the stroke potentiometer is fully CCW see Fig 1 6 Thread the knurled coupler onto the valve stem until approximately 1 4 in of thread remains between the knurled coupler and the Palnut Note It may be necessary to pull the valve stem up to meet the coupler or to apply 0 to 10 VDC to position the coupler above the valve stem 7 Secure the act...

Страница 2: ... 1 6 Thread the knurled coupler onto the valve stem until approximately 1 4 in of thread remains between the knurled coupler and the Palnut Note It may be necessary to pull the valve stem up to meet the coupler or to apply 0 to 10 VDC to position the coupler above the valve stem 7 Secure the actuator in place by tightening the spring plate with a large screwdriver see Fig 2 8 Stroke the actuator t...

Страница 3: ...r and insure that the feedback potentiometer plunger is on top of the coupler arm 2 Install the valve packing that is provided according to the instructions included with it 3 Thread the 1 4 in Palnut open side down onto the valve stem and all the way to the end of the threads 4 Loosely install the actuator by sliding the actuator yoke between the spring plate and valve centerpiece surface Finger ...

Страница 4: ... in box head wrench and with a small screw driver loosen the stem locking screw 4 For V 3000 Series Valves compress the spring using the JC 5389 Spring Compression Tool For V 3800 Series Valves compress the spring with hand pressure 5 Using a 9 16 in box head wrench unscrew the stem extension Lift the spring and upper spring plate off of the valve Remove the spring compression tool if used 6 Threa...

Страница 5: ...ollows Stroke Adjustment SeeFig 1 1 Adjust the stroke potentiometer fully CCW to maximum Adjust the span potentiometer fully CCW to minimum Zero Adjustment 2 Adjust the zero potentiometer fully CCW to maximum 3 Provide an input signal equal to the desired zero starting point value and then wait for the actuator to stroke to the stem up position 4 Slowly adjust the zero potentiometer CW until the a...