Johnson Controls VA-77 Series Скачать руководство пользователя страница 4

4

PB_VA-7700_Electricl Valve Actuators_02 2011

Auto-calibration■procedure■for■freely■defined■

control■signal■ranges■

Non standard control signals for example 2…8 VDC are applied 
by setting the DIP switches 3 and 4 

(see paragraph "DIP switch 

settings")

.

It is recommended to set the actuator to the desired control-signal 
type and action before fitting to valve 

(see paragraph "DIP switch 

settings").

 

Power must be connected before the auto-calibration cycle can 
be started. It is recommended that the signal span is always 
set superior or equal to 3V or 6 mA in order to keep acceptable 
proportional characteristics.

Procedure:■(Actuator■is■mounted■on■valve)

•  Verify that with the stem fully retracted, there is a minimum 

distance of 1 mm between the top of the actuator stem nut and 
the stem guide bush in the actuator motor housing base plate. 
If necessary correct the distance by adjusting the actuator / 
valve stem connection.

•  The auto calibration cycle is started by pushing both calibration 

buttons, on the pcb, simultaneously for at least 5 seconds.  
The actuator will then make a full cycle to detect the stem 
extended and retracted limits.

•  Apply one of the control signal values 

and■confirm■by■

pressing■one■of■the■two■calibration■buttons■for■2■seconds■

(the■5■LED■will■illuminate■for■5■sec■to■confirm■the■setting)

Now apply the second control signal value and again 

confirm■

by■pressing■one■of■the■two■calibration■buttons■for■2■

seconds■(the■5■LED■will■illuminate■for■5■sec■to■confirm■the■

setting).

•  Both the minimum and the maximum control signal values are 

stored in the memory of the actuator. 

•  When the auto calibration cycle is completed the LED 

stop flashing, the actuator stem moves to the position that 
corresponds to the control signal and the five LED indicate the 
stem position.

•  When the control signal changes the actuator stem moves to 

the new position this is indicated by one flashing LED. The LED 
stops flashing when the position corresponding to the control 
signal has been reached.

Position■feedback

The position feedback signal is for monitoring the actuator stroke 
position. It feeds information internally to the positioner and a 
0-10 VDC signal can supply an external supervisory system.

Electrical■manual■override

To select electrical manual override DIP switch 7 must be 
switched to “on” (right hand position; 

see paragraph "DIP 

switch settings")

. The actuator stem can now be driven via the 

calibration buttons. The upper button retracts the stem and the 
lower button extends the stem. The stem remains in the position 
at which the button is released. Switch DIP switch 7 to “off” to 
return to automatic drive. The five LED indicate the stem position.

Mechanical■manual■override

To select manual override turn the override knob from “AUT” to 
“MAN”, the hand wheel is then engaged and power disconnected 
internally. Turning the hand wheel clockwise extends the stem 
and anti-clockwise retracts the stem. Turning the override knob to 
AUT disengages the hand wheel and reconnects the power.

WARNING:■The■auxiliary■switches■(terminals■

10,■11,■and■12)■can■be■used■to■indicate■manual■

override■or■automatic■mode.

Calibration buttons

> 5 sec

During auto-calibration cycle all five 

status indication LED flash simultaneusly

Содержание VA-77 Series

Страница 1: ...des Enables sequence control Magnetic clutch Provides constant output force for close off of valves and protects motor in stall conditions Control Signal failure stem to pre determined position Actuat...

Страница 2: ...ectrical and Mechanical VA 7746 8201 24 VAC Electrical and Mechanical These actuators can be combined with the following valve ranges VG7000 Series Threaded Valves Female and male threaded valves Thes...

Страница 3: ...ranges The standard control signals are selected by setting DIP switches 3 and 4 switch see paragraph DIP switch settings It is recommended to set the actuator to the desired control signal and actio...

Страница 4: ...um and the maximum control signal values are stored in the memory of the actuator When the auto calibration cycle is completed the LED stop flashing the actuator stem moves to the position that corres...

Страница 5: ...VDC 3 0 10 VDC 4 4 3 5 10 VDC 5 4 6 Direct Acting mode 3 Free Range 7 Electrical manual override off 4 8 Signal failure position pre set Up 5 0 20 mA 5 4 20 mA 6 Action 6 DA 6 RA 7 Electrical Manual...

Страница 6: ...nd the LED indicate a general alarm code If the problem is cleared however the actuator continues normal function Fault mode If the actuator enters fault mode the LED will flash as shown The indicatio...

Страница 7: ...tion The controller 0 10 V output can operate several actuators with built in electronic positioner The number of actuators that can be linked to a single controller depends on the controller s active...

Страница 8: ...d lead to an abnormal operating condition that could cause personal injury or damage to the equipment or other property other devices limit or safety controls or systems alarm or supervisory systems i...

Страница 9: ...g models 230 VAC supply VA 7746 xx01 Proportional models 24 VAC supply WARNING Equipment Damage Hazard On 24 V models with manual override it is not permitted to connect voltages greater than 24 V to...

Страница 10: ...ors_02 2011 VA 7700 xx01 Floating models 24 VAC supply VA 7700 xx03 Floating models 230 VAC supply VA 7706 xx01 Proportional models 24 VAC supply Wiring Diagrams Models without mechanical manual overr...

Страница 11: ...11 PB_VA 7700_Electricl Valve Actuators_02 2011 Dimensions in mm VA 77xx 82xx 87 90 VA 77xx 10xx A 25 mm VA 770x actuators without manual override A 80 mm VA 774x actuators with manual override...

Страница 12: ...250 0 4 20 mA Resolution 0 5 up to 200 steps on 20 mm stroke Feedback ratings max 2mA at 0 10 VDC 5 k Manual contact micro switch max load 2A Resistive 1A Inductive 24 VAC 24 V switch 2A Resistive 1A...

Отзывы: