Johnson Controls VA-7010 Series Скачать руководство пользователя страница 4

4    VA-7010 Series Electric On/Off Actuator Product/Technical Bulletin

S

pecifications

Product

VA-7010 Series Electric On/Off Actuator

Action

On/Off

Type of Motor

Synchronous Stall

Supply Voltage (50/60 Hz)

VA-7010-8001:

24 VAC, Class 2, ±10%

VA-7010-8002:

120 VAC, ±10%

VA-7010-8003:

230 VAC, ±10%

VA-7010-8006:

208 VAC, ±10%

VA-7010-8007:

277 VAC, ±10%

Power Consumption

7 VA

Minimum Force

20.2 lb (90 N)

Nominal Stroke

0.12 in. (3 mm), maximum 0.2 in. (5 mm)

Full Stroke Time On

Nominal 10 seconds

Full Stroke Time Off

Nominal 5 seconds

Enclosure

IP40, NEMA 1

Ambient Operating

Condition

35 to 122

°

F (2 to 50

°

C), non-condensing

Ambient Storage

Condition

-4 to 149

°

F (-20 to 65

°

C), non-condensing

Electrical Connections

18 AWG, 20 in. (508 mm) long wire leads

Dimensions (H x W x D)

2.9 x 2.9 x 2.6 in. (75 x 75 x 65 mm)

Shipping Weight

1.1 lb (0.5 kg)

Agency Compliance

UL 873 Listed, File E27734, Guide XAPX, Plenum Rated
CSA C22.2 No. 139 Certified, File LR85083, Class 3221 01

CE Conformity

VA-7010-8001:

EMC Directive (89/336 EU)

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or
misuse of its products.

Controls Group
507 E. Michigan Street
P.O. Box 423

Printed in U.S.A.

Milwaukee, WI  53201

www.johnsoncontrols.com

Содержание VA-7010 Series

Страница 1: ...IT 977135 for specific information A lever at the side of the actuator housing can be used to open the mounted valve manually for servicing Figure 1 VA 7010 Actuator with VG5000 Valve Features and Benefits Low or Line Voltage Model Available Provides application flexibility AC Stall Type Motor Ensures quiet operation Manual Lever Allows manual position mode for servicing Flat Profile Design with S...

Страница 2: ... N C valves or the N C port of 3 way valves The lever will not fully close Normally Open N O valves or the N O port of 3 way valves Dimensions Figure 3 Dimensions in mm Mounting Observe the following recommendations when mounting the actuator Make sure the actuator is easily accessible for the electrical connections Make sure the actuator is free of thermal insulation material Leave at least 0 8 i...

Страница 3: ... through 3 8 in Flexible Metallic Conduit FMC or its equivalent as appropriate 2 Secure the FMC to the connector provided with the actuator by tightening the clamp screw using a 1 4 in flat blade screwdriver 3 Connect the wires as shown in Figure 5 for each respective model voltage White White White Black Green White Yellow Green White Red Green White Blue Green Power Power Case Ground N A VA 7010...

Страница 4: ...ing Ambient Storage Condition 4 to 149 F 20 to 65 C non condensing Electrical Connections 18 AWG 20 in 508 mm long wire leads Dimensions H x W x D 2 9 x 2 9 x 2 6 in 75 x 75 x 65 mm Shipping Weight 1 1 lb 0 5 kg Agency Compliance UL 873 Listed File E27734 Guide XAPX Plenum Rated CSA C22 2 No 139 Certified File LR85083 Class 3221 01 CE Conformity VA 7010 8001 EMC Directive 89 336 EU The performance...

Отзывы: