Design 

Criteria

The TYCO Model TFP PH5, 5.6 K-fac-

tor (SIN TY3390) Institutional Horizon-

tal Sidewall Sprinklers are intended for 

use in fire protection systems designed 

in accordance with the standard instal-

lation rules recognized by the appli-

cable Listing or Approval agency (for 

example, UL Listing is based on NFPA 

13 requirements).

NOTICE

The Sprinkler Body must not extend 

beyond the Institutional Escutcheon 

(Ref. Figure 4). Otherwise, the tamper-

resistant design of the Model TFP PH5 

will be compromised. Consequently, 

Model 1752 Spacers, which are associ-

ated with other TFP institutional sprin-

klers, cannot to be utilized.
Integrity of the tamper-resistant design 

of the Institutional Escutcheon is 

dependent on the piping installation 

design. When installed properly, the 

Institutional Escutcheon is held fast to 

the mounting surface by the tighten-

ing of the sprinkler assembly into the 

sprinkler fitting. In order to accomplish 

a proper installation, the sprinkler fitting 

must be:
•  properly located with respect to dis-

tance from the face of the sprinkler 

fitting to the face of the mounting 

surface (Ref. Figure 3);

•  rigidly secured and held immobile; 

and,

•  installed with the center-line of the 

sprinkler fitting perpendicular to the 

mounting surface to assure that the 

escutcheon sits squarely against 

the mounting surface around the 

entire perimeter of the Institutional 

Escutcheon.

Figure 3 illustrates a typical installa-

tion that can be utilized to help adjust 

the location of the sprinkler fitting; to 

help assure immobility of the sprinkler 

fitting; and, to help maintain perpen-

dicularity of the sprinkler fitting to the 

mounting surface.

Installation

The TYCO Model TFP PH5 Sprinklers 

must be installed in accordance with 

this section.

NOTICE

R

efer to the Design Criteria section for 

important information regarding the 

piping installation design and its effect 

on maintaining the integrity of the tam-

per-resistant design of the Institutional 

Escutcheons.

Obtain a leak-tight 1/2 in. NPT sprin-

kler joint by applying a minimum-to-

maximum torque of 7 to 14 lb-ft (9,5 

to 19,0 N

m). Higher levels of torque 

can distort the sprinkler inlet with con-

sequent leakage or impairment of the 

sprinkler.
Do not attempt to compensate for 

im proper location of the sprinkler fitting 

by under- or over-tightening the sprin-

kler. Re-adjust the position of the sprin-

kler fitting to suit.

The Model TFP PH5 (SIN TY3390) must 

be installed with a deflector-to-ceiling 

distance of 4 in. to 6 in. (100 mm to 

152,4 mm). To meet this requirement, 

the center-line of the sprinkler water-

way must be located 4-1/2 in. to 

 

6-1/2 in. (114,3 mm to 165,1 mm) below 

the ceiling (Ref. Figure 3).
Only the Institutional Escutcheons 

shown in Figure 2 can be utilized with 

the Model TFP PH5.

NPT

1/2"

CENTERLINE

WATERWAY

OF SPRINKLER

1/2"

(12.7 mm)

ASSEMBLY

DEFLECTOR

IN OPERATED

POSITION

WRENCHING

NOTCH (2)

SPRINKLER

LINKAGE

MECHANISM

WITH DEFLECTOR

INSTALL

SPRINKLER

HOOD ORIENTED AT

TOP AS SHOWN

SPRINKLER

FITTING

FACE OF

NOMINAL MAKE-IN

7/16" (11.1 mm)

12

8

1

4

5

10

11

9

2

3

7

6

2.81"

(71.4 mm)

(80.8 mm)

3.18"

INSTALLED SIDE VIEW

OPERATED SIDE VIEW

FRONT VIEW

INSTALLED

CROSS-SECTION VIEW

Deflector Post

-

-

-
-

-
-

-

-

Deflector Post Pin

Release Spring

Dust Cover

Fusible Element

Lever

Compression Screw

(2 req'd)

(2 req'd)
Deflector Core

-

-

-

Deflector

Body
Deflector Hood

1

4

2
3

5

7

6

8

10

9

11

Components:

FIGURE 1 

MODEL TFP PH5 INSTITUTIONAL 

HORIZONTAL SIDEWALL SPRINKLER

Содержание tyco TFP PH5

Страница 1: ...iability for damages or injury including death arising out of or caused by manipulation dismantling or misuse of TFP PH5 Sprinklers or the use or attempted use of the TFP PH5 Sprinklers or any component thereof as an instrument unrelated to its intended function as a fire protection device The owner is responsible for main taining their fire protection system and devices in proper operating con di...

Страница 2: ...ty of the sprinkler fitting to the mounting surface Installation The TYCO Model TFP PH5 Sprinklers must be installed in accordance with this section NOTICE Refer to the Design Criteria section for important information regarding the piping installation design and its effect on maintaining the integrity of the tam per resistant design of the Institutional Escutcheons Obtain a leak tight 1 2 in NPT ...

Страница 3: ...aned by means of gently dusting with a feather duster otherwise non operation in the event of a fire or inad vertent operation may result Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced Automatic sprinklers must never be painted plated coated or other wise altered after leaving the factory Modified sprinklers must be replaced Sprinklers that have ...

Страница 4: ...onal Horizontal Sidewall Sprin kler P N 51 106 9 165 Separately Ordered Escutcheons Specify Style B2 or C Chrome Plated Institutional Escutcheons P N specify Style B2 56 001 7 512 Style C 56 001 7 513 Separately Ordered Wrenches Specify Model 1509 3 Sprinkler Wrench P N 56 001 5 093 Separately Ordered Parts For Installation In Concrete Walls Specify Model 1781 Centering Grommet for installation in...

Отзывы: