Model TFP PH5 — 5.6 K-factor 

Institutional Horizontal Sidewall Sprinklers 

Standard Response, Standard Coverage

Page 1 of 4 

AUGUST 2018 

TFP654

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The TYCO Model TFP PH5, 5.6 K-fac-

tor, Institutional Horizontal Sidewall 

Sprinklers are standard-response, 

 standard-coverage spray sprinklers 

designed for use in areas such as cor-

rectional, detention, and mental health 

care facilities.
The unique features of the Model 

TFP PH5 provide a tamper-resistant 

sprinkler design that helps eliminate 

the opportunity for individuals to injure 

themselves or others with components 

of a fire sprinkler. At the same time, 

the Model TFP PH5 optimizes an 

aesthetically appealing flush design 

that conceals most of the operating 

parts.

NOTICE

The TYCO Model TFP PH5 Institu-

tional Horizontal Sidewall Sprinklers 

described herein must be installed 

and maintained in compliance with 

this document, as well as with the 

applicable standards recognized by 

the Approval agency, in addition to 

the standards of any authorities having 

jurisdiction. Failure to do so may impair 

the performance of these devices.
Johnson Controls specifically dis-

claims any liability for damages or 

injury (including death) arising out of or 

caused by manipulation, dismantling, 

or misuse of TFP PH5 Sprinklers or the 

use or attempted use of the TFP PH5 

Sprinklers or any component thereof as 

an instrument unrelated to its intended 

function as a fire protection device.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Sprinkler 

Identification 

Number (SIN)

TY3390

Technical 

Data

Approvals

UL and C-UL Listed for light and ordinary 

hazard occupancies (Refer to the Design 

Criteria section.) 

NYC under MEA 351-01-E

Maximum Working Pressure

175 psi (12,1 bar)

Inlet Thread Connection

1/2 in. NPT

Discharge Coefficient

K = 5.6 GPM/psi

½

 (80,6 LPM/bar

½

)

Temperature Ratings

165°F (74°C)

Finishes

Sprinkler: Chrome Plated 

Escutcheon: Chrome Plated

Physical Characteristics

Body  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Deflector Hood . . . . . . . . . . . . . . . . . . . . .Bronze

Deflector Post . . . . . . . . . . . . . . . . . . . . . .Bronze

Deflector Post Pin . . . . . . . . . . . . . . . . . . .Bronze

Deflector Core . . . . . . . . . . . . . . . . . . . . . .Bronze

Compression Screw . . . . . . . . . . . . . . . . .Bronze

Lever . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Release Spring . . . . . . . . . . . . . . . . . . . . .Bronze

Sealing Assembly  . .Beryllium Nickel w/TEFLON

Dust Cover   . . . . . . . . . . . . .Chrome Plated Steel

Fusible Element  . . . . . . . . . . . . .Solder, Copper,  

Stainless Steel

Operation

In the standby condition, the design of 

the TYCO Model TFP PH5 is such that 

a dynamic load of 80 lb (36 kg) or more 

applied to the linkage mechanism will 

release the sprinkler. Also, when prop-

erly installed, the escutcheon is held 

fast to the wall to deter its removal. 

The shape of the escutcheon cannot 

be grasped easily, which further deters 

tampering.
A fusible solder operating element 

secures the linkage mechanism of the 

Model TFP PH5. When the rated tem-

perature is reached, the solder melts, 

releasing the linkage mechanism that 

holds the sprinkler closed. This release 

allows the deflector to extend outward 

and water to flow.

Содержание tyco TFP PH5

Страница 1: ...iability for damages or injury including death arising out of or caused by manipulation dismantling or misuse of TFP PH5 Sprinklers or the use or attempted use of the TFP PH5 Sprinklers or any component thereof as an instrument unrelated to its intended function as a fire protection device The owner is responsible for main taining their fire protection system and devices in proper operating con di...

Страница 2: ...ty of the sprinkler fitting to the mounting surface Installation The TYCO Model TFP PH5 Sprinklers must be installed in accordance with this section NOTICE Refer to the Design Criteria section for important information regarding the piping installation design and its effect on maintaining the integrity of the tam per resistant design of the Institutional Escutcheons Obtain a leak tight 1 2 in NPT ...

Страница 3: ...aned by means of gently dusting with a feather duster otherwise non operation in the event of a fire or inad vertent operation may result Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced Automatic sprinklers must never be painted plated coated or other wise altered after leaving the factory Modified sprinklers must be replaced Sprinklers that have ...

Страница 4: ...onal Horizontal Sidewall Sprin kler P N 51 106 9 165 Separately Ordered Escutcheons Specify Style B2 or C Chrome Plated Institutional Escutcheons P N specify Style B2 56 001 7 512 Style C 56 001 7 513 Separately Ordered Wrenches Specify Model 1509 3 Sprinkler Wrench P N 56 001 5 093 Separately Ordered Parts For Installation In Concrete Walls Specify Model 1781 Centering Grommet for installation in...

Отзывы: