background image

Model LD — 11.2 K-factor 

Large Drop Upright Sprinkler, Standard Response 

Control Mode Specific Application

Page 1 of 4 

AUGUST 2018 

TFP335

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The TYCO Model LD, 11.2 K-factor 

Large Drop Upright Sprinkler, Stan-

dard Response Control Mode Specific 

Application is a glass bulb type auto-

matic sprinkler. It is intended for use 

with the National Fire Protection Asso-

ciation large drop sprinkler installation 

criteria for the protection of high piled 

storage. The LD Sprinkler can provide a 

higher level of protection than standard 

spray sprinklers and, in some cases, 

can provide an economic advantage by 

eliminating in-rack sprinklers.

NOTICE

The TYCO Model LD 11.2 K-factor, 

Large Drop Upright Sprinkler described 

herein must be installed and maintained 

in compliance with this document, as 

well as with the applicable standards 

of the National Fire Protection Asso-

ciation, in addition to the standards of 

any other authorities having jurisdiction.

 

Failure to do so may impair the perfor-

mance of these devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Sprinkler 

Identification 

Number

Refer to Table A for sprinkler identifica-

tion number.

Technical 

Data

Approvals

UL and C-UL Listed 

NYC Approved under MEA 289-04-E

Finish

Natural Brass

Physical Characteristics

Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Sealing Assembly  . .Beryllium Nickel w/TEFLON

Bulb  . . . . . . . . . . . . . . . . . . . . . .Glass (5mm dia.)

Compression Screw . . . . . . . . . . . . . . . . . .Brass

Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Additional Technical Data

Refer to Table A for additional techni-

cal data.

Operation

The glass bulb contains a fluid that 

expands when exposed to heat. When 

the rated temperature is reached, the 

fluid expands sufficiently to shatter the 

glass bulb, allowing the sprinkler to 

activate and flow water.

Design 

Criteria

The TYCO Model LD, 11.2 K-factor 

Large Drop Upright Sprinkler, Stan-

dard Response Control Mode Specific 

Application is only for use with National 

Fire Protection Association “large drop 

sprinkler” installation criteria.

Отзывы: