Table 6: Technical specifications
Item
Description
Network autonomy
Distributed data and processing.
Certifications/listing
USA: UL 294, UL 1076, FCC Part 15 Class B
Canada: ICES-003 (B)/NMB-003 (B)
Europe: EN 60950-1, EN 62368-1, EN 50130-4, EN 61000-6-3. CE Compliance
in accordance with applicable LVD and EMC Directives.
Australia/New Zealand: RCM Compliance.
AES encryption
NIST CAVP validation number AES 3092, key length 128.
Note: 1.
The KT-1 has been tested by UL with the PoE/PoE+ models Phihong POE36U-1AT-
R and/or the POE125U-4-HP-R. These devices shall be used in conjunction with UL listed
transient protectors. Other compatible PoE/PoE+ configurations may be possible.
Note: 2.
The KT-1 can restart automatically after total power loss, and keeps its
programming for an unlimited time of power interruption. The design uses flash memory to
save access rules.
Note: 3.
For KT-1 and Class B installations powered with a PoE device, use a ferrite on the
Ethernet cable (P/N 10000089).
Front cover LEDs
The front cover of the KT-1 has several LEDs. The following table describes the status that each LED
indicates when it turns on.
Table 7: LED status indicators
Name
LED color Status
LINK (Ethernet)
Green
There is an Ethernet cable and a network connection. The
LED is off when there is no Ethernet network or the cable is
disconnected.
DATA (Ethernet) Yellow
There is network activity.
RX1
Yellow
The RS-485 serial port is receiving activity from the gateway.
TX1
Yellow
The RS-485 serial port is transmitting activity to the gateway.
RX2
Yellow
The LED is reserved for future use.
TX2
Yellow
The LED is reserved for future use.
R1 (Relay 1)
Red
Relay 1 is activated.
R2 (Relay 2)
Red
Relay 2 is activated.
L1 (Lock 1)
Red
Lock output 1 is activated.
L2 (Lock 2)
Red
Lock output 2 is activated.
POWER
Green or
yellow
The primary power supply is present. The type of power source
determines which color LED illuminates. The LED is green when
the DC level is sufficient for all DC terminals, such as the 12 V AUX.
Kantech shield
(One Button)
Blue
The controller is communicating with EntraPass or the controller's
IP mode is activated. For more information about this LED, see
Kantech shield LED
The LED on the Kantech shield shows the controller's communication status and other conditions.
Use this information when you connect the controller to the EntraPass system. The following table
lists all possible conditions.
18
KT-1 One-Door Controller Installation Guide
Содержание Tyco KT-1
Страница 1: ...KT 1 One Door Controller Installation Guide D29008966R009 2021 03 08 DN2186 2103 ...
Страница 2: ......
Страница 8: ......
Страница 24: ...Figure 5 KT 1 PCB inputs and outputs 22 KT 1 One Door Controller Installation Guide ...
Страница 26: ...Figure 6 KT 1 controller with KT PS4085 power supply 24 KT 1 One Door Controller Installation Guide ...
Страница 29: ...Figure 8 KT 1 PCB EU inputs and outputs KT 1 One Door Controller Installation Guide 27 ...
Страница 56: ...KT 1 One Door Controller Installation Guide 54 ...