Johnson Controls tyco iSTAR Edge G2 Скачать руководство пользователя страница 9

8

Wiring

Wiring Specifications and Components

Signal

From

To

AWG

Shield

Max Length

RS-485 Comm,

two wire

iSTAR Edge
G2

RM and I/O
Modules

22

Yes

4000 ft (1212m)

Power

iSTAR Edge
G2

RM and I/O
Modules

22/18

No

Range of 600 ft to
1500 ft, depending on
AWG used.

RJ-45-Ethernet

iSTAR Edge
G2

Hub, Host

Cat 5e

24

N/A

328 ft (100m)

Supervised Input

iSTAR Edge
G2

Input

22/18

No

2000 ft (606m)

Request-to-exit

(REX or RTE)

iSTAR Edge
G2

Switch

22/18

No

2000 ft (606m)

Door Contact (DSM)

iSTAR Edge
G2

Contact

22/18

No

2000 ft (606m)

Supervised Input

iSTAR Edge
G2

Input

22

Yes

2000 ft (606m)

Reader Input

iSTAR Edge
G2

Proximity/Wiegand
signaling read
head

22

20

18

Yes

200 ft (60.96m)

300 ft (91.4m)

500 ft (152.4m)

Table 4:  iSTAR and Components Wiring Specifications

There are 2 jumpers on the PoE module:

x1 jumper to select PoE or PoE Plus (+). Ensure the jumpers are set correctly if using PoE.

x1 jumper to configure the voltage used to power the Edge G2 and to supply the wet relays for door locks. Set the
jumper to 24 VDC for the Edge G2.

Do not connect the PoE injector to a receptacle controlled by a switch.

The Tamper, Battery Low, and AC Power Fail inputs must be enabled and connected to report to comply with UL
requirements.

NOTE

Shielded cable must be used for AC Fail in Low Battery input connections.

Supervised Inputs must use shielded, 22 AWG (minimum) stranded, twisted-pair cable, such as Belden 9462 or equivalent, for
monitor points, DSMs, and REXs.

Wiring methods must be in accordance with the National Electrical Code, ANSI/NFPA 70.

Connections between PSE or power injector and the PD must use 26 AWG (0.13mm2) for patch cords and 24 AWG (0.21mm2) for
horizontal or riser cables connected through standard 8-pin RJ-45 connectors.

Содержание tyco iSTAR Edge G2

Страница 1: ...iSTAR Edge G2 Controller Quick Start Guide March 2021 Revision B0 www swhouse com Document Number 8200 1917 01...

Страница 2: ...ble laws Products offerings and specifications are subject to change without notice Actual products may vary from photos Not all products include all features Availability varies by region contact you...

Страница 3: ...e G2 4 readers metalencl with 2 RM 4 Table 1 iSTAR and Components Wiring Specifications NOTE All controllers and networking equipment in a cluster must be UL listed to qualify as UL Listed Products US...

Страница 4: ...12 VDC RM RS485 Reader Ports 12 VDC 1 2 A each Relay Ports 30 VDC 3 0 A Dry 12 24 VDC 750mA Wet Voltage is same as source voltage minus current switch drop Alloutputs are Class 2 power limited Totalpo...

Страница 5: ...Edge G2 modules must be installed in an enclosure which has an electrically supervised tamper switch to maintain UL compliance For Proprietary Burglar Alarm installations the iSTAR Edge G2 must be ins...

Страница 6: ...Ethernet Connection x2 Ethernet port onboard supports 10 100 1000 Base T Ethernet connections Communications Full 256 bit encryption NOTE All cabling must be shielded 5...

Страница 7: ...outs for all of the wiring inputs and outputs 4 Remove the enclosure door and place it on a soft surface 5 Align the keyhole mounting slots at the upper back of the enclosure with the two upper mounti...

Страница 8: ...Figure 1 iSTAR Edge G2 Enclosure NOTE The WIFI BLE MODULE PHASE 2 shown in Figure 1 is a future option which may not be included on your current iSTAR Edge G2 board 7...

Страница 9: ...2 jumpers on the PoE module x1 jumper to select PoE or PoE Plus Ensure the jumpers are set correctly if using PoE x1 jumper to configure the voltage used to power the Edge G2 and to supply the wet rel...

Страница 10: ...0 or 2K are considered Alert The wiring for NO and NC is different as shown in Figure 2 Figure 2 NO NC Double Resistor 1K The NO NC Double Resistor method will report Short Normal Secure 1K Alert 500...

Страница 11: ...VDC Use NO or NC as appropriate The jumper is in the Dry position Wet Relay Wiring Figure 4 Wet Relay Wiring Figure 4 shows a wet relay wiring setup for a normal NO latch Max current is 0 75 A at 12 V...

Страница 12: ...wiring for a magnetic lock GND and NC pins are used for energized magnetic locks The jumper is in the Wet position Wiring for AC Fail Low Batteries Figure 6 AC Fail Low Battery wiring Figure 6 shows w...

Страница 13: ...s Wiegand Readers Figure 7 Wiegand Readers Figure 7 shows direct Wiegand signaling read head connections RS485 Readers Figure 8 RS485 Readers Figure 8 shows RS485 full duplex and half duplex reader co...

Отзывы: