iSTAR Edge G2 Controller
Quick Start Guide
March 2021
Revision: B0
www.swhouse.com
Document Number:8200-1917-01
Страница 1: ...iSTAR Edge G2 Controller Quick Start Guide March 2021 Revision B0 www swhouse com Document Number 8200 1917 01...
Страница 2: ...ble laws Products offerings and specifications are subject to change without notice Actual products may vary from photos Not all products include all features Availability varies by region contact you...
Страница 3: ...e G2 4 readers metalencl with 2 RM 4 Table 1 iSTAR and Components Wiring Specifications NOTE All controllers and networking equipment in a cluster must be UL listed to qualify as UL Listed Products US...
Страница 4: ...12 VDC RM RS485 Reader Ports 12 VDC 1 2 A each Relay Ports 30 VDC 3 0 A Dry 12 24 VDC 750mA Wet Voltage is same as source voltage minus current switch drop Alloutputs are Class 2 power limited Totalpo...
Страница 5: ...Edge G2 modules must be installed in an enclosure which has an electrically supervised tamper switch to maintain UL compliance For Proprietary Burglar Alarm installations the iSTAR Edge G2 must be ins...
Страница 6: ...Ethernet Connection x2 Ethernet port onboard supports 10 100 1000 Base T Ethernet connections Communications Full 256 bit encryption NOTE All cabling must be shielded 5...
Страница 7: ...outs for all of the wiring inputs and outputs 4 Remove the enclosure door and place it on a soft surface 5 Align the keyhole mounting slots at the upper back of the enclosure with the two upper mounti...
Страница 8: ...Figure 1 iSTAR Edge G2 Enclosure NOTE The WIFI BLE MODULE PHASE 2 shown in Figure 1 is a future option which may not be included on your current iSTAR Edge G2 board 7...
Страница 9: ...2 jumpers on the PoE module x1 jumper to select PoE or PoE Plus Ensure the jumpers are set correctly if using PoE x1 jumper to configure the voltage used to power the Edge G2 and to supply the wet rel...
Страница 10: ...0 or 2K are considered Alert The wiring for NO and NC is different as shown in Figure 2 Figure 2 NO NC Double Resistor 1K The NO NC Double Resistor method will report Short Normal Secure 1K Alert 500...
Страница 11: ...VDC Use NO or NC as appropriate The jumper is in the Dry position Wet Relay Wiring Figure 4 Wet Relay Wiring Figure 4 shows a wet relay wiring setup for a normal NO latch Max current is 0 75 A at 12 V...
Страница 12: ...wiring for a magnetic lock GND and NC pins are used for energized magnetic locks The jumper is in the Wet position Wiring for AC Fail Low Batteries Figure 6 AC Fail Low Battery wiring Figure 6 shows w...
Страница 13: ...s Wiegand Readers Figure 7 Wiegand Readers Figure 7 shows direct Wiegand signaling read head connections RS485 Readers Figure 8 RS485 Readers Figure 8 shows RS485 full duplex and half duplex reader co...