background image

TFP226

Page 2 of 4

Operation

The glass bulb contains a fluid that 

expands when exposed to heat. When 

the rated temperature is reached, the 

fluid expands sufficiently to shatter the 

glass bulb, allowing the sprinkler to 

activate and flow water.

Design 

Criteria

The EC-8C 8.0 K-factor Special Appli-

cation, Quick Response Pendent and 

Recessed Pendent Sprinklers must 

only be installed in accordance with 

the applicable UL Listing requirements 

as indicated below. Only the Style 30 or 

40 Recessed Escutcheon is to be used 

for recessed installation, as applicable.

UL Listing Requirements

1. 

The Series EC-8C Pendent Sprin-

klers may be used for the coverage 

areas shown in Table A, based on 

maintaining the minimum specified 

flow rate as a function of coverage 

area for all of the sprinklers in the 

design area.

2. 

With respect to heat sensitivity, 

the Series EC-8C Pendent Sprin-

klers can be used with unobstruct-

ed construction consisting of flat, 

smooth ceilings (including bar 

joists) with a maximum pitch of one 

in six as defined and permitted by 

NFPA 13.

3. 

The minimum allowable spacing 

between the Series EC-8C Pendent 

Sprinklers, to prevent cold sol-

dering, is 12 ft (3,7 m) in the 28 ft 

(8,5 m) long spray direction.

4. 

The Series EC-8C Pendent Sprin-

klers are not to be installed with the 

short spray direction, 8 ft (2,4 m) or 

10 ft (3,1 m), oriented towards an-

other Series EC-8C Pendent Sprin-

kler’s short spray direction (See 

Figure 6).

5. 

The Series EC-8C Pendent Sprin-

klers are to be installed in accor-

dance with all other requirements 

of NFPA 13 for extended coverage 

pendent sprinklers.

Installation

The Series EC-8C 8.0 K-factor Special 

Application, Quick Response Pendent 

and Recessed Pendent Sprinklers 

must be installed in accordance with 

this section.

General Instructions

Do not install any bulb type sprinkler 

if the bulb is cracked or there is a loss 

of liquid from the bulb. With the sprin-

kler held horizontally, a small air bubble 

should be present. The diameter of the 

air bubble is approximately 1/16 in. 

(1,6 mm).
A leak tight 3/4 in. NPT sprinkler joint 

should be obtained with a torque of 

10 to 20 lb-ft (13,6 to 27,1 N

·

m). Higher 

levels of torque may distort the sprin-

kler inlet with consequent leakage or 

impairment of the sprinkler.
Do not attempt to compensate for 

insufficient adjustment of an escutch-

eon plate by under-or over-tightening 

the sprinkler. Re-adjust the position of 

the sprinkler fitting to suit.

Step 1.

 The sprinkler must be installed 

with the deflector parallel to the mount-

ing surface. Pendent sprinklers must be 

installed in the pendent position. The 

deflector is marked with “<-28 FEET 

(8,5 M)->” to indicate the direction of 

the 28 ft (8,5 m) coverage length. The 

frame arms do not need to be aligned 

parallel to the sprinkler pipe.

Step 2.

 After installing the Style 30 or 

40 mounting plate (or other escutch-

eon, as applicable) over the sprinkler 

pipe threads, and with pipe thread 

sealant applied to the pipe threads, 

hand tighten the sprinkler into the 

sprinkler fitting.

Step 3.

 Wrench tighten the deflector so 

that the marking “<-28 FEET (8,5 M)->” 

on the deflector is in the direction of 

the 28 ft (8,5 m) coverage length. The 

frame arms do not need to be aligned 

parallel to the sprinkler pipe. Use 

only the W-Type 6 (End “B”) Sprinkler 

Wrench or with a recessed escutcheon 

the W-Type 7 Sprinkler Wrench. The 

wrench recess of the applicable sprin-

kler wrench (See Figures 4 and 5) is to 

be applied to the sprinkler wrench flats 

(See Figure 1).

Description

Coverage 

Area

Flow 

Rate

Pressure

TY4282 (K=8.0) 

Pendent

28 ft x 8 ft 

(8,5 m x 2,4 m)

23 gpm 

(87,1 lpm)

8.3 psi 

(0,6 bar)

28 ft x 10 ft 

(8,5 m x 3,1 m)

28 gpm 

(106 lpm)

12.3 psi 

(0,9 bar)

Note:

 For coverage area dimensions less than or between those listed, use the minimum flow required for 

the next highest coverage area.

-

-

-

-

-

-

4

2

3

1

6

5

Bulb

Button

Frame

Deflector

Components:

Temperature

rating indicated

on Deflector

Sealing

Assembly

Compression

Screw

*

*

*

RECESSED PENDENT

PENDENT

CROSS SECTION

1/2" (12,7 mm)

NOMINAL MAKE-IN

ESCUTCHEON

PLATE SEATING

SURFACE

STYLE 30 or 40

RECESSED

ESCUTCHEON

WRENCH

FLATS

6

5

3

1

2

4

2-7/8" (73,0 mm) DIA.

3/4" NPT

1-7/16"

(36,5 mm)

2-1/4"

(57,2 mm)

FIGURE 1 

SERIES EC-8C (TY4282)  

SPECIAL APPLICATION PENDENT AND RECESSED PENDENT SPRINKLER

TABLE A 

FLOW CRITERIA FOR UL LISTING 

OF SERIES EC-8C SPRINKLERS

Содержание tyco EC-8C Series

Страница 1: ...reas with a finished ceiling uses either the two piece Style 30 or 40 Recessed Escutcheon The Style 30 Recessed Escutcheon provides up to 1 2 in 12 7 mm of total adjust ment from the flush pendent posi tion whereas the Style 40 provides 3 4 in 19 1 mm of vertical adjustment from the flush pendent position The adjustment provided by the Recessed Escutcheons reduces the accuracy to which the fixed p...

Страница 2: ... 4 in NPT sprinkler joint should be obtained with a torque of 10 to 20 lb ft 13 6 to 27 1 N m Higher levels of torque may distort the sprin kler inlet with consequent leakage or impairment of the sprinkler Do not attempt to compensate for insufficient adjustment of an escutch eon plate by under or over tightening the sprinkler Re adjust the position of the sprinkler fitting to suit Step 1 The spri...

Страница 3: ...lers permitted in Short Spray Direction Direction parallel to Short Spray Direction only Maintain spacing requirements per Standard or Extended Coverage sprinkler Extended Coverage Sprinkler Series EC 8C Sprinkler Orient Long or Standard Coverage Sprinkler area adjacent to Series EC 8C Sprinkler Sprinklers permitted in Long Spray Direction Short Spray Direction SHORT SPRAY DIRECTION LONG SPRAY DIR...

Страница 4: ...rec ommended to be initially performed for corrosion resistant coated sprin klers after the installation has been completed to verify the integrity of the corrosion resistant coating Thereafter annual inspections per NFPA 25 should suffice however instead of inspecting from the floor level a random sampling of close up visual inspections should be made so as to better determine the exact sprinkler...

Отзывы: