background image

TFP591

Page 3 of 4

the face of the fitting to the outside of 

the protected area may be determined 

by interpolating between the indicated 

values.

NOTE: The temperature within the 

protected area must be based on 

the lowest expected temperature. 

For example: a freezer may be rated 

at -20°F (-29°C), yet the condenser is 

emitting -30°F (-35°C). The dry sprin-

kler length must be calculated based 

on the lower temperature of -30°F 

(-35°C).

Sprinkler Fitting

TFP Dry Type Sprinklers must be 

installed in the 1 in. NPT outlet or run 

of a malleable or cast iron threaded tee 

as described in the applicable technical 

data sheets. With reference to Figure 

4 and in conjunction with use in a wet 

pipe system, the sprinkler drop may be 

installed as shown. The information in 

Figure 4 may only be used where the 

sprinkler fitting and water filled pipe 

above the sprinkler fitting is not subject 

to freezing. In areas subject to freez-

ing, the pipe connected to the dry type 

sprinkler must be configured to allow 

complete drainage as shown in Figure 

5.

Installation

The TYCO Model DSB-2 must be 

installed in accordance with this 

section.

WARNING

The Adhesive contains cyanoacrylate 

ester. Irritation will occur when inhaled. 

This adhesive bonds skin in seconds. 

Contact through clothing may cause 

burns. EYE IRRITANT.
Always refer to the Material Safety Data 

Sheet for additional adhesive handling 

recommendations. The Material Safety 

Data Sheet should be obtained from 

the adhesive manufacturer via their 

web site noted on the adhesive con-

tainer label before using the adhesive.
In case of skin contact, flush with 

water, and for eye contact seek medical 

attention.
Provide adequate ventilation in area 

of usage. When possible ventilation 

should be achieved by the use of local 

exhaust ventilation and good general 

ventilation. Vapors are heavier than air, 

therefore, downward ventilation should 

be used. When handling cyanoacrylate 

adhesives, goggles or safety glasses 

should always be worn. Polyethylene 

gloves should be used to protect the 

hands.

HEATED

AREA

DSB-2

SIDE

OUTLET

PLUGGED

TO WET

SYSTEM

(SEE DESIGN

CRITERIA

SECTION)

FITTING

SPRINKLER

DSB-2

DRY

SYSTEM

RUN

OUTLET

PLUGGED

FITTING

(SEE DESIGN

CRITERIA

SECTION)

SPRINKLER

AREA

SUBJECT

TO

FREEZING

TFP

DRY TYPE

SPRINKLER

EXPOSURE LENGTH

(SEE DESIGN CRITERIA

SECTION)

DSB-2

SPRINKLER

FITTING

HEATED

AREA

FREEZER

AREA

FIGURE 3 

EXPOSURE LENGTH

FIGURE 4 

SPRINKLER FITTING IN HEATED AREA

FIGURE 5 

SPRINKLER FITTING IN UNHEATED AREA

Содержание tyco DSB-2

Страница 1: ...ION ASSOCIATION in addition to the standards of any other authorities having jurisdiction Failure to do so may impair the performance of these devices The owner is responsible for main taining their fire protection system and devices in proper operating con dition Contact the installing contrac tor or product manufacturer with any questions Technical Data Approvals The TYCO Model DSB 2 Dry Sprin k...

Страница 2: ...et pipe sprinkler systems protecting areas subject to freezing temperatures e g sprinkler drops into freezers con sideration must be given to the appro priate length of the sprinkler that will prevent freezing of the water in the con necting pipes due to conduction When the temperature surrounding the wet pipe sprinkler system is maintained at a minimum temperature of 40 F 4 C the following are th...

Страница 3: ...hesive contains cyanoacrylate ester Irritation will occur when inhaled This adhesive bonds skin in seconds Contact through clothing may cause burns EYE IRRITANT Always refer to the Material Safety Data Sheet for additional adhesive handling recommendations The Material Safety Data Sheet should be obtained from the adhesive manufacturer via their web site noted on the adhesive con tainer label befo...

Страница 4: ... water The use of other cleaning techniques solvents etc may render the adhesive incapable of sealing Step 5 Apply the provided Adhesive to the building structure in a zig zag pattern Refer to Warning regarding the adhesive Step 6 Slide the Boot so that it comes in contact with the building structure and then press the Boot firmly against the building structure to help ensure that the Adhesive is ...

Отзывы: