and after installation. Nozzles damaged 

by dropping, striking, wrench twist/

slippage, or the like, must be replaced. 

Also, replace any nozzle that has a 

cracked bulb or that has lost liquid from 

its bulb (Ref. Installation section).
Frequent visual inspections are recom-

mended to be initially performed for 

nozzles installed in potentially corro-

sive atmospheres to verify the integ-

rity of the materials of construction 

and finish as they may be affected by 

the corrosive conditions present for a 

given installation. Thereafter, annual 

inspections per applicable standards 

are required, in addition to inspec-

tions required by the authority having 

jurisdiction.
The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of any other authorities having juris-

diction. Contact the installing contrac-

tor or product manufacturer with any 

questions.
Water mist systems should be in-

spected, tested, and maintained by a 

qualified Inspection Service in accor-

dance with local requirements and/or 

national codes.

Care and 

Maintenance

TYCO Ultra Low Flow AQUAMIST Type 

ULF AM28 Nozzles must be maintained 

and serviced in accordance with this 

section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system 

that it controls, obtain permission to 

shut down the affected fire protection 

system from the proper authorities 

and notify all personnel who may be 

affected by this action.
Nozzles which are found to be leaking 

or exhibiting visible signs of corrosion 

must be replaced.
Automatic nozzles must never be 

painted, plated, coated, or other-

wise altered after leaving the factory. 

Modified nozzles must be replaced. 

Nozzles that have been exposed to 

corrosive products of combustion, but 

have not operated, should be replaced 

if they cannot be completely cleaned 

by wiping the nozzle with a cloth or by 

brushing it with a soft bristle brush.
Care must be exercised to avoid 

damage to the nozzles before, during, 

Limited 

Warranty

For warranty terms and conditions, visit 

www.tyco-fire.com.

Ordering 

Procedure

Contact your local distributor for avail-

ability. When placing an order, indicate 

the full product name and part number 

(P/N).

Type ULF AM28 AQUAMIST Nozzles

Specify: Type ULF AM28 AQUAMIST 

Nozzle with 57ºC (135ºF) tempera-

ture rating, finish (specify), and P/N 

(specify):

Natural Brass . . . . . . . . . . . . . . . . . 49-028-1-135

Pure White (RAL9010)

a

  . . . . . . . . .49-028-3-135

Signal White (RAL9003)

b

. . . . . . . .49-028-4-135

Chrome Plated . . . . . . . . . . . . . . . .49-028-9-135

a.  Eastern Hemisphere sales only
b.  Formerly known as Bright White

Escutcheon

Specify: Style 20 Recessed Escutch-

eon with (specify*) finish, P/N (specify*)

* Refer to Technical Data Sheet TFP770

Wrench

Specify: W-Type 6 Sprinkler Wrench, 

P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench, 

P/N 56-850-4-001

Отзывы: