background image

TFP2202

Page 2 of 2

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;

TEFLON is a registered trademark of DuPont

1400 Pennbrook Parkway, Lansdale, PA 19446 | Tel1-215-362-0700

© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

Care and 

Maintenance

The TYCO AQUAMIST Nozzle Type 

AM31 must be maintained and ser-

viced in accordance with this section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system 

that it controls, obtain permission to 

shut down the affected fire protection 

system from the proper authorities 

and notify all personnel who may be 

affected by this action.
Type AM31 AQUAMIST Nozzle must 

never be painted, plated, coated or 

altered in any way after leaving the 

factory; otherwise, the spray perfor-

mance may be impaired.
Care must be exercised to avoid 

damage to the nozzles -before, during, 

and after installation. Nozzles damaged 

by dropping, striking, wrench twist/slip-

page, or the like, must be replaced.
Frequent visual inspections are rec-

ommended to be initially performed 

for nozzles installed in potentially cor-

rosive atmospheres to verify the integ-

rity of the materials of construction and 

finish as they may be affected by the 

corrosive conditions present for a given 

installation. Thereafter, annual inspec-

tions per NFPA 25 are required.
The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of the NATIONAL FIRE PROTECTION 

ASSOCIATION, for example, NFPA 25, 

in addition to the standards of any other 

authorities having jurisdiction. Contact 

the installing contractor or sprinkler 

manufacturer with any questions. 

Water spray fixed systems should be 

inspected, tested, and maintained by 

a qualified Inspection Service in accor-

dance with local requirements and/or 

national codes

Limited 

Warranty

For warranty terms and conditions, visit 

www.tyco-fire.com.

Ordering 

Procedure

Contact your local distributor for avail-

ability. When placing an order, indicate 

the full product name and Part Number 

(P/N).

Type AM31 AQUAMIST Nozzle

Specify: Type AM31 AQUAMIST 

Nozzle, Stainless Steel finish, P/N 

28229

Type AM31 AQUAMIST Nozzle with 

Dust Cap

Specify: Type AM31 AQUAMIST 

Nozzle, Stainless Steel, with Fluorosili-

cone Dust Cap, P/N 28250

Replacement Parts Dust Cap 

Assembly

Specify: Model F885 Dust Cap Assem-

bly, Fluorosilicone, with Stainless Steel 

Wire,* P/N 28247

*  Refer to Technical Data Sheet TFP2299 

for installation instructions.

Sprinkler Wrench

Specify: W-Type 6 Wrench, 

P/N 56-000-6-387

1-1/16"

(27,0 mm)

2"

(50,8 mm)

7/16"

(11,1 mm)

NOMINAL

MAKE-IN

WRENCH

FLATS

FACE OF

NOZZLE

FITTING

- Diffuser

3

4

5

Dust Cap

Assembly

4

5 -

- Strainer

1

Orifice

Insert
Frame

3 -

2

2 -

Components:

1

1/2" NPT

1.22"

(31,0 mm)

WRENCH RECESS

(USE ONLY

END "A")

FIGURE 1 

TYPE AM31 AQUAMIST NOZZLE 

NOMINAL DIMENSIONS AND ASSEMBLY

FIGURE 2 

W-TYPE 6  

SPRINKLER WRENCH

Отзывы: