background image

TEC26x7-2 Series BACnet® MS/TP Networked Thermostats with Two Outputs Installation Instructions 

13

Connecting the MS/TP Bus

To connect the MS/TP Bus:

1.

Set the MS/TP address of the TEC26x7-2 Series 
Thermostat per the engineering drawings and test 
for bus voltage, polarity, and isolation prior to wiring 
the MS/TP Bus. (See the 

Com addr

 parameter in 

Table 5 to set the MS/TP address for the 
thermostat.)

Note:

Pressing and holding the 

UP/DOWN

 arrow keys 

simultaneously displays the MS/TP address that is 
assigned.

Note:

The wiring rules for the MS/TP Bus differ from 

the wiring rules for the N2 Bus. For more details on 
wiring the MS/TP Communications Bus, refer to the 

MS/TP Communications Bus Technical  Bulletin 
(LIT-12011034)

.

2.

Observe the polarity when connecting the bus 
wires to the thermostat.

3.

After the bus wires are connected to the first 
thermostat, continue in a daisy-chained fashion to 
the next thermostat.

Note:

The bus wiring must be twisted-pair lines. Do 

not run the bus wiring in the same conduit as line 
voltage wiring (30 VAC or above) or other wiring that 
switches power to highly inductive loads (such as 
contactors, coils, motors, or generators).

The MS/TP Bus requires proper termination and 
biasing at each end of a segment (a segment is a 
physically continuous length of wire). The thermostat is 
not equipped with the ability to provide this termination; 
therefore, it is not recommended that it be located at 
the physical ends of a bus segment.

Note:

See Table 6 for end-of-line terminator ordering 

information.

It is recommended that the thermostat be configured 
for automatic baud rate detection. Do not exceed the 
maximum number of devices allowed on a Field Bus. 
Be sure that the wiring terminations are set correctly, 
and that all communication wiring is daisy-chained with 
no taps.

A small green light under the thermostat cover (on the 
left edge when facing the thermostat) indicates the 
communications mode when the thermostat is 
operating. The following blink codes may be seen:

Short-Short-Long: Indicates that the baud rate is 
known and that communication is active.

Short-Short: Indicates that the thermostat is 
scanning for the correct baud rate and that there is 
no communication.

Off: indicates that there is no power to the 
thermostat or that the MS/TP wiring polarity is 
reversed.

Long: Indicates that the MS/TP communication 
daughter board is the wrong type for the main 
board.

MS/TP Device Mapping

Preparation

Before mapping a TEC26x7-2 Series Thermostat into a 
Network Automation Engine (NAE):

1.

Decide which point objects within the thermostat 
need to be mapped. Only map the point objects 
that need to be viewed on a regular basis, since 
excessive mapping lowers system performance. 
Suggested point objects for mapping include: 
Room Temp, System Mode, Fan Status, Occupied 
Heat Setpoint, Occupied Cool Setpoint, 
Unoccupied Heat Setpoint, and Unoccupied Cool 
Setpoint. In addition, alarm points may be mapped 
if they are used, and other point objects may be 
mapped if required. Use the Engineering view to 
examine infrequently used point objects.

Note:

It is recommended that all thermostat 

configuration parameters be set as desired, prior to 
mapping the objects into the controller. If any 
thermostat configuration parameters are altered after 
the objects are mapped into the controller, it is 
recommended that all objects be re-mapped.

2.

Verify that a Field Bus is defined in the NAE. 
BACnet MS/TP devices attach to a Field Bus. 
Refer to the 

BACnet MS/TP Integration with the 

NAE Technical Bulletin (LIT-12011013)

 for 

instructions on how to define a Field Bus.

3.

Verify that a BACnet Integration is defined for the 
Field Bus. The thermostat is mapped as a BACnet 
device under a Field Bus BACnet Integration. 
Refer to the 

BACnet System Integration with NAE 

Technical Bulletin (LIT-1201531)

 for instructions on 

how to define a BACnet Integration.

At this point, the thermostat and the required point 
objects inside the thermostat can be mapped.

Содержание TEC2627-2

Страница 1: ...anual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his her own expense Canada This Class A digital apparatus meets all the requirements of the Canadian Interference Causing Equipment Regulations Cet appareil numérique de la Class...

Страница 2: ...ions Note Be sure to position the thermostat mounting base so that the arrow on the base points upward to indicate the top of the thermostat 6 Drill a 3 16 in 5 mm hole at each of the two marked locations and tap nylon anchors included with the thermostat flush to the wall surface 7 Position the thermostat mounting base on the wall and use the two mounting screws included with the thermostat to se...

Страница 3: ...nnectors 5 Reattach the thermostat cover to the mounting base top side first 6 Use a Phillips head screwdriver to reinstall the security screw on the bottom of the thermostat cover CAUTION Risk of Electric Shock Disconnect the power supply before making electrical connections to avoid electric shock CAUTION Risk of Property Damage Do not apply power to the system before checking all wiring connect...

Страница 4: ...ote Override Filter Alarm Service Alarm Voltage Free Contact Remote NSB Motion Window Three Pole Right Top Connector 9 10 11 12 13 14 15 16 REF BO2 BO5 Aux BO5 Aux Scom BO1 AO1 UI3 BI1 BI2 BO3 Two Pole Left Top Connector 24 V Hot 24 V Com BO4 AO2 RS Same 24 VAC Power Source for Auxiliary Output 24 VAC Maximum Separate 24 VAC Power Source for Auxiliary Output 24 VAC Maximum BO5 Aux BO5 Aux 24 VAC T...

Страница 5: ...Thermostat for Proportional 0 to 10 VDC Control Pressure Dependent VAV Cooling Only Room Temperature Control Thermostat Minimum and Maximum Position Adjusted on Actuator Proportional Actuator FIG tec2647_clng_only 0 to 10 VDC UI3 COS 24 V Com 24 V Hot AO1 Figure 8 Wiring the TEC2627 2 Thermostat for Floating Control Pressure Dependent VAV Heating Cooling with Changeover FIG tec2627_htng_clng_chngv...

Страница 6: ...ng with Changeover and Reheat FIG tec2627_htng_clng_chngvr_rht Changeover Sensor Room Temperature Control Thermostat Minimum and Maximum Position Adjusted on Actuator Heating Cooling and On Off Duct Heater Floating Actuator Supply Air Temperature Sensor 1 C UI3 COS 24 V Com 24 V Hot BO1 Open BO2 Close BO5 Aux BO5 Aux Figure 11 Wiring the TEC2647 2 Thermostat for Proportional 0 to 10 VDC Control Pr...

Страница 7: ... TEC2647 2 Thermostat for Proportional 0 to 10 VDC Control Heating Cooling Hydronic Valve Control FIG tec2647_htng_clng_hdrnc Room Temperature Control Thermostat 0 to 10 VDC UI3 COS 24 V Com 24 V Hot AO1 Figure 14 Wiring the TEC2627 2 Thermostat for Floating Control Heating Cooling Hydronic Valve Control with Changeover FIG tec2627_htng_clng_hdrnc_chngvr Floating Heating Cooling Valve Optional Wat...

Страница 8: ...om Temperature Control Thermostat Supply Water Temperature Sensor 0 to 10 VDC UI3 COS 24 V Com 24 V Hot AO1 Figure 16 Wiring the TEC2627 2 Thermostat for On Off Control Two Pipe Applications Four Pipe Applications TEC2627onoff 24 V Com 24 V Hot or 24 V Com 24 V Hot Cooling Valve or Heating Valve or Figure 17 Wiring the TEC2627 2 Thermostat for Floating Control Two Pipe Applications Four Pipe Appli...

Страница 9: ... System Mode3 MSV 13 1 Off 2 Cool 3 Heat 4 Auto Occupancy3 MSV 12 1 Resume Schedule 2 Occupied 3 Unoccupied 4 Temporary Occupied PI Heating Demand5 AV 54 0 to 100 PI Cooling Demand5 AV 55 0 to 100 Supply Temperature5 AI 11 40 0 F 40 0 C to 122 0 F 50 0 F AUX BO5 Status5 BI 65 0 Off 1 On AUX BO5 Output3 BV 47 0 Off 1 On Heating BO3 and BO4 Valve Status TEC2627 2 Model 5 MSV 66 For On Off Control 1 ...

Страница 10: ...nt3 7 AV 49 40 0 F 4 5 C to 90 0 F 32 0 C Occupied Cool Setpoint3 7 AV 50 54 0 F 12 0 C to 100 0 F 37 5 C Unoccupied Heat Setpoint3 7 AV 51 40 0 F 4 5 C to 90 0 F 32 0 C Unoccupied Cool Setpoint3 7 AV 52 54 0 F 12 0 C to 100 0 F 37 5 C Keypad Lockout3 MSV 40 1 Level 0 2 Level 1 3 Level 2 4 Level 3 5 Level 4 6 Level 5 BI1 Configuration3 MSV 16 1 None 2 Rem NSB 3 Motion NO 4 Motion NC 5 Window BI2 C...

Страница 11: ...0 Hours 2 1 Hour 3 2 Hours 4 3 Hours 5 4 Hours 6 5 Hours 7 6 Hours 8 7 Hours 9 8 Hours 10 9 Hours 11 10 Hours 12 11 Hours 13 12 Hours 14 13 Hours 15 14 Hours 16 15 Hours 17 16 Hours 18 17 Hours 19 18 Hours 20 19 Hours 21 20 Hours 22 21 Hours 23 22 Hours 24 23 Hours 25 24 Hours Door Time3 MSV 31 1 1 Minute 2 2 Minutes 3 3 Minutes 4 4 Minutes 5 5 Minutes 6 6 Minutes 7 7 Minutes 8 8 Minutes 9 9 Minut...

Страница 12: ...ide object of Room Temp Override This corresponding override object needs to be set to 1 Override to be able to write Room Temp to a different value 2 This MS TP Bus object may automatically release after 10 minutes with no BACnet traffic 3 This MS TP Bus object is readable and writable 4 This MS TP Bus object is valid only if it is written via the network 5 This MS TP Bus object is readable only ...

Страница 13: ...the thermostat indicates the communications mode when the thermostat is operating The following blink codes may be seen Short Short Long Indicates that the baud rate is known and that communication is active Short Short Indicates that the thermostat is scanning for the correct baud rate and that there is no communication Off indicates that there is no power to the thermostat or that the MS TP wiri...

Страница 14: ...anged by writing a new one into the thermostat device object that should be done before any point objects are mapped Be sure that the ID of the new thermostat being added to the NAE matches that of the thermostat itself This number goes into the Instance Number field Network section Hardware tab of the Configure step in the Insert Field Device Wizard Adding Point Objects The required point objects...

Страница 15: ...he TEC26x7 2 Series Thermostats include a 2 line 8 character backlit display Low level backlighting is present during normal operation and it brightens when any user interface key is pressed The backlight returns to low level when the thermostat is left unattended for 45 seconds Light Emitting Diodes LEDs Two LEDs are included to call for heat or call for cooling The HEAT LED is on when heating or...

Страница 16: ...t the thermostat Each input can be configured to the Selection Options included in Table 5 Configuring the Output Options Out1Conf For applications that enable heating cooling operation from the same output choose the selection option 2 0 in the Out1Conf parameter For applications that enable heating cooling operation from different outputs choose the selection option 4 0 Configuring the Sequence ...

Страница 17: ...our Pipe See Figure 24 8 N O Heating 9 N C Heating 10 N O Cooling 11 N C Cooling 8 Open Heating 9 Closed Heating 10 Open Cooling 11 Closed Cooling 9 Proportional Heating 10 Proportional Cooling 5 Cool Heat Four Pipe and Reheat See Figure 25 6 and 7 Reheat 8 N O Heating 9 N C Heating 10 N O Cooling 11 N C Cooling 6 and 7 Reheat 8 Open Heating 9 Closed Heating 10 Open Cooling 11 Closed Cooling 6 and...

Страница 18: ...s Temperature Increase Increments of 1F 0 5C Heating Setpoint Device Closed Cooling Setpoint Device Opened FIG htng_clng Deadband On Off Floating or Proportional Outputs Heating Output Cooling Output Off Off On On Figure 25 Heating Cooling with Reheat Four Pipe Applications Temperature Increase Increments of 1F 0 5C Heating Setpoint Device Closed Device Closed Device Opened Cooling Setpoint Device...

Страница 19: ...at heating or cooling action when a window is open A Window alarm is displayed indicating that the window needs to be closed to resume heating or cooling These settings disable any local override function When this setting is selected the heating and or cooling outputs are enabled only when the contact is closed BI2 Configuration of Binary Input 2 Default None None No function is associated with a...

Страница 20: ...eters Default on off The scroll is inactive on The scroll is active C or F Provides temperature scale options for display Default F C Celsius scale F Fahrenheit scale Lockout Selectable Lockout Levels for limiting end user keypad interaction Default 0 Lockout Level Function Unoccupied Override Occupied Temperature Setpoints 0 Access Access 1 No Access Access 2 This lockout level is not used 3 This...

Страница 21: ...ue Default 80 0 F 26 5 C Range 54 0 F 12 0 C to 100 0 F 37 5 C Heat max Sets the Occupied and Unoccupied maximum Heating setpoint values Default 90 0 F 32 0 C Range 40 0 F 4 5 C to 90 0 F 32 0 C Cool min Sets the Occupied and Unoccupied minimum Cooling setpoint values Default 54 0 F 12 0 C Range 54 0 F 12 0 C to 100 0 F 37 5 C Set type Provides the option of temporarily changing the heating or coo...

Страница 22: ...ed the option functions like option 1 or 2 respectively FL time Sets the maximum actuator stroke timing floating ContrlTyp TEC2627 2 model Default 1 5 min Range 0 5 to 9 0 min adjustable in 0 5 minute increments Cph Sets the maximum number of cycles per hour on off CntrlTyp TEC2627 2 model Default 4 Range 3 to 8 cycles per hour RA DA Choice of reverse or direct acting analog output signal TEC2647 ...

Страница 23: ...ooting Details1 Part 1 of 2 Symptom Probable Causes Multiple Symptoms Excessive bus errors may be occurring A device may have been added or changed with a duplicate address may not be the same address as some devices having problems and may have happened sometime before the problem was noticed Wiring errors or wire problems may exist The baud rate may have been changed on some devices on the netwo...

Страница 24: ...accordance with the programmable Binary Input BI1 Table 7 Troubleshooting Details1 Part 2 of 2 Symptom Probable Causes TEC26x7 2 Series BACnet MS TP Networked Thermostats with Two Outputs Part 1 of 2 Power Requirements 19 to 30 VAC 50 60 Hz 2 VA Terminals 4 and 5 at 24 VAC Nominal Class 2 or Safety Extra Low Voltage SELV Relay Triac Contact Rating On Off and Floating Control 30 VAC 1 0 A Maximum 1...

Страница 25: ...XAPX7 Under CAN CSA C22 2 No 24 Temperature Indicating and Regulating Equipment Industry Canada ICES 003 Europe CE Mark EMC Directive 89 336 EEC Australia and New Zealand C Tick Mark Australia NZ Emissions Compliant Shipping Weight 0 75 lb 0 34 kg The performance specifications are nominal and conform to acceptable industry standards For application at conditions beyond these specifications consul...

Отзывы: