Mounting

Location Considerations

Locate the TE730 Series Temperature Sensor:

on a partitioning wall, approximately 1.5 m (5 ft) 
above the floor in a location of average 
temperature

away from direct sunlight, radiant heat, outside 
walls, outside doors, air discharge grills, or 
stairwells; and from behind doors

away from steam or water pipes, warm air stacks, 
unconditioned areas (not heated or cooled), or 
sources of electrical interference

Note:

The temperature sensor is shock and vibration 

resistant; however, be careful not to drop the unit or 
mount it where it could be exposed to excessive 
vibration.

The following ambient operating conditions apply:

Temperature: 0 to 40°C (32 to 104°F)

Humidity: 10 to 90% Relative Humidity (RH), 
noncondensing; 30°C (86°F) maximum dew point

To mount the temperature sensor to the wall:

1.

Use a 1.5 mm (1/16 in.) Allen wrench or 
Johnson Controls T-4000-119 Allen-Head 
Adjustment Tool to loosen the security screw on 
the top of the unit.

2.

Insert a coin into the slot next to the security screw 
location, then carefully pry the top edge of the 
temperature sensor assembly away from its 
mounting base and remove.  

3.

Pull out approximately 152 mm (6 in.) of cable from 
the wall, and insert the cable through the hole in 
the mounting base.

4.

Align the mounting base on the wall, and use the 
base as a template to mark the location of the two 
mounting holes on the surface. 

Note:

Confirm that the mounting base is positioned 

with the proper edge up. The mounting base is 
positioned properly when the security screw is located 
on the top edge of the base.

5.

Secure the mounting base to the wall using the 
appropriate mounting hardware (field furnished).

6.

Align the tabs on the bottom edge of the mounting 
base with the slots on the bottom edge of the 
temperature sensor assembly, and rotate the 
assembly onto its mounting base.

7.

Use a 1.5 mm (1/16 in.) Allen wrench or 
Johnson Controls T-4000-119 Allen-Head 
Adjustment Tool to tighten the security screw and 
fasten the temperature sensor assembly to the 
mounting base.

Wiring

Keep wires as short as possible to minimize 
temperature sensor error. Each 76 m (250 ft) run of 
1.0 mm diameter (18 AWG) wire or 15 m (50 ft) of 
0.5 mm diameter (24 AWG) wire creates 0.83C° 
(1.5F°) of error for a platinum sensor due to wire 
resistance. To maintain less than 0.83C° (1.5F°) of 
error, hold the total resistance of all temperature sensor 
wiring below 3 ohms. When wiring the temperature 
sensor, do not run low voltage wiring in the same 
conduit as line voltage wiring or other conductors 
supplying highly inductive loads.      

IMPORTANT:

Do not remove the Printed Circuit 

Board (PCB). Removing the PCB voids the product 
warranty.

!

CAUTION: Risk of Property Damage.

Do not apply power to the system before 
checking all wiring connections. Short 
circuited or improperly connected wires 
may result in permanent damage to the 
equipment.

MISE EN GARDE : Risque de dégâts 
matériels.

Ne pas mettre le système sous tension 
avant d'avoir vérifié tous les raccords de 
câblage. Des fils formant un court-circuit 
ou connectés de façon incorrecte 
risquent d'endommager 
irrémédiablement l'équipement.

IMPORTANT:

Use copper conductors only. Make 

all wiring connections in accordance with local, 
national, and regional regulations.

Содержание TE730 Series

Страница 1: ...e TE730 Series Temperature Sensors are intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the temperature sensor could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or alarm sys...

Страница 2: ...itioned properly when the security screw is located on the top edge of the base 5 Secure the mounting base to the wall using the appropriate mounting hardware field furnished 6 Align the tabs on the bottom edge of the mounting base with the slots on the bottom edge of the temperature sensor assembly and rotate the assembly onto its mounting base 7 Use a 1 5 mm 1 16 in Allen wrench or Johnson Contr...

Страница 3: ... polarity not reversed Misalignment can cause damage b Check all supply voltage connections 3 Check the settings a Verify that any scaling modifications setpoint adjustments and overrides have been saved and downloaded to the digital controller b Check the override status Temporary Occupancy mode vs Unoccupied mode at the digital controller c Check the setpoint settings 4 Replace the temperature s...

Страница 4: ...l Occupancy Override TE730 39C 0 Model Integral Manual Occupancy Override Push Button Ambient Operating Conditions 0 to 40 C 32 to 104 F 10 to 90 RH Noncondensing 30 C 86 F Maximum Dew Point Ambient Storage Conditions 40 to 60 C 40 to 140 F 5 to 95 RH Noncondensing 30 C 86 F Maximum Dew Point Materials White Thermoplastic Enclosure Accessory NS WALLPLATE 0 Adapts the TE730 Series Temperature Senso...

Отзывы: