Warmer/Cooler Setpoint and No Setpoint
Models
For the Warmer/Cooler Setpoint and No Setpoint models,
the factory default is the
LED Mode:ON
described as
follows. The switch positions enable/disable the following
functions:
Table 3: Warmer/Cooler Setpoint and No Setpoint
models switch positions status
Status
Description
LED Mode: OFF
(LED
Disabled, but Sensor and PB
Enabled)
Switch positions are down,
up, and down. The LED
remains off at all times.
LED Mode: ON
(LED, Sensor,
and PB Enabled)
Switch positions are
factory set up, down,
and up. The controller
determines the LED mode.
LED Mode: NO PB
(LED and
PB Disabled, but Sensor
Enabled)
Switch positions are all
down. LED is off, and the
PB does not function.
Figure 5: DIP Switch Positions
Table 4: Controller Compatibility with LED Mode and PB
Features Recognized by Controller
Types of TE-6800 LED Mode
Features
Enabled on
TE-6800
AHU
UNT1100
VAV1xx or
UNT1xx
1
VMA1200
Series
VMA1400
Series
2
LED Off
Sensor and
Manual
Override
No
Yes
Yes
Yes
Yes
LED On
Sensor,
Manual
Override,
and LED
No
No
No
Yes
Yes
Warmer/Cooler
Setpoint
No PB
Room
Sensor Only
Yes
Yes
Yes
Yes
Yes
1
For these controllers, the LED appears brighter when the manual override PB is pushed.
2
Holding the manual Override PB for more than 2 seconds may affect the sensor reading.
Temperature Setpoint
Adjust the setpoint using the setpoint adjustment dial. Rotate clockwise to raise the temperature. Rotate
counterclockwise to lower the temperature.
TE-6800 Series Temperature Sensors Installation Guide
4