background image

TE-6800 Series Temperature Sensors Installation

Guide

Applications

The TE-68xx-xN00S Series provides temperature sensing

in room wall mount applications. It allows local setpoint

temperature adjustment and temporary occupancy

override.
A warmer/cooler dial is included on certain models for

minor temperature adjustments from the setpoint. An

occupancy override button allows the user to request

a time-of-day scheduling override when the space is

occupied outside of the normal occupied hours schedule.

All sensors have DIP switches that enable or disable unit

functions.
Depending on the model chosen, the wires connecting the

sensor to the controller can be terminated using a screw

terminal block or modular jack connection, offering wiring

flexibility. All models include a Zone Bus access port for

connecting accessories to access the 6-pin modular jack.

This feature allows a technician to commission or service

the controller via the sensor.

Important: 

The TE-6800 Series Temperature Sensor

is intended to provide an input to equipment

under normal operating conditions. Where

failure or malfunction of the sensor could lead

to personal injury or property damage to the

controlled equipment or other property, additional

precautions must be designed into the control

system. Incorporate and maintain other devices,

such as supervisory or alarm systems or safety or

limit controls, intended to warn of or protect against

failure or malfunction of the sensor.

Important: 

Le TE-6800 Series Temperature Sensor

est destiné à transmettre des données entrantes

à un équipement dans des conditions normales

de fonctionnement. Lorsqu'une défaillance ou un

dysfonctionnement du sensor risque de provoquer

des blessures ou d'endommager l'équipement

contrôlé ou un autre équipement, la conception du

système de contrôle doit intégrer des dispositifs de

protection supplémentaires. Veiller dans ce cas à

intégrer de façon permanente d'autres dispositifs,

tels que des systèmes de supervision ou d'alarme, ou

des dispositifs de sécurité ou de limitation, ayant une

fonction d'avertissement ou de protection en cas de

défaillance ou de dysfonctionnement du sensor.

Installation

Special Tools Needed

A 1/16 in. (1.5 mm) hex wrench or a Johnson Controls

®

T-4000-119 hex-head adjustment tool is required during

installation.

Accessories

To install the TE-6800 Series Temperature Sensor on a

wallbox requires accessory NS-WALLPLATE-0, ordered

separately.

Mounting

About this task:

Location Considerations

Locate the TE-6800 sensor:
• on a partitioning interior wall, and approximately

5 ft (1.5 m) above the floor in a location of average

temperature

• away from direct sunlight, radiant heat, outside walls,

behind doors, air discharge grills, stairwells, or outside

doors

• away from steam or water pipes, warm air stacks,

unconditioned areas (no heating and no cooling), or

sources of electrical interference

Note: 

The TE-6800 Series sensor is shock and

vibration resistant; however, be careful not to drop

the unit or mount it where it could be exposed to

excessive vibration.
The following ambient operating conditions apply:

• Temperature: 32 to 131°F (0 to 55°C)

• Humidity: 10 to 95% Relative Humidity (RH),

noncondensing; 86°F (30°C) maximum dew point

To mount the sensor to the wall:

1. Use a 1/16 in. (1.5 mm) hex wrench or Johnson

Controls T-4000-119 hex-head adjustment tool to

loosen the security screw on the top of the unit.

2. Insert a blade screwdriver into the slot next to the

security screw location, and then carefully pry the

top edge of the sensor assembly away from its

mounting base and remove.

Important: 

Do not remove the Printed Circuit

Board (PCB). Removing the PCB voids the

product warranty.

3. Pull out approximately 6 in. (152 mm) of cable from

the wall, and insert the cable through the hole in

the mounting base.

4. Align the mounting base on the wall, and use the

base as a template to mark the location of the two

mounting holes on the surface.

Note: 

Confirm that the mounting base is

positioned with the proper edge up. The

mounting base is positioned properly when the

security screw is located on the top edge of the

base.

*24104091G*

Part No. 24-10409-1   Rev. G

2021-04-02

TE-68xx-xN00S

Содержание TE-6800 Series

Страница 1: ...pervision ou d alarme ou des dispositifs de sécurité ou de limitation ayant une fonction d avertissement ou de protection en cas de défaillance ou de dysfonctionnement du sensor Installation Special Tools Needed A 1 16 in 1 5 mm hex wrench or a Johnson Controls T 4000 119 hex head adjustment tool is required during installation Accessories To install the TE 6800 Series Temperature Sensor on a wall...

Страница 2: ...ons in accordance with local national and regional regulations Figure 1 Modular Jack Pin Number Assignments Keep wires as short as possible to minimize sensor error Each 250 ft 76 m run of 18 AWG wire or 50 ft 15 m of 24 AWG wire creates 1F 0 56C error for a nickel sensor or 1 5F 0 83C error for a platinum sensor due to wire resistance To maintain less than 1F 0 56C error for nickel or 1 5F 0 83C ...

Страница 3: ...ity not reversed Misalignment can cause damage Refer to the controller documentation to determine the appropriate cable assembly Important Do not insert a 6 pin connector or anything other than an RJ 45 8 pin connector into the 8 pin jack on the back of the TE 6800 Temperature Sensor to prevent damaging the modular jack Table 2 Modular Jack Pin Designations Modular Jack Pin Number Signal Designati...

Страница 4: ...ctory set up down and up The controller determines the LED mode LED Mode NO PB LED and PB Disabled but Sensor Enabled Switch positions are all down LED is off and the PB does not function Figure 5 DIP Switch Positions Table 4 Controller Compatibility with LED Mode and PB Features Recognized by Controller Types of TE 6800 LED Mode Figure 5 Features Enabled on TE 6800 AHU UNT1100 VAV1xx or UNT1xx 1 ...

Страница 5: ... free from dust or obstruction If the TE 6800 temperature sensor fails to operate within its specifications replace the unit For a replacement sensor contact the nearest Johnson Controls representative Technical Specifications Table 5 TE 6800 Series Temperature Sensors technical specifications Specification Description Temperature Sensor 1000 ohm thin film nickel Temperature Coefficient Approximat...

Страница 6: ...om misapplication or misuse of its products Product warranty This product is covered by a limited warranty details of which can be found at www johnsoncontrols com buildingswarranty Software terms Use of the software that is in or constitutes this product or access to the cloud or hosted services applicable to this product if any is subject to applicable end user license open source software infor...

Отзывы: