Technical Specifications

ColorDisplay Series Thermostat Controllers

92

Touch Screen Series Thermostat Controllers

Power Requirements

20 - 30 VAC 50/60 Hz, 4.8 VA @ 24V nominal.

W1, W2, W3 = 0.2A max, 0.01A min, 3A inrush, 20 - 30 VAC
Y1, Y2, G = 0.4A max, 0.01A min, 3A inrush, 20 - 30 VAC

Thermistor, NTC 10K @ 25C

Thermistor, NTC 10K @ 25C

16 AWG (100 ft max) to 24 AWG (36 ft max)
35 to 99 deg F (2 to 36 degC)

35 to 65 deg F +/- 3 degF, greater than 65 to less than 80 degF +/- 2 degF,
80 to 99 degF +/_ 3 degF, greater than 99 to 104 degF +/- 5 degF

Adjustable 1 to 6 deg first stage, 0 - 10 deg 2nd & 3rd stages

35 to 104 degF (2 o 40 degC), 5 - 95% RH non-condensing, 86 degF
max dew point
-22 to 122 degF (-30 to 50 degC), 5-95% RH non-condensing, 86 degF
max dew point
UL/cUL listed, file E107041, NEC Class 2
4.0” H x 5.2” W x 1.1”D
0.34 kg

Output Rating

Local Temperature
Sensor Type

Remote Temperature
Sensor Type

Temperature Adjustment
Range

Accuracy

+/- 10% RH from 30-70% RH, 50-90F 

Humidity

Wire Size

Deadband

Operating

Storage

Ambient
Conditions

Compliance
Dimensions
Shipping Weight

This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules. These limits are

designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment. This equipment

generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful

interference to radio communications.  Operation of this equipment in a residential area may cause harmful interference, in which case the users

will be required to correct the interference at their own expense.

United States

Canada

North American Emissions Compliance

This Class (B) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numerique de la Classe (B) respecte toutes les exigences du Reglement sur le materiel brouilleur du Canada.

Содержание T9100

Страница 1: ...model T9100 Commercial High Resolution Touch Screen Digital Thermostat Owner s Manual and Installation Instructions Owner s Manual with Humidity Control Code No LIT 12012271 Issued September 27 2017...

Страница 2: ...tation inscription signifie simplement que le produit est conforme aux sp cifications techniques d Industry Canada This color touch screen has the ability to receive updates to its firmware Periodical...

Страница 3: ...lest temperature that the space should drop to before heating is turned on without regard to deadband Icon The word or symbol that appears on the thermostat display Mode The current operating conditio...

Страница 4: ...ylight Savings setup 10 Connect to Wi Fi 11 WiFi Setup 12 MAIN MENU BUTTONS View My Schedule 15 Edit My Schedule 15 Unoccupied Settings 16 FAN SETTINGS 17 Fan On Auto 18 Occupied Fan State 18 Preoccup...

Страница 5: ...27 Sound Options 27 HUMIDITY 28 Humidification Settings 29 Dehumidification Settings 29 HOLIDAYS 30 Holiday Schedule On Off 31 Edit Holidays 31 Preset Holidays 33 SECURITY 34 Auto Screenlock 35 Setpo...

Страница 6: ...e 45 Heat Pump Settings 59 Heat Pump Lockout Enabled Disabled 59 Heat Pump Lockout Outdoor Temp 59 Aux Heat Lockout Enabled Disabled 59 Aux Heat Lockout Temp 59 Aux Output Settings 60 Fan Off Delay 61...

Страница 7: ...ALLATION INSTRUCTIONS 73 Remove Replace the Old Thermostat 73 Wire Connections 74 Determining Your Existing Wiring and Equipment 75 Making 4 Wires Work When 5 Wires Are Required 77 Making 5 Wires Work...

Страница 8: ...tton Override Button OutdoorTemperature Cooler Button Warmer Button SD Card Slot Menu Button Mode Buttons If optional accessory is used or connected to Skyport Indoor Humidity Reading Connectivity Sym...

Страница 9: ...Connected to local access point w IP address without Skyport enabled Connected to local access point w IP address but not yet connected to Skyport Connected to Skyport Connectivity Symbol Table Dropdo...

Страница 10: ...the following 3 days This page displays sensor information Select Onboard to view room temperature and if equipped humidity sensors that are built into the thermostat Select Wireless to view all wirel...

Страница 11: ...4 Get To Know Your Thermostat Thermostat Info Equipment Configuration Thermostat Outputs These 3 screens are for informational purposes only Settings may not be changed from these screens...

Страница 12: ...uch screen Only use your finger tip to press the screen buttons Use a soft damp cloth to clean the screen CAUTION DO NOT USE ABRASIVE CLEANERS OR CLEANERSTHAT CONTAIN SOLVENTS DO NOT SPRAY ANYTHING DI...

Страница 13: ...cooling systems OFF heating and cooling systems are turned off AUTO CHANGEOVER MODE Pressing theWARMER or COOLER buttons in Auto mode will adjust both the heat and cool setpoints simultaneously To ad...

Страница 14: ...eriods pressing the OVERRIDE button will force the thermostat into an unoccupied period for the rest of the day During this forced unoccupied period the OVERRIDE button will operate as described above...

Страница 15: ...me OFF Start Schedule Starts On Day Month Stop Schedule Ends On Day Month 2nd Sun March 1st Sun November NOTE When the thermostat is connected to the Skyport the Time Date are automatically synchroniz...

Страница 16: ...e 12 00 AM hr hr min min Press and to set the current time Press when finished Press then Press Use AM PM ON Use AM PM OFF For 12 hour AM PM clock For 24 hour clock Choose Press when finished Set Time...

Страница 17: ...5 14 13 12 11 18 19 20 21 22 23 24 31 30 29 28 27 26 25 1 2 3 4 5 6 7 Press Press Daylight Savings Time OFF Daylight Savings Time ON Start Schedule Starts On Day Month Stop Schedule 2nd Sun March Ends...

Страница 18: ...onnect to from the list Enter the password for the Wi Fi Access Point and press NEXT Select automatic setup and press NEXT When finished a dialog box will appear confirming the successful connection t...

Страница 19: ...tic setup and press NEXT When finished a dialog box will appear confirming the successful connection to the local Wi Fi Access Point Select OK then the Wi Fi status page will appear Upon closing of th...

Страница 20: ...ned to a Skyport account you may join the thermostat to an account by doing the following Select MENU from the thermostat s home screen Scroll down Select Skyport Select Skyport Account and follow the...

Страница 21: ...14 Main Menu Buttons Schedule Schedule Unoccupied Settings View My Schedule Edit My Schedule Mode Off Auto Heat Auto Cool Heat Setpoint 55 Cool Setpoint 85...

Страница 22: ...ettings This may be repeated for each day View My Schedule Press and select day s to program Then press NEXT Edit My Schedule Continued Select individual day s or Select groups of day s Press and sele...

Страница 23: ...o desired settings TheTime Period May also be Enabled or Disabled Un check the enabled box forTime Periods you don t want to use Press DONE when finished Save Edit Mode Done Enable Disable Time Period...

Страница 24: ...17 Main Menu Buttons Fan Settings Who To Call For Service View Runtime Graphs Fan Auto Fan Purge OFF Fan Settings Occupied Fan State On Auto Auto Preoccupancy Purge Time 15 mins...

Страница 25: ...to run continuously or Auto for fan to run only with heating or cooling Press to turn on Preoccupancy Fan Purge This feature allows the fan to run for a preset amount of time before Occupied 1 begins...

Страница 26: ...raphs Screensaver OFF Screensaver Setup Screensaver Turn On Delay Change Image After Show Clock OFF Screensaver Type Screensaver Home Screen Info OFF View Runtime Graphs Screensaver Preview Slideshow...

Страница 27: ...ore returning to the Home Screen After the preview press anywhere on the screen to return to the sub menu Screensaver Screensaver Setup The Screensaver allows you to create custom slideshows Screensav...

Страница 28: ...Reset Air Filter Alert Reset UV Lamp Alert Alerts Set Edit Reminders Service Information UV Lamp Reminder OFF Max UV Lamp Runtime 500 hrs Set Max Filter Days 180 days 360 days Service Call OFF Days U...

Страница 29: ...rn reminders on or off Alerts appear on the bottom bar of the Home Screen Press to view and reset current alerts View and reset current service alerts here Dealer s Logo here Air Filter Reminder OFF S...

Страница 30: ...23 Main Menu Buttons Display Screen Cleaning Touch Calibration Active Brightness Night Dimmer Display Maintenance Auto Night Dimmer OFF Set Idle Brightness Set Dimmer Schedule Idle Brightness...

Страница 31: ...ay is active for 3 minutes after last touch it then goes idle You may dim the brightness of the touch screen at night The screen can be set to dim automatically at night Dimming the display can prolon...

Страница 32: ...brate the touch screen Screen Cleaning Mode disables the touch feature for 15 seconds so the screen may be cleaned without altering any settings Under normal circumstances the touch screen should not...

Страница 33: ...tons Preferences User Interface Themes Custom Wallpaper Heat Cool Indicator OFF Taskbar red white OFF Room Temp red blue OFF Mode Status red blue OFF Preferences Heat Cool Indicator Sound Options Beep...

Страница 34: ...ground will change to an evening scene At 7 AM it will return to a daytime scene You may choose your own background image by selecting a photo that you have uploaded from an SD memory card Sound Optio...

Страница 35: ...ty Humidification Settings Humidify setpoint 0 Dehumidification Settings Humidify with heat OFF Run fan w humidity demand OFF Dehumidity setpoint 99 0 Run A C to dehumidify OFF Maximum Overcool Reheat...

Страница 36: ...umidification 0 20 degrees F Dehumidify setpoint 99 Adjust Dehumidify setpoint 25 99 Run A C to dehumidify OFF When this step is ON the A C system will be used for Dehumidification When this step is O...

Страница 37: ...30 Main Menu Buttons Holidays Holiday Schedule OFF Edit Holidays Preset Holidays Holidays...

Страница 38: ...nued You may continue to select more holidays or you can press the Repeat button for recurring holidays Choose to repeat the holiday every week month or year Or press CANCEL to go back If you choose t...

Страница 39: ...n holiday If you choose to edit repeating holidays that affect this day press NEXT and the next screen will appear Press BACK to save your changes and return to the Holiday menu Deselecting Holidays M...

Страница 40: ...standard preset holidays to observe When the preset holidays are set to ON they will be observed every year on that date Editing Repeating Holidays continued Overriding Holiday Mode You may override...

Страница 41: ...Screenlock Setpoint Limits Security Auto Screenlock OFF Set Passcode Lock After Setpoint Limits OFF Minimum Cool Setpoint Maximum Heat Setpoint Allow fan mode changes NO Allow setpoint changes NO Allo...

Страница 42: ...ttings Set the time the screen will automatically lock after the last button press When the thermostat is locked the bottom bar of the display will show Allow fan mode changes NO Allow setpoint change...

Страница 43: ...36 Main Menu Buttons Information View Runtime Graphs Information Last 7 Days Cooling Last 7 Days Heating Who To Call For Service Delete Runtime Data Last 7 Days Override...

Страница 44: ...w Runtime Graphs Last 7 Days Cooling Last 7 Days Heating Track your system s runtime energy usage Press the information icon to learn more about each graph Press anywhere on the screen to return to th...

Страница 45: ...ly Cool Only Fahrenheit Celsius Heat Cool Stages Compressor Stages Aux Heat Stages English Spanish Espanol French Francais Heat Cool Stages Continued next page Import Settings from SD Card Export Sett...

Страница 46: ...eadband 2nd Stage Deadband 2nd Stage Timer 2nd Stage Turnoff Point 3rd Stage Deadband Deadband Setpoint 3rd Stage Deadband 3rd Stage Timer 3rd Stage Turnoff Point 4th Stage Deadband Deadband Setpoint...

Страница 47: ...sabled Continued next page Sensor Settings Control Source Thermostat Sensor Only Wired Sensor Only Average All Wireless Sensors Average Wired Thermostat Average Wireless Thermostat Average all availab...

Страница 48: ...Settings Dealer Information Dealer Name Contact Name Dealer Phone Dealer Email Dealer Website Factory Defaults Restart Thermostat Installation Settings Settings Test Outputs Upgrade Firmware Delete Cu...

Страница 49: ...are found in this menu Name appears here General Setup Units F Fahrenheit F Celsius C SD Card Import and export files to and from the thermostat See the ColorDisplay Desktop app instructions for furt...

Страница 50: ...art Recovery is active Language en Installation Settings Heat Cool Stages 1h1c Heat Cool Stages 1h1c Up to 2 Stages Cooling and 4 stages Heating Compressor Stages 1h1c Up to 2 compressors Aux Heat Sta...

Страница 51: ...set to 2 degrees the room temperature will need to drop to 66 degrees before the heat turns on 3rd Stage Deadband 4th Stage Deadband 1st Stage Deadband 2 1 6 deg F 2nd Stage Deadband 2nd Stage Deadba...

Страница 52: ...rder to reduce energy usage on demand This is known as Automated Demand Response or ADR for short You must register to participate in a utility sponsored program if offered by your local utility to ta...

Страница 53: ...e thermostat is configured to respond to the energy provider s signals It also sets operational parameters for the thermostat The left column of the ADR configuration page allows or prevents access by...

Страница 54: ...tpoints for ADR events are adjusted here The Static Settings are applied when the utility sends a signal to allow the occupant to enforce their own discrete temperature settings during an ADR event Th...

Страница 55: ...48 Main Menu Buttons Settings Selecting the Overview tab of the ADR page will cause a summary of ADR events to be displayed Office Configuration...

Страница 56: ...at the Skyport Cloud Services account From the thermostat Home Screen press the Menu button then select Settings From the above screen the Automated Demand Response button is pressed By selecting ADR...

Страница 57: ...action is taken when the price rises above the set threshold In the above example if the price threshold is exceeded the thermostat will invoke the Offset Setpoints configured for an ADR event until...

Страница 58: ...51 Main Menu Buttons Settings The user may limit the maximum Cooling Setpoint...

Страница 59: ...52 Main Menu Buttons Settings The user may limit the minimum Heating Setpoint...

Страница 60: ...53 Main Menu Buttons Settings 2 The user may adjust the ADR Cooling static Setpoint...

Страница 61: ...54 Main Menu Buttons Settings 2 The user may adjust the ADR Heating static Setpoint...

Страница 62: ...55 Main Menu Buttons Settings The user may adjust the ADR Cool offset During an ADR event the cooling setpoint will be adjusted by the amount of degrees configured in this step 2...

Страница 63: ...56 Main Menu Buttons Settings 2 The user may adjust the ADR Heat offset During an ADR event the heating setpoint will be adjusted by the amount of degrees configured in this step...

Страница 64: ...ending and hasn t started yet there will be a yellow leaf on the top bar This will be accompanied by associated text as shown below During an ADR event there will be a green leaf on the top bar This w...

Страница 65: ...ssed during an active ADR event then the user is presented with this opt out screen If a pricing triggered ADR event is enabled there will be a green leaf on the top bar along with the actual cost of...

Страница 66: ...ED Aux Heat Lockout ENABLED Turns on Aux Heat Lockout Aux Heat Lockout Temp 65 Aux Heat will not run above this temp 0 75 deg F GAS EL or HP dip switch must be set for HP and GAS or ELEC dip switch mu...

Страница 67: ...ehumidification Continued AUX output usage W3 IMPORTANT Aux Output Usage must be set for Hum or Dehum before any settings will take effect in the Humidity Main Menu AUX output polarity NO The AUX Outp...

Страница 68: ...tat the user may choose which sensor source is used to measure room temperature Wired Sensor Use remote The wired sensor may be used as follows Use as an Outdoor sensor Use as a Remote Sensor Use as a...

Страница 69: ...te Sensors 0 The thermostat and wired sensor may be calibrated 7 to 7 degrees F Thermostat Wired Sensor Humidity The installer or service technician can use this feature to test the functions without...

Страница 70: ...y Desktop APP that firmware is up to date or simply try reinserting the SD card Dealer s Logo here Delete Custom Images Press to delete the custom photos you uploaded to the thermostat Dealer Name Con...

Страница 71: ...64 Main Menu Buttons Wi Fi Wi Fi Setup Choose Network Password Entry Local API OFF API Protocol Wi Fi Status Wi Fi Enabled Local API Option HTTP HTTPS...

Страница 72: ...lows the wifi radio to be turned off or on Wi Fi Setup Choose your network from the list and enter the network password If your network does not appear in the list hit the refresh button Network Name...

Страница 73: ...een If a Secure API is required then select API Protocol This is the default with the local API OFF Upon pressing API Protocol the following screen will appear Then select HTTPS and press BACK Local A...

Страница 74: ...API OFF Basic Auth User Basic Auth User API Protocol http API Protocol http API Protocol https Basic Auth Password Q W E R T Y U I O 64 remaining A S D F G H J K L Shift BACK DONE Basic Auth User 123...

Страница 75: ...elow and press DONE to save Q W E R T Y U I O 64 remaining A S D F G H J K L Shift BACK DONE Basic Auth Password 123 SPACE Z X C V B N M Del P X Basic Auth Password The last step is to turn the Local...

Страница 76: ...ort Account Skyport Skyport Services ON Weather Updates ON Pressing this button will let you know if you are paired with a Skyport account If not then you may follow prompt and instructions to create...

Страница 77: ...peration the thermostat will turn on the fan and substitute auxiliary stages of heat for the first second stages of heat The heatpump will not be available for heating but can be used for cooling To e...

Страница 78: ...bsite in the background and updates the software and firmware the operating system for touch screen at no cost The ColorDisplay Desktop App allows you to use your computer to ColorDisplay Desktop App...

Страница 79: ...der on your computer Save to SD SD Card Slot At the thermostat Press then Settings SD Card Insert the SD card into the SD Card Slot Next press Press Then press Select the items to import into your the...

Страница 80: ...ews any brackets and instructions Turn off the power to the Heating Air Conditioning system at the main fuse panel Most residential systems have a separate breaker for disconnecting power to the furna...

Страница 81: ...agrams that follow Wire from the Install on the old thermostat Function new thermostat terminal marked connector marked G or F Fan G Y1 Y Cooling Y1 W1 W Heating W1 0 B Rh R M Vr A Power R C Common C...

Страница 82: ...he Making 4 Wires Work When 5 Wires Are Required section on page 72 If there are only 4 wires present that are connected to the existing thermostat there are at least 2 options available to connect th...

Страница 83: ...ll new thermostat wire from the HVAC equipment to the thermostat so that there are at least 5 wires available E If you have a heat pump with aux heat the JCI model will require 6 wires R 24Vac C 24Vac...

Страница 84: ...t the furnace locate the terminals that the wires are attached to 4 Remove the G wire from the terminal marked G 5 Place the G wire on terminal C 6 Place one end of the 3 long jumper on terminal G 7 P...

Страница 85: ...es usually at the furnace locate the terminals that the wires are attached to 4 Remove the G wire from the terminal marked G 5 Place the G wire on terminal C 6 Place one end of the 3 long jumper on te...

Страница 86: ...nections IMPORTANT This thermostat requires both R 24 VAC Return and C 24 VAC Common be connected to the backplate terminals To remove the thermostat backplate Using the Finger Pull Areas pull the fro...

Страница 87: ...red for HP this dip switch O or B must be set to control the appropriate reversing valve If O is chosen the W1 O B terminal will energize in cooling If B is chosen the W1 O B terminal will energize in...

Страница 88: ...Heat 5 Wire 1 Stage Cooling 1 Stage Heat 24VAC Power 24VAC Common 1st Stage Heat 1st Stage Cool Fan Residential Commercial 2 Stage Cooling with 3 stage Gas Heat 8 Wire 2 Stage Cooling 3 Stage Heat 24V...

Страница 89: ...or Heat Y2 2nd Stage Compressor Cool or Heat G Fan Residential Commercial Heat Pump with O ReversingValve 6 Wire 1 Stage Cooling 2 Stage Heat R 24VAC Power C 24VAC Common W1 O B Reversing Valve Y1 1s...

Страница 90: ...O B W2 W3 AUX 10K Thermistor Outdoor Sensor Use 18 22 gauge thermostat wire C R G Y1 Y2 W1 O B W2 W3 AUX 10K Thermistor Remote Sensor Use 18 22 gauge thermostat wire SENSOR SENSOR ACC RSEN Indoor Remo...

Страница 91: ...UM HUM Dehumidification Terminal on Equipment SENSOR SENSOR 84 Installation Instructions Sample Wiring Diagrams Use 16 24 gauge thermostat wire Use 16 24 gauge thermostat wire AUX Output Usage must be...

Страница 92: ...set point limit See Setpoint Limits page 33 SYMPTOM The heating does not attempt to turn on CAUSE The heating setpoint is set too low REMEDY Raise the heating setpoint or raise the heating setpoint l...

Страница 93: ...lsius 42 Choose Network 25 65 Cleaning 5 25 Clock Display 1 Setting 9 ColorDisplay Desktop App 71 Cool 1st stage deadband see Deadband 2nd stage deadband see Deadband Hours of runtime 37 Custom Wallpa...

Страница 94: ...nd stage deadband see Deadband electric strip heat see Aux Heat hours of runtime 37 3rd stage deadband see Deadband 4th stage deadband see Deadband timer 44 turnoff point 44 electric heat pump 59 mode...

Страница 95: ...at 29 Remote Sensor 61 83 Reset alert messages 22 thermostat settings see Factory Defaults runtime fan filter 18 UV light 22 Reversing Valve 80 Runtime resetting see Reset service filter 22 UV light 2...

Страница 96: ...59 cycles per hour 43 1st stage to 2nd stage 44 2nd stage to 3rd stage 44 3rd stage to 4th stage 44 Time schedule see Schedule Touch Calibration 25 62 Upgrade Firmware 63 User InterfaceThemes 27 UV Li...

Страница 97: ...90 Notes...

Страница 98: ...N WHATSOEVER ALL WORK UNDERTHETERMS OFTHIS WARRANTY SHALL BE PERFORMED DURING NORMAL WORKING HOURS ALL REPLACEMENT PARTS WHETHER NEW OR REMANUFACTURED ASSUME ASTHEIR WARRANTY PERIOD ONLYTHE REMAININGT...

Страница 99: ...Accuracy 10 RH from 30 70 RH 50 90F Humidity Wire Size Deadband Operating Storage Ambient Conditions Compliance Dimensions Shipping Weight This equipment has been tested and found to comply with the l...

Страница 100: ...Printed on recycled paper 12012271 Rev 3 09 17...

Отзывы: