background image

T-901/T-903/T-905 Instruction Bulletin    3

mechanism changes location of the set point screw
with respect to the control rod, thus changing the set
point.

Range of Remote Readjustment

The range of remote readjustment is the number of
degrees the set point can be changed as master
pressure changes from zero to maximum.  The
readjusting bellows moves a fixed amount for each
psi change in master pressure.  Since the movement
is transmitted through the readjustment spring, Fig. 3,
to the readjusting mechanism, the amount of channel
movement depends upon where the pin rests on the
spring.  The pin, also shown in Fig. 3, is rigidly
attached to the post.  Turning the dial and post
results in a varying channel movement from 0 to
100 percent of bellows movement.  The readjusting
dial is calibrated in degrees F of remote readjustment
for a full change in master pressure.  The possible
minimum and maximum ranges vary with the
maximum master pressure available.  The “Range of
Remote Readjustment” for various master pressure
ranges is shown in Table II.

Stops for Readjustment Mechanism

Sometimes it is necessary to readjust the submaster
thermostat over only a portion of the master pressure
range.  Special stops are available to make this
possible.  These stops, Fig. 4, may be arranged to
limit readjustment at the lower end only, or in both
directions, as required.

Adjustment

Setting Range of Remote Readjustment

The readjusting dial, Fig. 2, is used to adjust the
range of remote readjustment.  It is calibrated in
F degrees for a full change of master pressure.

The range of remote readjustment is obtained from
control system design information, for example:

MASTER PRESSURE

TEMPERATURE

0 psi

140

°

F

15 psi

65

°

F

The range of remote readjustment is:

140 - 65 = 75 F

°

.

Set the readjusting dial at 75 degrees.

Checking the Range of Remote Readjustment

1.

Set master pressure to either its extreme
maximum or extreme minimum value.

2.

Turn the lower adjusting screw until an
intermediate control line pressure is obtained,
e.g. 10 psi.  Make a written note of the lower dial
setting at this pressure.

Fig. 4:  T-901 Series Submaster Thermostat

Showing Adjustable Stops

Содержание T-901

Страница 1: ...n temperature increases A simple change of pivots converts the thermostats from one action to the other See Fig 1 and Table I Readjusting Action Depending on the pivots used an increasing master pressure either raises or lowers the set point When increasing master pressure raises set point the thermostat has direct readjustment When increasing master pressure lowers set point the thermostat has re...

Страница 2: ... port pressure This varying pressure is used to operate a relay of large capacity located in the thermostat Operation of Readjusting Mechanism Set point depends on the position of the control mechanism assembly with respect to the control port The assembly is so pivoted that turning the set point dial positions the assembly to establish set point The readjusting bellows contacts the free end of th...

Страница 3: ...emote Readjustment for various master pressure ranges is shown in Table II Stops for Readjustment Mechanism Sometimes it is necessary to readjust the submaster thermostat over only a portion of the master pressure range Special stops are available to make this possible These stops Fig 4 may be arranged to limit readjustment at the lower end only or in both directions as required Adjustment Setting...

Страница 4: ...nt adjusting screw until the dial setting corresponds to the set point determined by the master pressure Referring to the example this would be 140 F at 0 psi master pressure Adjusting the Stops The procedure for adjusting the stops is shown by another example MASTER PRESSURE TEMPERATURE 5 psi 60 F 10 psi 53 F This means that 5 psi change in master pressure must readjust the temperature 60 53 7 de...

Отзывы: