Installation, operation and maintenance manual - SVER-type economiser
0005708 en 2017.01

3/7

Design

Design

SVER is a closed flash economiser. In principle, the economiser consists of a shell with domed
ends. Nozzles are welded in the shell and end.

On delivery, the nozzles are blanked off with seal caps protecting against moisture and dirt during
transport and storage.

Option

Float valve

Level switch

1)

Danfoss HFI080

E Hauser FTL51

2)

Danfoss SV4

Danfoss AKS 38

N1

To economiser connection

N2

Liquid to evaporator

N3

Liquid from condenser

N6

Safety valve

N7

2) Level connection, SV4

N9

1) Level switch, FTL51

Application

The function of the economiser is to cool the liquid refrigerant (subcooling) from the condenser
before it is led to the evaporator. The flash gas side is connected to the economiser port of the
screw compressor, where the intermediate pressure gas from SVER is added to the suction gas.
The liquid will be subcooled to improve the efficiency of the refrigeration plant.

Product Description

By connecting the economiser to the economiser port of the compressor, gas of intermediate
pressure is led to the compressor resulting in increased COP. The refrigeration capacity of the
economiser appears as subcooling of the liquid from the high-pressure side to the low-pressure
side of the refrigeration plant.

N1

N6

N7

N3

N9

N2

Name plate

Sight glass