Johnson Controls SABROE SVER Скачать руководство пользователя страница 5

Installation, operation and maintenance manual - SVER-type economiser
0005708 en 2017.01

5/7

Shipping

Connection
nominal diameter

Connection
external diameter
OD

Standard
connection
thickness
DIN 2448

Connection possibilities

DN

inch

ANSI SCH40
x cut off

ANSI SCH80

y cut off

15

1/2

21.3

2.3

7

11

20

3/4

26.9

2.3

7

11

25

1

33.7

2.6

8

13

32

1 1/4

42.4

2.6

9

14

40

1 1/2

48.3

2.6

9

15

50

2

60.3

2.9

9

16

65

2 1/2

76.1

2.9

20

22

80

3

88.9

3.2

14

23

100

4

114.3

3.6

15

25

Shipping

The economiser must be blanked off and primed on delivery. The primer is not intended for out-
door storage. If the economiser is not put into immediate service, take precautions against corro-
sion or contamination.

Only lift the economiser when it is empty, and make sure it is not subjected to strokes or bumps
during transport. When lifting the economiser before it is built into the unit, always use straps
around the shell.

The weight is stated in the technical data.

A shipping description can be made when the economiser is built together with the unit.

Installation

The site and personal protection must be in accordance with EN 378-3 or national requirements.

Check the economiser immediately upon receipt for any damage occurred during transport. If the
economiser is damaged, it must not be installed and started.

When placing the economiser, make sure there is enough space for inspection, maintenance, es-
cape and emergency.

Foundations must be sufficiently robust, as their purpose is to provide permanent support without
settling and to absorb any normal vibrations from outside causes.

The SVER-type economiser is for horizontal installation.

Temporary seal cap.

OD

Cut off = Standard marking line

X Cut off = SCH 40

Y Cut off = SCH 80

Std. thickness

DIN 2448

Отзывы: