Johnson Controls SABROE ChillPAC Скачать руководство пользователя страница 5

Installation guide - ChillPAC and HeatPAC
006616 en 2021.10

5/7

Installation guide

Vibration dampers

ChillPACs and HeatPACs are designed for either 4 or 6 vibration dampers. For installation on solid con-
crete floor, anti-vibration machine feet are sufficient. Such machine feet are designed for minimum 70%
vertical isolation (100% capacity).

For installation on decks, special dampers are often required. Please consult a vibration expert or a
Johnson Controls Denmark representative for further information.

To ensure optimum effect of each individual anti-vibration machine foot, the load on the feet must result
in roughly the same deflection of all machine feet, see Fig. 3. Deflection of a machine foot can be ad-
justed by increasing or reducing the load compared to the other supports by turning the adjusting rod.

Fig. 3: Anti-vibration machine foot

Other damper types can be adjusted by using liner plates.

H

Содержание SABROE ChillPAC

Страница 1: ...ChillPAC and HeatPAC Chiller heat pump unit with reciprocating compressor Installation guide EN...

Страница 2: ...te that this installation guide only describes the main issues to consider dur ing installation Further installation guidance is available in the operating manual which must be read carefully before o...

Страница 3: ...is in good condition Also make sure that the lifting capacity of the crane and the loading capacity of chains straps lifting eyes and shackles as a minimum correspond to the total weight of the unit W...

Страница 4: ...erformed Fig 2 shows the minimum required spacing Fig 2 A For operation and opening of electric panel 1100 mm B For withdrawing suction filter and pistons 200 mm C For withdrawing pistons 200 mm D For...

Страница 5: ...n on decks special dampers are often required Please consult a vibration expert or a Johnson Controls Denmark representative for further information To ensure optimum effect of each individual anti vi...

Страница 6: ...d safety valves Never exceed the test pressure of the unit stated on the unit name plate All ChillPAC and HeatPAC units are pressure and performance tested from factory Electrical connection Connect p...

Страница 7: ...ome out of the top of the plates The plates should not be completely covered by liquid Note The liquid level must never be visible in the inspection glass Power supply Turn on power Control system Che...

Страница 8: ...Johnson Controls Denmark ApS Sabroe Factory Christian X s Vej 201 8270 H jbjerg Denmark Phone 45 87 36 70 00 www sabroe com Version 2...

Отзывы: