![Johnson Controls Penn System 450 Series Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/johnson-controls/penn-system-450-series/penn-system-450-series_technical-bulletin_2023540016.webp)
System 450™ Series Modular Control Systems with Standard Control Modules Technical Bulletin
16
System 450 Sensors and Transducers for Standard Control Modules
Table 2 shows the Sensor Types, output setup values, value ranges, and product
types for the temperature sensors, humidity sensors, and pressure transducers that
are compatible with the C450CxN-x standard control module models.
Table 2: System 450 Sensor Types, Setup Values, and Sensor/Transducer
Product Codes
Sensor
Type
Unit of Measurement
Value
(Condition/Units)
Effective
Sensing
Range
Range of
Usable
Values
1
1. Because of the way that the System 450 Differential Sensor (Sn-d) is set up and calculated with two identical sensors
(Sn-1 and Sn-2), the Range of Usable Values is twice as large as a single sensor. See Table 5 on page 26 for the
Range of Usable Values when an output references Sn-d.
Resolution
Increment
Value
Minimum
Proportional
or Control
Band
Sensor Product
Type Number
2
2. See
Repair and Ordering Information
on page 62 (Table 12 through Table 20) for additional ordering information for
System 450 compatible sensors and transducers.
F
F
(Temperature/degrees) -46 to 255
-40 to 250
1
1
A99B-xxx
C
C
(Temperature/degrees) -43 to 124
-40 to 121
0.5
0.5
A99B-xxx
rH
%
(Humidity/%RH)
1 to 100
10 to 95
1
2
HE-67Sx-xxxxx
HE-67Nx-xxxxx
HE-68Nx-0N00WS
P 0.5
INWC
(Pressure/in. W.C.)
0 to 0.5
0.025 to 0.5 0.005
0.025
DPT2650-0R5D-AB
P 2.5
INWC
(Pressure/in. W.C.)
0 to 2.5
0.1 to 2.5
0.02
0.1
DPT2650-2R5D-AB
P 5
INWC
(Pressure/in. W.C.)
0 to 5.0
0.25 to 5.0
0.05
0.25
DPT2650-005D-AB
P 8
bAR
(Pressure/bar)
-1 to 8
-1 to 8
0.05
0.1
P499Rxx-401C
P 10
INWC
(Pressure/in. W.C.)
0 to 10
0.5 to 10
0.05
0.2
DPT2650-10D-AB
P 15
bAR
(Pressure/bar)
-1 to 15
-1 to 15
0.1
0.2
P499Rxx-402C
P 30
bAR
(Pressure/bar)
0 to 30
0 to 30
0.1
0.4
P499Rxx-404C
P 50
bAR
(Pressure/bar)
0 to 50
0 to 50
0.2
0.4
P499Rxx-405C
P 100
PSI
(Pressure/psi)
0 to 100
0 to 100
0.5
1
P499Rxx-101C
P 110
3
3. See
on page 17 for information on setting up System 450 outputs that reference the P 110
Sensor Type.
Hg/PSI
(Pressure/Hg-psi)
-10 to 100
(20 inHg to
100 psi)
-10 to 100
0.5
1
P499Rxx-100C
P 200
PSI
(Pressure/psi)
0 to 200
0 to 200
1
1
P499Rxx-102C
P 500
PSI
(Pressure/psi)
0 to 500
90 to 500
1
5
P499Rxx-105C
P 750
PSI
(Pressure/psi)
0 to 750
150 to 750
2
6
P499Rxx-107C
HI
F
F
(Temperature/degrees) -50 to 340
-40 to 340
4
4. Many of the temperature sensors that can be set up as HI°F or HI°C Sensor Types are not designed for use across the
entire Range of Usable Values for HI°F and HI°C Sensor Types. Refer to the Technical Specifications for the sensor
you intend to use to determine the condition range that the sensor is specified to be mounted and operate in.
1
1
TE-631x, TE-6000-x
TE-68NT-0N00S
HI
C
C
(Temperature/degrees) -45.5 to
170
-40 to 170
0.5
0.5
TE-631x, TE-6000-x
TE-68NT-0N00S