P216 Series Condenser Fan Speed Controller Installation Instructions 

5

P499 Electronic Pressure Transducers

P216 Series controllers are designed to reference 
either one or two Johnson Controls P499 Electronic 
Pressure Transducers to monitor condenser pressure. 

On P216 Series controller applications that use two 
P499 transducers, the P216 Series controller always 
references the transducer that is sensing the higher 
pressure.

P499VCS-405C, 0-50 bar, 0-10 Vdc Output, 
Pressure Transducer

Only P499 models that have a 0-10 Vdc output signal 
can be used with the P216 control.

IMPORTANT:

Operate the P216 only in 

combination with one or two P499VCS-405C 
Pressure Transducers.

Wire Connection

Terminal

Red

V

Black

C

White

P

Содержание Penn P216 Series

Страница 1: ...ified ambient operating conditions See Technical Specification for ambient operating conditions IMPORTANT Use this P216 Series Condenser Fan Speed Controller only as an operating control Where failure or malfunction of the P216 Series Fan Speed Controller could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the ...

Страница 2: ... power supplies before making electrical connections More than one disconnect or isolation may be required to completely de energize equipment Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death IMPORTANT Do not connect supply power to the P216 Series controller before finishing wiring and checking all wiring connections Sho...

Страница 3: ...defines the input voltage level that causes the motor to run at full speed For example if the 2 10 Vdc Setpoint Range is selected and the Setpoint potentiometer is adjusted completely to then the motor will run at full speed when Vin 10 Vdc If the Setpoint potentiometer is adjusted midway between and then the motor will run at full speed when Vin 6 0 Vdc see P216 Slave Operation Example 1 2 3 4 ON...

Страница 4: ...es the motor to always run at minimum speed or greater P216 0 10 Vdc Slave Operation Example using 230 V Supply Output vs Input Voltage Input Pressure Bar Output to Motor VAC 16 Bar 20 Bar Setpoint 220 V Min Speed 46 V DIP Switch Block Setpoint 60 from Min speed 20 20 100 Proportional Band 1 2 3 4 ON 0 V Input Voltage Output to Motor VAC 6 0 Vdc Setpoint 220 V 230 V 0 2 46 V Setpoint at midscale M...

Страница 5: ...sure On P216 Series controller applications that use two P499 transducers the P216 Series controller always references the transducer that is sensing the higher pressure P499VCS 405C 0 50 bar 0 10 Vdc Output Pressure Transducer Only P499 models that have a 0 10 Vdc output signal can be used with the P216 control IMPORTANT Operate the P216 only in combination with one or two P499VCS 405C Pressure T...

Страница 6: ...he performance specifications are nominal and conform to acceptable industry standards For application at conditions beyond these specifications consult the local Johnson Controls office Johnson Controls Inc shall not be liable for damages resulting from misapplication or misuse of its products P216xxx x Condenser Fan Speed Controller Input Signal 0 10 Vdc Power Supply 208 240 Vac 50 60 Hz Control...

Отзывы: