P216 Series Condenser Fan Speed Controller Installation Instructions

1

 Refer to the 

QuickLIT website

 for the most up-to-date version of this document.

Applications  

 

 

Mounting

Location and Mounting Considerations

Observe these guidelines when locating and mounting 
a P216 Series Fan Speed Controller:

Ensure that the mounting surface and mounting 
hardware can support the control and wiring.

Mount the P216 Series controller upright on a 
vertical surface with the heat sink fins oriented 
vertically and the conduit/electrical holes facing 
down.

Figure 1: P216 Condenser Fan Speed Controller 

Mounting Dimensions, mm

Ensure that air can flow through the heat sink fins 
and provide 10 cm (4 in.) minimum clearance 
around the heat sink.

Mount the P216 Series controller in a location 
away from sources of excessive heat and within 
the specified ambient operating conditions. 
See 

Technical Specification

 for ambient operating 

conditions.

IMPORTANT:

Use this P216 Series Condenser 

Fan Speed Controller only as an operating control. 
Where failure or malfunction of the P216 Series Fan 
Speed Controller could lead to personal injury or 
property damage to the controlled equipment or 
other property, additional precautions must be 
designed into the control system. Incorporate and 
maintain other devices, such as supervisory or 
alarm systems or safety or limit controls, intended to 
warn of or protect against failure or malfunction of 
the P216 Series Fan Speed Controller.

!

CAUTION: Risk of Property Damage

Use only single-phase Permanent Split 
Capacitor (PSC) motors approved by the 
manufacturer for speed control 
application with the P216 Series 
controller. Failure to use a single-phase 
PSC motor may damage the motor and 
other property.

165

178

76

66

P216 Series Condenser Fan Speed Controller

Installation Instructions

P216xxx-x

Part No. 24-85895-18, Rev. D

Issued 27 August 2015

Содержание Penn P216 Series

Страница 1: ...ified ambient operating conditions See Technical Specification for ambient operating conditions IMPORTANT Use this P216 Series Condenser Fan Speed Controller only as an operating control Where failure or malfunction of the P216 Series Fan Speed Controller could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the ...

Страница 2: ... power supplies before making electrical connections More than one disconnect or isolation may be required to completely de energize equipment Contact with components carrying hazardous voltage can cause electric shock and may result in severe personal injury or death IMPORTANT Do not connect supply power to the P216 Series controller before finishing wiring and checking all wiring connections Sho...

Страница 3: ...defines the input voltage level that causes the motor to run at full speed For example if the 2 10 Vdc Setpoint Range is selected and the Setpoint potentiometer is adjusted completely to then the motor will run at full speed when Vin 10 Vdc If the Setpoint potentiometer is adjusted midway between and then the motor will run at full speed when Vin 6 0 Vdc see P216 Slave Operation Example 1 2 3 4 ON...

Страница 4: ...es the motor to always run at minimum speed or greater P216 0 10 Vdc Slave Operation Example using 230 V Supply Output vs Input Voltage Input Pressure Bar Output to Motor VAC 16 Bar 20 Bar Setpoint 220 V Min Speed 46 V DIP Switch Block Setpoint 60 from Min speed 20 20 100 Proportional Band 1 2 3 4 ON 0 V Input Voltage Output to Motor VAC 6 0 Vdc Setpoint 220 V 230 V 0 2 46 V Setpoint at midscale M...

Страница 5: ...sure On P216 Series controller applications that use two P499 transducers the P216 Series controller always references the transducer that is sensing the higher pressure P499VCS 405C 0 50 bar 0 10 Vdc Output Pressure Transducer Only P499 models that have a 0 10 Vdc output signal can be used with the P216 control IMPORTANT Operate the P216 only in combination with one or two P499VCS 405C Pressure T...

Страница 6: ...he performance specifications are nominal and conform to acceptable industry standards For application at conditions beyond these specifications consult the local Johnson Controls office Johnson Controls Inc shall not be liable for damages resulting from misapplication or misuse of its products P216xxx x Condenser Fan Speed Controller Input Signal 0 10 Vdc Power Supply 208 240 Vac 50 60 Hz Control...