1183746-UIM-D-1015
20
Johnson Controls Unitary Products
FIGURE 12:
Ladder Wiring Diagram - 2 to 3 Ton Models
LADDER WIRING DIAGRAM
COOLING UNIT WITH GAS HEAT
WITH RECIPROCATING COMPRESSOR
208/230-1-60
CAUTION - OPEN ALL DISCONNECTS
BEFORE SERVICING THIS UNIT
GROUND
L1
LUG
L2
NOTES:
R
RED
L1
T1
BLK
C COMPRES
S
R
RED
BLK/WHT
C
OD FAN
MOTOR
S
T2
L2
DUAL
CAPACITOR
BRN
H
C
F
RED
5
2
1
YEL
RED
START RELAY
START CAP
BLK
L
BLOWE
MOTOR
R
N
PUR
G
CONTROL
BOARD
RELAY
PUR
WHT
DRAFT
BLK
L1
IND
MOTOR
CONTROL BOARD SETTINGS:
COMBUSTION BLOWER POST PURGE: 60 SEC
INDOOR BLOWER HEAT ON DELAY: 30 SEC
INDOOR BLOWER COOL OFF DELAY: 60 SEC
INDOOR BLOWER HEAT OFF DELAY: FIELD SELECT
LINE VOLTAGE
FIELD INSTALLED POWER
LOW VOLTAGE
FIELD INSTALLED CONTROL
CAP
208V
230V
PRI
COM
BLK
PUR
XFMR
RED
BLU
24V SEC
40 VA
DSI Fault Codes
HI PRESS
Green Heartbeat
Amber Heartbeat
Rapid Green Flashes
Standby mode
Call for furnace heat active
Control in Factory Test mode
YEL
YEL
THERMOSTAT
CONTACTOR
C
BLU
C
COIL
3A
R
RED
R
FUSE
Operational Fault Codes
O
Y
Flashes
None
Slow Green Flashes
Slow Amber Flashes
Rapid Amber Flashes
4 Amber Flashes
Steady on Red
1 Red Flash
2 Red Flashes
3 Red Flashes
4 Red Flashes
5 Red Flashes
6 Red Flashes
7 Red Flashes
8 Red Flashes
9 Red Flashes
10 Red Flashes
11 Red Flashes
Fault Condition
Y
W
WHT
W
Power Off or open fuse
Normal Operation
Normal Operation with call for heat
Low flame sense current
No G from thermostat with Y call
Control Failure
Flame present with gas off
Check pressure switch wiring
Vent OR termination problem
Airflow problem
Flame Rollout
Repeated pressure switch cycles
Failed to light burners
Loss of flame during call for heat
Incorrect polarity OR Don't have neutral
Gas valve shorted "ON"
Check blower motor/wiring
CONTROL
G
GRN
G
BOARD
RED
RED/GRN
ROLLOUT
BLU
LIMIT
3
2
1
RED/BLK
YEL
6
5
4
GRN
9
8
7
YEL
GAS
PRESSURE
VALVE
ORG
FLAME
IGNITOR
SENSOR
ORG
3
WHT
W SPD
4
2
SPARK
TRANSFORMER
L1
IND
FS
5
1
RED
G SPD
BLOWER
MOTOR
Y SPD
C
2
3
ORG
BLU
24V COM
1
YEL
RED
1. ALL FIELD WIRING TO BE ACCOMPLISHED FOLLOWING CITY, LOCAL AND/OR
NATIONAL CODES IN EFFECT AT THE TIME OF INSTALLATION OF THE UNIT.
2. CAUTION : LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING
CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS
OPERATION. IF ANY OF THE WIRING, AS SUPPLIED WITH THE UNIT, MUST
BE REMOVED, IT MUST BE REPLACED WITH TYPE 105 C. 600 VOLT
WIRE OR EQUIVALENT CLEARLY RENUMBERED FOR IDENTIFICATION.
VERIFY PROPER OPERATION AFTER SERVICING.
3. FACTORY WIRED FOR 230 VOLT SUPPLY POWER. FOR 208 VOLT, MOVE
BLACK WIRES FROM THE 230 TO THE 208 VOLT TAP ON THE TRANSFORMER.
4. MOTORS ARE INHERENTLY PROTECTED.
5. SEE UNIT NAMEPLATE FOR MAXIMUM FUSE AND/OR CIRCUIT BREAKER SIZE
AND MINIMUM CIRCUIT AMPACITY.
6. SELECT INDOOR BLOWER SPEED TO REMAIN WITHIN THE TEMPERATURE
RISE RANGE ON THE NAMEPLATE IN HEATING AND TO OBTAIN APPROX.
400 CFM/TON IN COOLING.
7. BLOWER MOTOR SPEED CONNECTIONS SHOWN ARE TYPICAL,
BUT MAY VARY BY MODEL AND APPLICATION.
BLK/WHT
BRN
BRN/WHT