Technical Specifications     

NS Series Network Discharge Air Sensors

Supply Voltage

9.8 to 16.5 VDC; 15 VDC nominal

Current Consumption

12 mA maximum (non-transmitting) per discharge air sensor; 
60 mA maximum total current consumption per SA Bus

Terminations

Four color-coded wiring leads, stripped and tinned; 
Factory-installed at the discharge air sensor screw terminal block

Sensor Addressing

DIP switch set (204 to 211); factory set at 204

Wire Size

1.0 to 0.6 mm (18 to 22 AWG) diameter);
0.6 mm (22 AWG) diameter recommended; 305 cm (10 ft) wiring lead included with the 
unit

Communication Rate

Auto-detect: 9.6k, 19.2k, 38.4k, or 76.8k bps

Temperature Measurement 
Range

-10°C/14°F to 60°C/140°F

Temperature Sensor Type

Local 1k Ohm platinum resistance temperature detector (RTD); Class A per IEC 60751

Temperature 
Accuracy

NS Series 
Discharge Air 
Sensor

±0.6C°/±1.0F°

Temperature 
Element Only

0.2C° at 21°C (0.35F° at 70°F)

Ambient 
Conditions

Operating

-10 to 60°C (14 to 140°F); 10 to 90% RH, noncondensing; 29°C (85°F) maximum dew 
point

Storage

-40 to 70°C (-40 to 158°F); 5 to 95% RH, noncondensing

Compliance

BACnet® 
International

BACnet Testing Laboratories™ (BTL) 135-2004 Listed BACnet Smart Sensor (B-SS)

United States

UL Listed, File E107041, CCN PAZX,
Under UL 916, Energy Management Equipment

FCC Compliant to CFR 47, Part 15, Subpart B, Class A

Canada

UL Listed, File E107041, CCN PAZX7,
Under CAN/CSA C22.2 No. 205, Signal Equipment

Industry Canada, ICES-003

Europe

CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the 
essential requirements and other relevant provisions of the EMC Directive.

Australia and 
New Zealand

RCM Mark, Australia/NZ Emissions Compliant

Dimensions

Sensor 
Enclosure
(Height x 
Width x Depth)

76 x 76 x 51 mm (3 x 3 x 2 in.)

Temperature 
Probe

NS-DTN7043-x: 102 mm (4 in.) long

NS-DTN7083-x: 203 mm (8 in.) long

Shipping 
Weight

NS-DTN7043-x

1.15 lb (0.52 kg)

NS-DTN7083-x

1.17 lb (0.53 kg)

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these 
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damage resulting from misapplication or 
misuse of its products.

Содержание NS-DTN7043-2

Страница 1: ...ion of the discharge air sensors could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or protect against failure or malfunction of the discharge air sensors IMPORTANT Le ...

Страница 2: ...to obtain them 4 Reinstall the cover on the discharge air sensor and tighten the two cover holding screws to secure it in place 5 Wire the discharge air sensor to the SA Bus screw terminal block as illustrated in Figure 2 This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonab...

Страница 3: ...12011147 for more details Repair Information If the NS Series Network Discharge Air Sensor fails to operate within its specifications replace the unit For a replacement discharge air sensor contact the nearest Johnson Controls representative Risk of Electric Shock Disconnect the power supply before making electrical connections to avoid electric shock Risque de décharge électrique Débrancher l ali...

Страница 4: ... to 90 RH noncondensing 29 C 85 F maximum dew point Storage 40 to 70 C 40 to 158 F 5 to 95 RH noncondensing Compliance BACnet International BACnet Testing Laboratories BTL 135 2004 Listed BACnet Smart Sensor B SS United States UL Listed File E107041 CCN PAZX Under UL 916 Energy Management Equipment FCC Compliant to CFR 47 Part 15 Subpart B Class A Canada UL Listed File E107041 CCN PAZX7 Under CAN ...

Страница 5: ...s of their respective owners 2016 Johnson Controls Inc Building Efficiency 507 E Michigan Street Milwaukee WI 53202 European Single Point of Contact NA SA Single Point of Contact APAC Single Point of Contact JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 22 BLOCK D NEW DISTRICT WUXI JIA...