520413-BIM-A-0209
Johnson Controls Unitary Products
5
Physical Data Indoor Unit
Air Discharge Conversion
These units are shipped for Vertical Airflow operation as seen in
Figure 1 Positions 1 thru 4, but may be converted for Horizontal
Airflow operation illustrated in Figure 2 Positions 1 thru 4.
Conversion Example:
Convert Vertical Airflow Position 1 to Horizontal Airflow Position
1 as follows:
1.
Remove the front blower panel from the blower section and
set aside. This allows access to the clamps that hold the
blower section to the evaporator section.
2.
Remove the bolts and clamp angles that hold the coil
section and blower section together.
3.
Place the panel removed in Step 1 on top of the blower
section and screw together.
4.
Set the blower section aside.
5.
Remove the evaporator section rear panel and set aside.
6.
Rotate the blower section and mate it to the hole left when
the panel was removed in Step 5.
7.
Bolt and clamp the two sections together.
8.
Place the panel remove
1.
d in Step 5 on top of the evaporator section and screw
together.
NOTE:
1 inch blower duct flange shipped with air handler.
Table 2:
Physical Data Indoor Unit
Component
Models
NH-07
NH-10
NJ-10
NH-15
NJ-15
NH-20
NJ-20
Nominal Tonnage
7 1/2
10
10
15
15
20
20
DIMENSIONS (inches)
Length
56.0
56.0
56.0
74.5
74.5
98.5
98.5
Width
30.0
30.0
30.0
33.0
33.0
30.0
30.0
Height
65.0
65.0
65.0
75.0
75.0
65.0
65.0
WEIGHTS (lb)
Unit Shipping
405
512
512
681
681
874
874
Unit Operating With
Standard Motor and Drive
381
468
468
632
632
816
816
High Static Motor and Drive
385
492
492
661
661
854
854
INDOOR BLOWER (Forward Curve)
Diameter x Width
12 x 12
15 x 15
15 x 15
18 x 18
18 x 18
15 x 15
15 x 15
Quantity
1
1
1
1
1
2
2
INDOOR COIL
Face area (Sq. Ft.)
10.6
10.6
10.6
18.3
18.3
20.0
20.0
Rows
3
4
4
3
4
4
3
Fins per inch
15
15
15
15
15
15
15
Tube diameter
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Circuitry Type
Interfaced
Interfaced
Interfaced
Interfaced
Interfaced
Interfaced
Interfaced
Refrigerant Control
TXV
TXV
TXV
TXV
TXV
TXV
TXV
Operating Charge (lb)
4
6
6
10
10
10
10
SYSTEM DATA
No. Refrigeration Circuits
1
1
2
1
2
1
2
Suction Line OD (in.)
1 1/8
1 3/8
1 1/8
1 5/8
1 1/8
1 5/8
1 3/8
Liquid Line OD (in.)
5/8
7/8
5/8
7/8
5/8
7/8
7/8
FILTERS
Size and Quantity Per Model (In.)
16 x 25 x 2
4
4
4
---
---
8
8
20 x 24 x 2
---
---
---
6
6
---
---
Face area (Sq. Ft.)
11.1
11.1
11.1
20.0
20.0
22.2
22.2
Size and Quantity Per Model (In.)
16 x 25 x 4
4
4
4
---
---
8
8
18 x 24 x 4
---
---
---
6
6
---
---
Face area (Sq. Ft.)
11.1
11.1
11.1
18.0
18.0
22.2
22.2