Application

The Network Automation Engine (NAE) and Network
Integration Engine (NIE) are Web-enabled,
Ethernet-based, supervisory devices. Network Automation
Engines (NAEs) and Network Integration Engines (NIEs)
monitor and control networks of field-level building
automation devices, including HVAC equipment, lighting,
security, and fire safety equipment.

Figure 1

shows a

typical NAE55 model.

This document describes how to install an NAE55 or
NIE55, which are referred to collectively as NAE55 or
NAE unless specified otherwise.

North American Emissions
Compliance

United States

This equipment has been tested and found to comply with the
limits for a Class A digital device pursuant to Part 15 of the
FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when this equipment
is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and,
if not installed and used in accordance with the instruction
manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential
area may cause harmful interference, in which case the users
will be required to correct the interference at their own
expense.

Canada

This Class (A) digital apparatus meets all the requirements of
the Canadian Interference-Causing Equipment Regulations.

Cet appareil numérique de la Classe (A) respecte toutes les
exigences du Règlement sur le matériel brouilleur du Canada.

Installation

Follow these guidelines when installing an NAE55:

Transport the NAE55 in the original container to
minimize vibration and shock damage to the NAE55.

Verify that all the parts shipped with the NAE55. The
data protection battery and NAE55 ship together but
are packaged separately.

Do not drop the NAE55 or subject it to physical shock.

Do not open the NAE55 housing (except the data
protection battery compartment). The NAE55 has no
user-serviceable parts inside.

Parts Included

one NAE55

one data protection battery

one installation instructions sheet

one quick start guide

Materials and Special Tools Needed

four fasteners appropriate for the mounting surface
(M4 screws - Europe, #8 screws - North America)

two 36 cm (14 in.) or longer pieces of 35 mm DIN rail
(for DIN rail mount applications only)

1

NAE55/NIE55 Installation Instructions

Содержание NAE55 Series

Страница 1: ...stalled and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area may cause harmful interference in which case the users will be required to correct the interference at their own expense Canada This Class A digital apparatus meets all the requirements of the Canadian Interference Causing Equipment Reg...

Страница 2: ...cal Features and Mounting Orientation Note The features shown in Figure 1 may or may not be present depending on the NAE55 NIE55 model See Ordering Information for a list of features available on the NAE55 NIE55 models 2 NAE55 NIE55 Installation Instructions ...

Страница 3: ...m in Each NAE55 application is different and no general guidelines can be given about the heat dissipating devices that may be mounted in an enclosure with the NAE55 Monitor the NAE55 processor temperature for each application to determine the acceptable combinations of devices and proper mounting location for your specific application Important Do not add any devices to an enclosure with an NAE55...

Страница 4: ...E55 See the Installing the Data Protection Battery section In North America use a Class 2 24 VAC power supply with a 50 VA minimum output Outside North America use a 24 VAC Safety Extra Low Voltage SELV transformer at the appropriate rating The minimum input voltage for the NAE55 to operate properly is 20 VAC See the Technical Specifications section Use a dedicated power supply to the NAE55 only D...

Страница 5: ... guidelines when wiring the NAE55 Important Do not apply 24 VAC power to the NAE before completing and checking connections Short circuits or improperly connected wires may result in permanent damage to the equipment Important Do not apply 24 VAC power to the NAE55 before installing the data protection battery See the Installing the Data Protection Battery section in this document Important Use co...

Страница 6: ...the transformer to the removable power terminal block plug Figure 7 Power supply wire colors may be different on transformers not manufactured by Johnson Controls Follow the transformer manufacturer s instructions and the project installation drawings The 24 VAC power should be connected to all network devices so transformer phasing is uniform across the devices Powering network devices with unifo...

Страница 7: ...ble is recommended Stranded 0 6 mm 22 AWG shielded 4 wire two twisted pairs shielded cable is acceptable Note The and bus leads should be a twisted pair On applications using 4 wire two twisted pairs cable isolate and insulate unused conductor Refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 for more information Cable Type 1 Two FC devices with End of Line EOL switches in the ...

Страница 8: ...bus topology the maximum length stub cable is 3 m 10 ft and the stub lengths must be calculated into the overall segment length Table 5 Guidelines for LONWorks Network Free Topology Maximum Segment Length with FTT10 and or LPT10 11 Devices Maximum Node to Node Distance Cable Type 500 m 1 640 ft 500 m 1 640 ft Belden 85102 Cable 500 m 1 640 ft 500 m 1 640 ft Belden 8471 Cable 500 m 1 640 ft 400 m 1...

Страница 9: ...le you to set the NAE55 as a network terminated device on the bus To set an NAE55 as an FC Bus terminated device position the switch on the EOL switch block to the ON position Figure 8 Figure 8 FC Bus EOL Switch in the Factory Default ON Up Position Note The NAE55 is shipped with the EOL switches for both FC Buses in the initial factory position ON Figure 8 If the NAE55 is not a terminated device ...

Страница 10: ...epends on the size of the database and can take several minutes Figure 10 NAE55 with LED Designations System Re Boot Switch The System Re Boot switch Figure 1 forces a manual restart of the NAE55 processor All data changes made to the system since the last time the NAE55 saved data are lost on restart including alarm trend and audit trail data Note Press the System Re Boot switch only if the NAE55...

Страница 11: ... 1 second NAE55 software is in startup mode On 0 5 seconds Off 0 5 seconds NAE55 software is shutting down Off Steady Operating system is shutting down or software is not running On Steady Run Green On Steady 24 VAC power is present Off Steady Loss of 24 VAC power In the Off Steady condition the NAE55 can be running on battery power Also see the POWER LED On Steady 24 VAC Green On Steady Battery f...

Страница 12: ...nks or two BACnet MS TP RS 485 trunks or one N2 trunk and one BACnet MS TP trunk includes an internal modem Supports up to 255 devices on the LONWORKS trunk MS NAE5521 2 Contains ToggleTunnel utility for converting an NAE55 NIE55 to an NAE55 model with the N2 Tunneling features enabled Not for use with MS NAE5510 OU or MS NIE5510 OU MS MULTENGSW 6 1 Some models are also available in a Buy American...

Страница 13: ...andard USB connectors support an optional user supplied external modem Options One telephone port for internal modem up to 56 kbps 6 pin RJ 12 connector One LONWORKS port FTT10 78 Kbps pluggable keyed 3 position terminal block LONWORKS port available on NAE552x x models only Network and Serial Interfaces Plastic housing with internal metal shield Plastic material ABS polycarbonate Protection IP20 ...

Страница 14: ...3202 Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2013 Johnson Controls Inc www johnsoncontrols com Published in U S A 14 NAE55 NIE55 Installation Instructions ...

Отзывы: