16
TEC1100 Series Thermostat Technical Bulletin
Table 11: N2 Bus Objects
Point Name
TEC
Point
Type/
Addr.
N30
(CPN/
FAC)
Object
Type
BAS
Model
Point
Type
Override Range
TEC
1101
TEC
1102
TEC
1103
Room Temp
ADI-1
N2 AI
(AI)
d
CSAD ADI1
0 to 48°C
(28 to 124°F)
♦
♦
♦
Outdoor Temp
a
ADI-2
N2 AI
(AI)
d
CSAD ADI2
-48 to 48°C
(-54 to 124°F)
♦
♦
♦
Heating SP
a
ADI-3
N2 AO
(AO)
CSAD ADI3
1 to 47°C (29 to 99°F)
♦
♦
♦
Cooling SP
a
ADI-4
N2 AO
AO
CSAD ADI4
1 to 47°C (29 to 99°F)
♦
♦
♦
Setback Heating SP
a
ADI-5
N2 AO
(AO)
CSAD ADI5
1 to 47°C (29 to 99°F)
♦
♦
♦
Setback Cooling
SP
a
ADI-6
N2 AO
(AO)
CSAD ADI6
1 to 47°C (29 to 99°F)
♦
♦
♦
Minimum Heat SP
a
ADI-7
N2 AO
(AO)
CSAD ADI7
1 to 47°C (29 to 99°F)
♦
♦
♦
Maximum Heat SP
a
ADI-8
N2 AO
(AO)
CSAD ADI8
1 to 47°C (29 to 99°F)
♦
♦
♦
Minimum Cool SP
a
ADI-9
N2 AO
(AO)
CSAD ADI9
1 to 47°C (29 to 99°F)
♦
♦
♦
Maximum Cool SP
a
ADI-10
N2 AO
(AO)
CSAD
ADI10
1 to 47°C (29 to 99°F)
♦
♦
♦
Fan
a
BD-1
N2 BO
(BO)
CSBD BD1
0 = Off/Auto,
1 = On/MAN
♦
♦
♦
Mode
a
BD-2
N2
MSO
ef
(AO)
CSMS BD2
0 = Off 1= Cool,
2 = Heat, 3= Auto,
4 = E Ht (Aux Heat)
f
Mode
0-3
Mode
0-4
Mode
0-3
Occupancy
a
BD-3
N2 BO
(BO)
CSBD BD3
0 = Unoccupied,
1 = Occupied
♦
♦
♦
W1 State
BD-4
N2 BI
(BI)
CSBD BD4
0 = Off, 1 = On
Heat 1
E Heat
Heat 1
W2 State or Heat
Pump ‘O/B’
BD-5
N2 BI
(BI)
CSBD BD5
0 = Off, 1 = On
Heat
Pump
O/B
Heat 2
Continued on next page . . .
Notes:
a
Commandable
c
On the Metasys NCM system, map BD9 Temp Units Mode as a Binary Output (BO) object in a Control System
(CS) object with Autorestore and Local Control set.
d
AIs are commandable in the Companion/Facilitator system.
e
The Multiple Command Output (MCO) object is used to schedule multiple Multi-State Objects (MSOs).
f
When defining the N2 MSO object, select TEC Mode from the States Text Menu. Type 5 in the Number of
States field if you’re using the TEC1102 Heat Pump model, or type 4 for any other model. Mode 4, or
Emergency (Auxiliary) Heat (displayed as E ht), is only available on the TEC1102 Heat Pump model.
The Controller Point Type is the fixed point definition inside the controller. The CPN/FAC point is the software point
definition inside of the Companion software. The BAS Model Point type is the definition inside the model file. An
NCM CS object must be used to retrieve the data.
Control of the Analog Data (AD) objects is the last command received is the one that controls the thermostat. For
example, if the Metasys system sends a Night override, but the occupant selects Day mode, the TEC goes into Day
mode.