Notification Appliances—PS12/24ADA Series Signaling Strobe and Sounder 7
All models can be powered using Full-Wave Rectified (FWR), unfiltered
(unregulated) power supplies. However, if the power supply is
unregulated, the notification appliance must be compatibility listed for use
with the fire alarm system. If the power supplied is from a regulated
power supply, no compatibility listing is required. In addition, follow the
guidelines listed below:
●
Under no circumstances can PS24ADA series devices input voltage
exceed 33 VDC or be less than 16 VDC peak when using a regulated
power supply. When using an unregulated power supply, the range is
16-33 VRMS.
●
Under no circumstances can a PS12ADA or MASS12ADA series
device input voltage exceed 18.7 VDC or be less than 8.5 VDC for a
regulated power supply. When using an unregulated power supply,
the range is 8.5-18.7 VRMS.
Table 2: PS12/24ADA Series Operating Current from Regulated Supply
Model
Operating
Voltage
Supply
Voltage
Range
Average
Operating
Current
(mA)
Peak Current
(mA)
20/30V
Peak Current
(mA)
10.5/17V
PS24110ADA
PS24110ADAW
24 volt
20-30V
225
470/500
—
PS2475ADA
PS2475ADAW
24 volt
20-30V
185
385/400
—
PS2415ADA
PS2415ADAW
24 volt
20-30V
90
160/180
—
PS1215ADA
PS1215ADAW
12 volt
10.5-1V
182
—
360/380
PS241575ADA
PS241575ADAW
24 volt
20-30V
108
210/220
—
PS121575ADA
PS121575ADAW
12 volt
10.5-17V
240
—
510/560
Note: The strobes are available in red and white. The W suffix indicates white.
Power