Intelligent Products—DH500 Series Intelligent Air Duct Smoke Detector 23
The RTS451 remote test station facilitates testing the alarm capability of
the duct detector as indicated in the RTS451 Remote Test Station Technical
Bulletin located in the Intelligent Products section of this manual. The
DH500 series duct detector cannot be reset by the RTS451. It must be
reset at the system control panel.
To install the RTS451 test coil:
1.
Connect the device (Figure 9).
2.
Place the coil in the detector housing with the arrow facing up and
pointing toward the detector (Figure 9).
3.
Attach the coil leads to the housing terminals as shown.
Polarity is not important.
4.
Firmly screw the test coil mounting bracket in place over the test coil.
5.
Use wire that is less than 25 ohms when connecting the remote test
station to the duct detector.
Figure 9: RTS451 Test Coil Installation
RTS451 Remote
Test Station
Detector
Head
dhfig14
Test Coil