Johnson Controls M9102-AGA-2S Series Скачать руководство пользователя страница 3

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.
Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2013 Johnson Controls, Inc.

www.johnsoncontrols.com

3

M9102-AGA-2S, -3S and M9104-xGA-2S, -3S Series Electric Non-Spring Return 
Actuators (Continued)

   

Technical Specifications 

M9102-AGA-2S, -3S and M9104-xGA-2S, -3S Series Electric Non-Spring Return Actuators 

Power Requirements

M910x-AGA-xS

AC 24 V 

25%/-20% at 50/60 Hz, 2.1 VA Supply, Class 2, Safety Extra-Low Voltage (SELV)

M9104-IGA-xS

AC 24 V 

25%/-20% at 50/60 Hz, 3.0 VA Supply, Class 2, SELV

M9104-GGA-xS

AC 24 V 

25%/-20% at 50/60 Hz, 3.6 VA Supply, Class 2, SELV

Control Type

M910x-AGA-xS

Floating Control without Timeout

M9104-IGA-xS

Floating or On/Off Control with Timeout

M9104-GGA-xS

Proportional Control

Input Signal

M910x-AGA-xS

AC 24 V 

25%/-20% at 50/60 Hz, Class 2, SELV without Timeout

M9104-IGA-xS

AC 24 V 

25%/-20% at 50/60 Hz, Class 2, SELV with Timeout

M9104-GGA-xS

0(2) to 10 VDC or 0(4) to 20 mA with field-furnished 500 ohm resistor

Feedback Signal

M9104-GGA-2S

0 to 10 VDC or 2 to 10 VDC for 90° (10 VDC at 1 mA) 
Corresponds to input signal span selection

Motor Input Impedance

200 ohms Nominal

Running Torque

M9102 Series

18 lb·in (2 N·m)

M9104 Series

35 lb·in (4 N·m)

Travel Time

M9102 Series

30 Seconds at 60 Hz (36 Seconds at 50 Hz) for 90°

of Rotation

M9104 Series

60 Seconds at 60 Hz (72 Seconds at 50 Hz) for 90° of Rotation

Rotation Range

93° 



3°, CW or CCW

Cycles

100,000 Full Stroke Cycles;
2,500,000 Repositions at Rated Running Torque

Audible Noise Rating

35 dBA Nominal at 39-13/32 in. (1 m)

Electrical Connections

M9102-AGA-2S
M9104-xGA-2S

48 in. (1.2 m) UL 444 Type CMP Plenum Rated Cable with 19 AWG (0.75 mm

2

) conductors and 

1/4 in. (6 mm) ferrule ends

M9102-AGA-3S,
M9104-xGA-3S

M3 Screw Terminals

Mechanical Connections

Up to 1/2 in. (13 mm) Diameter Round Damper Shaft or 3/8 in. (10 mm) Square Damper Shaft

Enclosure

M9102-AGA-2S,
M9104-xGA-2S

NEMA 2, IP42

M9102-AGA-3S,
M9104-xGA-3S

NEMA 1, IP40

Ambient Conditions

Operating

-4 to 140°F (-20 to 60°C); 90% RH Maximum, noncondensing

Storage

-20 to 150°F (-29 to 66°C); 90% RH Maximum, noncondensing

Compliance

United States

UL Listed, File E27734, CCN XAPX (United States) and XAPX7 (Canada)

Actuator Housing is Plenum Rated per CSA C22.2 No. 236/UL 1995, Heating and Cooling Equipment

Europe

CE Mark - Johnson Controls, Inc., declares that this product is in compliance with the essential requirements 
and other relevant provisions of the EMC Directive 2004/108/EC.

Australia and New 
Zealand

C-Tick Mark Australia/NZ Emissions Compliant

Shipping Weight

1.0 lb (0.5 kg)