LX Series Unit Ventilator Controller User's Guide
79
Similarly, a variable speed fan requires time to speed up or slow down so that its
speed matches the output. The alarm delay must be long enough to allow the fan to
reach its commanded speed; otherwise, false alarms generate.
General Settings Configuration
Figure 36 shows the General Settings Configuration screen.
Table 20: General Settings Parameters
Field
Description
Fresh Air Minimum
Input
Select either Damper Position or Air Volume. If you are not using the
fresh air damper, the minimum input area is not applicable and
remains in gray text.
Damper Position
Select the Damper Position and enter a percentage value in the box
below Minimum Input. The percentage value sets the minimum fresh
air intake. The damper opens as least as much as that value during
occupied mode. Fully open is 100% and fully closed is 0%.
Air Volume
Select Air Volume and enter a percentage to for a minimum amount
of fresh air. The fresh air minimum is calculated using return air
temperature, mixed air temperature, and outside air temperature.
Damper Drive Time
Enter the time required for the damper drive to move the damper
from fully open to fully closed.
Figure 36: General Settings Configuration Screen