SECTION 6 – USER INTERFACE CONTROL CENTER
FORM 145.05-NOM7
ISSUE DATE: 10/31/2019
6
OPTIONS
The items under the OPTIONS key involve the set up
of the unit based on the ordered options. Many of these
parameters are preset at the factory based on the unit
configuration and should not be changed. To view the
values press the OPTIONS key. After pressing the OP-
TIONS key use the ◄ key or the ► key to select the
menu subsection: Unit, Cooling, Compressor Systems,
Supply System, Heating, Economizer, Ventilation, or
Condenser, that contains the parameter you would like
to view. The parameters contained under each of these
menu subsections and their password level is contained
in
▲
and
▼
key to navigate to the
parameter within the subsection you want to view.
If you need to change any of the “Options” parameters
press the CHECK key. The Enter Password screen ap-
pears. All “Program” parameters require the use of a
password before they can be changed.
on page 168 for information on how to enter a pass-
word into the User Interface.
If a Level 1 password is
entered, only Level 1 “Options” parameters are avail-
able for change. Entering a Level 2 password make
all “Options” parameters available.
Once a password is entered it remains active for 15
minutes.
TABLE 38 -
OPTIONS
USER
INTERFACE
KEY
SUBSECTION
DISPLAYED TEXT
RANGE
DEFAULT
VALUE
UNIT
SETTING
Options
Unit Data
Unit Type
Constant Volume / Variable Air
Volume / FlexSys
Variable Air
Volume
Options
Unit Data
Unit Size
12-105 Ton
25
Options
Unit Data
Freezestat
Not Installed/Installed
Not Installed
Options
Unit Data
Refrigerant Type
R22 / R409c / R410a
R410a
Options
Unit Data
Comp Staging
Sequencing
Simple / Mixed
Simple
Options
Supply Fan
High Duct Static SW
Not Installed / Installed
Not Installed
Options
Supply Fan
Sf Vfd Bypass
Not Installed / Installed
Not Installed
Options
Supply Fan
DP Sensor #2
Not Installed / Installed
Not Installed
Options
Supply Fan
Duct Pressure Signal 0-5 VDC/1-5 VDC
0-5 VDC
Options
Supply Fan
Duct Pressure
Transducer Span
.25/1.25/2.50/5.00 "W.C.
5.00 "W.C.
Options
Supply Fan
Supply Fan
Piezometer
Not Installed / Installed
Not Installed
Options
Heating
Heating System Type None / Electric / Hot Water Steam
None
Options
Heating
Elec Heat Capacity
17.5 Kw / 35 Kw / 52.5 Kw / 70 Kw
17 Kw
Options
Economizer
Econo Installed
None / Dry Bulb / Single Enthalpy /
Dual Enthalpy / Waterside
Waterside
Options
Ventilation
Damper Hardware
None / 2 Position / Standard
None
Options
Condenser
Cond Valves Installed None / Cond Only / Cond W/ Bypass
None
Options
Condenser
Water Flow Switch
Not Installed / Installed
Not Installed
Options
Condenser
Condenser Type
Water Cooled / Air Cooled
Water Cooled