FXVMA Installation Instructions

2

Installation

Observe these guidelines when installing the FXVMA:

Transport the FXVMA in its original container to 
minimize vibration and shock damage.

Do not drop the FXVMA or subject it to physical 
shock.

Accessories

Use Table 1 to order accessories. 

Mounting

To mount the FXVMA:

1.

Place the FXVMA in the proper mounting position 
on the damper shaft so that the wiring connections 
are easily accessible.

2.

Make sure the FXVMA base is parallel to the VAV 
box (perpendicular to the damper shaft). If needed, 
use a spacer to offset tipping of the FXVMA caused 
by the shaft bushings.

3.

Secure the self-piercing No.10 screw through the 
FXVMA mounting slot with a power screwdriver 
and 100 mm (4 in.) extension socket; otherwise, 
use a punch to mark the position of the shoulder 
washer and then drill a hole into the VAV box using 
a 3.5 mm (9/64 in.) drill bit.

4.

Insert and tighten the mounting screw against the 
washer.

5.

Locate the damper position using the typical 
marking on the end of the damper shaft (Figure 2).

6.

Note the direction, Clockwise (CW) or 
Counterclockwise (CCW), required to close the 
damper. 

7.

Grasp the damper shaft firmly with pliers and either 
manually close the damper for 90° boxes or 
manually open for 45° or 60° boxes.

8.

Push down and hold the Manual Override button, 
and turn the FXVMA coupler until it contacts the 
mechanical end-stop at either the fully closed (90° 
boxes) or fully open (45° and 60° boxes) position.

Table 1:  FXVMA Accessories Ordering 

Information

Product 
Code 
Number

Description

Y64T15-0

Transformer: 120/208/240 VAC Primary 
to 24 VAC Secondary, 92 VA, Foot 
Mount, 30 in. Primary Leads and 30 in. 
Secondary Leads, Class 2

Y65A13-0

Transformer: 120 VAC Primary to 
24 VAC Secondary, 40 VA, Foot Mount, 
8 in. Primary Leads and 30 in. 
Secondary Leads, Class 2

Y65T42-0

Transformer: 120/208/240 VAC Primary 
to 24 VAC Secondary, 40 VA, Hub 
Mount, 8 in. Primary Leads and 
Secondary Screw Terminals, Class 2

Y65T31-0

Transformer: 120/208/240 VAC Primary 
to 24 VAC Secondary, 40 VA, Hub 
Mount, 8 in. Primary Leads and 
Secondary Screw Terminals, Class 2

AP-TBK1002-0

2-position screw terminal that plugs into 
spade lugs 

AP-TBK1003-0

3-position screw terminal that plugs into 
spade lugs

IMPORTANT:

When the air supply to the VAV box 

is below 10°C (50°F), make sure that any 
condensation on the VAV box (particularly on the 
damper shaft) does not enter the electronics. Mount 
the FXVMA vertically above the damper shaft to 
allow any shaft condensation to fall away from the 
FXVMA. Additional measures may be required in 
some installations.

IMPORTANT:

Do not overtighten the screws, or the 

threads may strip. If you plan to mount to the VAV 
box, make sure the screws do not interfere with 
damper blade movement.

Figure 2: Typical Damper End Shaft Icons

FI

G

:d_

sh

af

t

Содержание LP-FXVMA Series

Страница 1: ...edded communication capability that enables the FXVMA to integrate into an N2 or BACnet Master Slave Token Passing MS TP depending on model network of a building automation system North American Emissions Compliance United States Canada Figure 1 FXVMA VAV Box Controller This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Ru...

Страница 2: ...al Override button and turn the FXVMA coupler until it contacts the mechanical end stop at either the fully closed 90 boxes or fully open 45 and 60 boxes position Table 1 FXVMA Accessories Ordering Information Product Code Number Description Y64T15 0 Transformer 120 208 240 VAC Primary to 24 VAC Secondary 92 VA Foot Mount 30 in Primary Leads and 30 in Secondary Leads Class 2 Y65A13 0 Transformer 1...

Страница 3: ... assignments for the inputs and outputs vary according to the control application configuration Obtain the actual I O channel assignments from FX Builder Express or FX Builder The wiring connections for the inputs and outputs vary depending on the FXVMA application Universal Input Wiring Details The FXVMA features one Universal Input UI that you can configure to accept either a passive sensor an a...

Страница 4: ... SENSOR Figure 5 Active Sensor Connection Powered by the FXVMA Ground Common Power Output ACTIVE SENSOR 15 IN ICOM UNIVERSAL FXVMA FIG ActiveSensorVMA Figure 6 Dry Contact Maintained Switch Connection MAINTAINED SWITCH DRY CONTACT N O or N C as required 15 IN ICOM UNIVERSAL FXVMA FIG dry contact Table 3 FXVMA Binary Output Description Terminal Label Function and Electrical Ratings Specifications O...

Страница 5: ...ired 10 mA maximum output current or Binary Output 24 VAC triac When the binary output is activated OUTX is connected to OCOMX 30 VAC maximum output voltage 0 5 A maximum output current 40 mA minimum load current OCOMX Analog Output common Provides the signal common for Configurable Output terminals when the CO is configured for analog output operation Isolated from all other terminal commons or B...

Страница 6: ... Bus Technical Bulletin LIT 12011034 Use Figure 14 to make the BACnet MS TP bus connections to the FXVMA BACnet MS TP devices including the FXVMA are networked together in a daisy chain configuration For runs up to 1 220 m 4 000 ft we recommend you use stranded 22 AWG twisted 3 conductor wire Avoid using solid wire when possible as it is prone to break when pulled Power Wiring Details The FXVMA re...

Страница 7: ... BACnet MS TP bus otherwise leave it at its default Off position See Figure 17 Troubleshooting Use Table 5 to troubleshoot the FXVMA Repair Information If the FXVMA Variable Air Volume Box Controller fails to operate within its specifications refer to the FXVMA VAV Box Controller Technical Bulletin LIT 12011249 for a list of repair parts available Figure 17 EOL Switch 1 O N 1 O N ON Position OFF P...

Страница 8: ...box damper shaft using single set screw and to duct with single mounting screw Actuator Rating 4 N m 35 lb in minimum Minimum shaft length 44 mm 1 3 4 in Dimensions Width 182 mm 7 2 in Length 182 mm 7 2 in Height 64 mm 2 5 in Center of Output Hub to Center of Anti Rotation Slot 160 mm 6 3 in Weight 0 86 kg 1 9 lb Compliance United States UL Listed File E107041 CCN PAZX UL 916 Energy Management Equ...

Отзывы: