LN Application Specific, Remote I/O, and Free Programmable Controllers Installation Instructions
9
Wiring Discrete Outputs
If a 12 VDC relay is being controlled, connect it to a universal output according to Figure 14.
Wiring Voltage Inputs
Connect the 0 to 10 VDC output according to Figure 15.
If an analog actuator is being controlled, connect the 0 to 10 VDC output, along with an external 24 VAC power
source, to the analog actuator according to Figure 16.
Two network terminators are required for the bus topology network configuration. Place one network terminator at
each end of the bus topology channel.
One network terminator is required for the free topology network configuration. You can put the network terminator
anywhere on the channel.
Communications Wiring
The recommended cable type for L
ON
W
ORKS
® communications is 22 AWG (0.65 mm), twisted pair,
UNSHIELDED
wire. The L
ON
W
ORKS
communication wire is polarity insensitive and can be laid out in a bus, star, or free topology.
For loop topology, take special care to maintain the polarity when connecting the L
ON
W
ORKS
network to avoid a
short circuit.
Note:
We recommend you use the bus topology network configuration for all L
ON
W
ORKS
communication wiring.
This configuration allows you to troubleshoot the network easily.
Figure 14: Discrete 0 to 12 VDC
Figure 15: Voltage 0 to 10 VDC
Universal Output
Figure 16: Voltage 0 to 10 VDC
Universal Output – Analog Actuator