5370597-JIM-D-1019
Johnson Controls Ducted Systems
7
Figure 4: Component Location (JA3ZT Shown)
Location
Use the following guidelines to select a suitable location for
these units:
1.
Unit is designed for
outdoor installation only
.
2.
Condenser coils must have an unlimited supply of air.
Where a choice of location is possible, position the unit on
either north or east side of building.
3.
Suitable for mounting on roof curb.
4.
For ground level installation, use a level concrete slab with
a minimum thickness of 4 inches. The length and width
should be at least 6 inches greater than the unit base rails.
Do not tie slab to the building foundation.
5.
Roof structures must be able to support the weight of the
unit and its options/accessories. Unit must be installed on a
solid, level roof curb or appropriate angle iron frame.
6.
Maintain level tolerance to 1/2” across the entire width and
length of unit.
Intelligent control board
for safe and efficient
operation
w/screw connectors for T-stat
wiring and Network
Connections
Disconnect location
(optional disconnect switch)
Filter access
(2" or 4”
filter options)
Filter drier (solid core)
Slide out motor and
blower assembly for
easy adjustment
and service
Base rails w/
forklift slots
(three sides)
and lifting
holes
Toolless door
latch
Side entry power
and control wiring
knockouts
Premium Efficiency
Belt-drive blower motor
Power ventor
motor
20-gauge aluminized
steel tubular heat
exchanger for long life
(stainless steel option)
Two stage gas heating to
maintain warm, comfortable
temperature
Slide-out drain pan
with
" NPT
connection
Compressor access (High-
Efficiency 2-Stage compressor)
Second model nameplate
inside hinged access
panel
Roof curbs in eight-and
fourteen-inch heights.
Roof curbs for transitioning
from Series 5 footprint
to the
-$$
ZT footprint
are available
(field-installed accessory)
Micro-Channel Aluminum
Tube/Aluminum Fin
Condenser
High Efficiency
SineWave Fin Evaporator Coil
6
PDUW
(
TXLSPHQW
w/IntelliSpeed™ Supply Fan Controls
ECM Outdoor Fan motor
VFD
Table 1: JA3 thru JA5ZT Unit Limitations
Size
(Tons)
Model
Unit Voltage
Unit Limitations
Applied Voltage
Outdoor DB Temp
Min
Max
Max (°F)
JA3
(3.0)
ZT
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
JA4
(4.0)
ZT
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
JA5
(5.0)
ZT
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125