5370597-JIM-D-1019
40
Johnson Controls Ducted Systems
Table 18: Airflow Performance - Bottom Duct Application
JA3ZT (3.0 Ton) Bottom Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
FS
4
Standard 1.5 Hp & Drive
High Static 1.5 Hp & Drive
FS
4
900
469
0.26
580
0.34
682
0.43
775
0.52
860
0.60
936
0.69
1004
0.78
1063
0.87
1113
0.96
1155
1.05
1000
486
0.27
597
0.36
699
0.45
793
0.54
879
0.63
956
0.72
1024
0.81
1083
0.91
1135
1.00
1177
1.10
1100
504
0.29
613
0.38
714
0.47
807
0.56
892
0.66
969
0.75
1037
0.84
1098
0.93
1151
1.02
1196
1.12
1200
526
0.31
635
0.40
736
0.50
828
0.59
911
0.69
986
0.78
1053
0.87
1112
0.97
1162
1.06
1203
1.15
1300
552
0.33
657
0.42
755
0.52
844
0.62
926
0.71
1001
0.81
1067
0.90
1126
0.99
1177
1.08
1220
1.17
1400
577
0.35
679
0.46
774
0.56
862
0.65
943
0.75
1017
0.84
1084
0.93
1144
1.02
1198
1.11
-
-
1500
610
0.39
707
0.49
797
0.60
882
0.70
959
0.79
1031
0.89
1095
0.98
1154
1.07
1206
1.15
-
-
JA4ZT (4.0 Ton) Bottom Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Standard 1.5 Hp & Drive
High Static 1.5 Hp & Drive
FS
4
1200
-
-
633
0.38
728
0.47
816
0.56
898
0.65
973
0.75
1042
0.85
1104
0.95
1159
1.05
1208
1.16
1300
-
-
656
0.41
748
0.50
834
0.59
914
0.68
988
0.77
1056
0.87
1118
0.96
1174
1.07
1224
1.17
1400
586
0.37
680
0.46
769
0.55
852
0.65
930
0.74
1003
0.84
1070
0.93
1132
1.02
1189
1.12
-
-
1500
612
0.40
703
0.50
790
0.59
871
0.69
948
0.78
1019
0.88
1086
0.97
1148
1.07
1205
1.17
-
-
1600
643
0.44
731
0.53
814
0.63
893
0.73
967
0.82
1037
0.92
1103
1.01
1164
1.11
1221
1.21
-
-
1700
671
0.47
756
0.57
837
0.67
914
0.77
987
0.87
1056
0.97
1121
1.07
1183
1.17
-
-
-
-
1800
699
0.53
781
0.63
860
0.73
935
0.84
1006
0.94
1074
1.04
1139
1.14
1199
1.24
-
-
-
-
1900
726
0.58
805
0.69
881
0.80
954
0.90
1024
1.01
1092
1.12
1157
1.22
1218
1.33
-
-
-
-
2000
755
0.64
831
0.75
905
0.86
977
0.97
1046
1.08
1113
1.19
1178
1.3
-
-
-
-
-
-
JA5ZT (5.0 Ton) Bottom Duct
Air Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
FS
4
Standard 1.5 Hp & Drive
High Static 2.0 Hp & Drive
1500
616
0.39
696
0.50
771
0.60
841
0.71
907
0.81
968
0.91
1024
1.02
1075
1.12
1122
1.23
1164
1.33
1600
643
0.43
719
0.54
791
0.64
858
0.74
921
0.85
980
0.95
1034
1.06
1084
1.16
1130
1.26
1171
1.37
1700
671
0.47
746
0.58
817
0.68
884
0.78
947
0.88
1006
0.98
1062
1.09
1113
1.19
1160
1.29
1203
1.39
1800
698
0.52
771
0.62
840
0.72
905
0.83
967
0.93
1025
1.03
1080
1.13
1131
1.24
1178
1.34
1222
1.44
1900
725
0.57
796
0.67
864
0.77
929
0.88
990
0.98
1048
1.09
1102
1.19
1154
1.29
1202
1.40
1246
1.50
2000
753
0.62
822
0.73
888
0.83
952
0.94
1012
1.04
1069
1.15
1123
1.25
1174
1.36
1222
1.46
1267
1.57
2100
782
0.68
849
0.79
913
0.89
975
1.00
1033
1.11
1090
1.21
1143
1.32
1194
1.43
1243
1.54
1288
1.64
2200
809
0.74
874
0.85
936
0.96
997
1.07
1055
1.18
1110
1.29
1164
1.39
1215
1.50
1264
1.61
1310
1.72
2300
837
0.82
900
0.93
960
1.04
1019
1.15
1076
1.26
1132
1.37
1185
1.48
1236
1.59
1285
1.70
1333
1.81
2400
865
0.89
925
1.01
984
1.12
1042
1.23
1098
1.35
1152
1.46
1205
1.57
1256
1.69
1306
1.80
-
-
2500
893
0.98
952
1.09
1009
1.21
1065
1.33
1120
1.44
1173
1.56
1226
1.67
1277
1.79
1327
1.91
-
-